ASTM F1207M-1996(2007) Standard Specification for Electrical Insulation Monitors for Monitoring Ground Resistance in Active Electrical Systems [Metric]《监测有源系统中地面阻抗的电绝缘监控器的标准规范》.pdf
《ASTM F1207M-1996(2007) Standard Specification for Electrical Insulation Monitors for Monitoring Ground Resistance in Active Electrical Systems [Metric]《监测有源系统中地面阻抗的电绝缘监控器的标准规范》.pdf》由会员分享,可在线阅读,更多相关《ASTM F1207M-1996(2007) Standard Specification for Electrical Insulation Monitors for Monitoring Ground Resistance in Active Electrical Systems [Metric]《监测有源系统中地面阻抗的电绝缘监控器的标准规范》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: F 1207M 96 (Reapproved 2007)METRICAn American National StandardStandard Specification forElectrical Insulation Monitors for Monitoring GroundResistance in Active Electrical Systems Metric1This standard is issued under the fixed designation F 1207M; the number immediately following the d
2、esignation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers
3、electrical insulation monitor-ing devices, intended as permanently installed units, for use inthe detection of ohmic insulation faults to ground in active, acungrounded electrical systems.1.2 LimitationsThis specification does not cover deviceswhich are not intended for operation for: dc ungroundeds
4、ystems or ac ungrounded systems with dc components unlessac to dc conversion is isolated from the monitored system withtransformers.1.3 The values stated in SI units are to be regarded as thestandard. The values given in parentheses are for informationonly.1.4 The following precautionary caveat pert
5、ains only to thetest methods portion, Section 9, of this specification: Thisstandard does not purport to address all of the safety concerns,if any, associated with its use. It is the responsibility of the userof this standard to establish appropriate safety and healthpractices and determine the appl
6、icability of regulatory limita-tions prior to use.2. Referenced Documents2.1 UL Standard:UL 1053 Ground-Fault Sensing and Relaying Equipment23. Terminology3.1 Definitions:3.1.1 ac internal resistancea monitors impedance be-tween the measuring terminals and ground terminals.3.1.2 ac ungrounded electr
7、ical systema monitored systemthat has no intentional connection from phase or neutral toground and can continue to perform normally if one conductorbecomes connected to ground.3.1.3 dc internal resistancea monitors ohmic resistancebetween the measuring and ground terminals.3.1.4 input voltagethe sup
8、ply voltage at the terminals ofan insulation monitor.3.1.5 measuring voltagethe output dc voltage from theinsulation monitor that is superimposed between the ac un-grounded system and ground.3.1.6 nominal contact voltagethe voltage rating for amonitors internal relay contacts.3.1.7 nominal frequency
9、the frequency of a monitoredsystem.3.1.8 nominal voltagethe voltage (phase-to-phase) of amonitored system.3.1.9 response valuethe adjustable or preset set pointvalue of system insulation resistance for which an insulationmonitor will provide alarm indication.3.1.10 system insulation resistancethe to
10、tal insulationresistance to ground to be monitored which is measured by dcvoltage.4. Monitor Classification4.1 Type 1Insulation monitor for 115-V, 3-phase orsingle-phase, 60-Hz, ac ungrounded electrical systems.4.2 Type 2Insulation monitor for 115-V, 3-phase orsingle-phase, 400-Hz, ac ungrounded sys
11、tems.4.3 Type 3Insulation monitor for 440-V, 3-phase orsingle-phase, 60-Hz, ac ungrounded systems.4.4 Type 4Insulation monitor for 440-V, 3-phase orsingle-phase, 400-Hz, ac ungrounded systems.1This specification is under the jurisdiction of ASTM Committee F25 on Shipsand Marine Technology and is the
12、 direct responsibility of Subcommittee F25.10 onElectrical.Current edition approved May 1, 2007. Published June 2007. Originallyapproved in 1989. Last previous edition approved in 2002 as F 1207M - 96(2002).2Available from Underwriters Laboratories (UL), 333 Pfingsten Rd., North-brook, IL 60062-2096
13、, http:/.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.4.5 Type 5Insulation monitor for up to 1000-V, 3-phase orsingle-phase, 50 to 400-Hz, ac ungrounded systems.5. Ordering Information5.1 Monitoring devices shall be ordered by spe
14、cifying thefollowing information:5.1.1 Nominal voltage and frequency.5.1.2 Response value/set point range in kilohm.5.1.3 Special options, that is, test buttons, ohmeters, visualindicators, and so forth.6. Requirements6.1 The measuring voltage shall not increase more than10 % when the monitor is sup
15、plied with 110 % of the inputvoltage.6.2 The monitor shall be capable of both continuous andon-demand operation.6.3 The monitor shall have provisions for an external(remote) audible or visual alarm to operate when the resistancevalue falls below the response value or a remote indication ofthe insula
16、tion value of the ac ungrounded system in kilohms, orboth.6.4 The ac internal resistance shall be at least 250-V/Vnominal voltage. The minimum resistance shall not be less than15 kV.6.5 The dc internal resistance shall be at least 30-V/Vnominal voltage and shall limit the measuring dc output current
17、from exceeding 12 mA.6.6 The monitors response tolerance shall not exceed65 % of the set point value at room temperature (25 6 5C (726 9F) and rated input voltage.6.7 When specified, insulation monitors shall be furnishedwith adjustable response values and designed to precludetampering or unauthoriz
18、ed changes.6.8 The insulation monitor shall reliably function in anambient temperature range from 0 to 50C (32 to 122F).Storage temperatures of 20 to +60C (4 to 140F) must notdamage the insulation monitors.6.9 Insulation monitors shall include a built-in test device orbe equipped with connection pro
19、visions for a test device to befurnished with the equipment which can verify the monitorsproper functioning. If the monitor is equipped with a built-intest device, the value of the test resistor shall be marked on themonitor.6.10 Insulation monitors shall include an integral visualindicator or exter
20、nal connection provisions for external annun-ciation of the monitors set-point response.6.11 If the insulation monitor includes an ohmmeter for theinsulation resistance indication, the meters tolerance (actualrather than indicated values) shall not exceed 65 % for:6.11.1 An insulation monitor with o
21、ne preset response valueat this value.6.11.2 An insulation monitor with adjustable response valueat the midpoint of the adjustment range.6.11.3 Conditions of room temperature (as specified in 6.6)and rated input voltage.6.12 Built-in relays for connection to external alarms shallhave a switching cap
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMF1207M19962007STANDARDSPECIFICATIONFORELECTRICALINSULATIONMONITORSFORMONITORINGGROUNDRESISTANCEINACTIVEELECTRICALSYSTEMSMETRIC

链接地址:http://www.mydoc123.com/p-534422.html