《ASTM F1207M-2012 Standard Specification for Electrical Insulation Monitors for Monitoring Ground Resistance in Active Electrical Systems [Metric]《监视激活电子系统中接地电阻用电绝缘监视器的标准规范 (米制)》.pdf》由会员分享,可在线阅读,更多相关《ASTM F1207M-2012 Standard Specification for Electrical Insulation Monitors for Monitoring Ground Resistance in Active Electrical Systems [Metric]《监视激活电子系统中接地电阻用电绝缘监视器的标准规范 (米制)》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F1207M 12 An American National StandardStandard Specification forElectrical Insulation Monitors for Monitoring GroundResistance in Active Electrical Systems Metric1This standard is issued under the fixed designation F1207M; the number immediately following the designation indicates the
2、year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers electrical insulation moni
3、tor-ing devices intended as permanently installed units for use inthe detection of ohmic insulation faults to ground in active ACungrounded electrical systems.1.2 LimitationsThis specification does not cover deviceswhich are not intended for operation for: DC ungroundedsystems or AC ungrounded syste
4、ms with DC componentsunless AC to DC conversion is isolated from the monitoredsystem with transformers.1.3 The values stated in SI units are to be regarded as thestandard. The values given in parentheses are for informationonly.1.4 The following precautionary caveat pertains only to thetest methods
5、portion, Section 9, of this specification: Thisstandard does not purport to address all of the safety concerns,if any, associated with its use. It is the responsibility of the userof this standard to establish appropriate safety and healthpractices and determine the applicability of regulatory limit
6、a-tions prior to use.2. Referenced Documents2.1 UL Standard:UL 1053 Ground-Fault Sensing and Relaying Equipment23. Terminology3.1 Definitions:3.1.1 AC internal resistancea monitors impedance be-tween the measuring terminals and ground terminals.3.1.2 AC ungrounded electrical systema monitored sys-te
7、m that has no intentional connection from phase or neutral toground and can continue to perform normally if one conductorbecomes connected to ground.3.1.3 DC internal resistancea monitors ohmic resistancebetween the measuring and ground terminals.3.1.4 input voltagethe supply voltage at the terminal
8、s ofan insulation monitor.3.1.5 measuring voltagethe output DC voltage from theinsulation monitor that is superimposed between the ACungrounded system and ground.3.1.6 nominal contact voltagethe voltage rating for amonitors internal relay contacts.3.1.7 nominal frequencythe frequency of a monitoreds
9、ystem.3.1.8 nominal voltagethe voltage (phase-to-phase) of amonitored system.3.1.9 response valuethe adjustable or preset set pointvalue of system insulation resistance for which an insulationmonitor will provide alarm indication.3.1.10 system insulation resistancethe total insulation re-sistance to
10、 ground to be monitored, which is measured by DCvoltage.4. Monitor Classification4.1 Type 1Insulation monitor for 115-V, 3-phase or single-phase, 60-Hz, AC ungrounded electrical systems.4.2 Type 2Insulation monitor for 115-V, 3-phase or single-phase, 400-Hz, AC ungrounded systems.4.3 Type 3Insulatio
11、n monitor for 440-V, 3-phase or single-phase, 60-Hz, AC ungrounded systems.4.4 Type 4Insulation monitor for 440-V, 3-phase or single-phase, 400-Hz, AC ungrounded systems.4.5 Type 5Insulation monitor for up to 1000-V, 3-phase orsingle-phase, 50 to 400-Hz, AC ungrounded systems.5. Ordering Information
12、5.1 Monitoring devices shall be ordered by specifying thefollowing information:5.1.1 Nominal voltage and frequency.5.1.2 Response value/set point range in kilohm.5.1.3 Special options, that is, test buttons, ohmeters, visualindicators, and so forth.1This specification is under the jurisdiction of AS
13、TM Committee F25 on Shipsand Marine Technology and is the direct responsibility of Subcommittee F25.10 onElectrical.Current edition approved Oct. 1, 2012. Published November 2012. Originallyapproved in 1989. Last previous edition approved in 2007 as F1207M - 96(2007).DOI: 10.1520/F1207M-12.2Availabl
14、e from Underwriters Laboratories (UL), 333 Pfingsten Rd.,Northbrook, IL 60062-2096, http:/.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States16. Requirements6.1 The measuring voltage shall not increase more than10 % when the monitor is s
15、upplied with 110 % of the inputvoltage.6.2 The monitor shall be capable of both continuous andon-demand operation.6.3 The monitor shall have provisions for an external(remote) audible or visual alarm to operate when the resistancevalue falls below the response value, or a remote indication ofthe ins
16、ulation value of the AC ungrounded system in kilohms,or both.6.4 The AC internal resistance shall be at least 250-/Vnominal voltage. The minimum resistance shall not be less than15 k.6.5 The DC internal resistance shall be at least 30-/Vnominal voltage and shall limit the measuring DC outputcurrent
17、from exceeding 12 mA.6.6 The monitors response tolerance shall not exceed65 % of the set point value at room temperature (25 6 5C (726 9F) and rated input voltage.6.7 When specified, insulation monitors shall be furnishedwith adjustable response values and designed to precludetampering or unauthoriz
18、ed changes.6.8 The insulation monitor shall function reliably in anambient temperature range from 0 to 50C (32 to 122F).Storage temperatures of 20 to +60C (4 to 140F) must notdamage the insulation monitors.6.9 Insulation monitors shall include a built-in test device orbe equipped with connection pro
19、visions for a test device to befurnished with the equipment which can verify the monitorsproper functioning. If the monitor is equipped with a built-intest device, the value of the test resistor shall be marked on themonitor.6.10 Insulation monitors shall include an integral visualindicator or exter
20、nal connection provisions for external annun-ciation of the monitors set-point response.6.11 If the insulation monitor includes an ohmmeter for theinsulation resistance indication, the meters tolerance (actualrather than indicated values) shall not exceed 65 % for:6.11.1 An insulation monitor with o
21、ne preset response valueat this value.6.11.2 An insulation monitor with adjustable response valueat the midpoint of the adjustment range.6.11.3 Conditions of room temperature (as specified in 6.6)and rated input voltage.6.12 Built-in relays for connection to external alarms shallhave a switching cap
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF1207M2012STANDARDSPECIFICATIONFORELECTRICALINSULATIONMONITORSFORMONITORINGGROUNDRESISTANCEINACTIVEELECTRICALSYSTEMSMETRIC

链接地址:http://www.mydoc123.com/p-534423.html