ASTM E761 E761M-1992(2015)e1 0526 Standard Test Method for Compressive Strength of Sprayed Fire-Resistive Material Applied to Structural Members《结构构件上喷涂防火材料抗压强度的标准试验方法》.pdf
《ASTM E761 E761M-1992(2015)e1 0526 Standard Test Method for Compressive Strength of Sprayed Fire-Resistive Material Applied to Structural Members《结构构件上喷涂防火材料抗压强度的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM E761 E761M-1992(2015)e1 0526 Standard Test Method for Compressive Strength of Sprayed Fire-Resistive Material Applied to Structural Members《结构构件上喷涂防火材料抗压强度的标准试验方法》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E761/E761M 92 (Reapproved 2015)1Standard Test Method forCompressive Strength of Sprayed Fire-Resistive MaterialApplied to Structural Members1This standard is issued under the fixed designation E761/E761M; the number immediately following the designation indicates the yearof original ado
2、ption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval.A superscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the U.S. Department of Defen
3、se.1NOTEDesignation was changed to dual and units information was corrected editorially in August 2015.1. Scope1.1 This test method covers a procedure for measuring thecompressive strength of sprayed fire-resistive material (SFRM)applied to a rigid substrate. These fire-resistive materialsinclude sp
4、rayed fibrous and cementitious materials applieddirectly in contact with these structural members. The testmethod is applicable to laboratory procedure.1.2 The values stated in either SI units or inch-pound unitsare to be regarded separately as standard. The values stated ineach system may not be ex
5、act equivalents; therefore, eachsystem shall be used independently of the other. Combiningvalues from the two systems may result in non-conformancewith the standard.1.3 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of th
6、e user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2D2092 Guide for Preparation of Zinc-Coated (Galvanized)Steel Surfaces for Painting (Withdrawn 2008)3E84 Tes
7、t Method for Surface Burning Characteristics ofBuilding MaterialsE119 Test Methods for Fire Tests of Building Constructionand MaterialsE605/E605M Test Methods for Thickness and Density ofSprayed Fire-Resistive Material (SFRM) Applied toStructural Members3. Summary of Test Method3.1 The compressive s
8、trength of SFRM applied to a steelsheet is determined by applying a crushing load normal to thesurface of the specimen. This test method measures the stressat 10 % deformation or at failure, whichever is smaller.4. Significance and Use4.1 The intent of this test method is to determine propertiesof d
9、irect-applied SFRM that may be used to provide anindication of serviceability. Satisfactory performance of fire-resistive material applied to structural members and assembliesdepends upon its ability while in place to withstand the variousinfluences that may occur during the life of the structure, a
10、swell as upon its satisfactory performance under fire tests.4.2 This test method measures the compressive strength ofSFRM and is a measure of the resistance to deformation undera compressive load. It is an indication of the ability of SFRMto remain in place and resist removal during anticipated serv
11、iceconditions.5. Apparatus5.1 Testing MachineAny form of standard hydraulic ormechanical compression testing machine accurate to 0.005 kg0.01 lb and 0.25 mm 0.001 in.5.2 Spherical Bearing Block Assembly, having a planebearing surface of 150 mm 6 in. square. The upper bearingshall be a spherically se
12、ated, hardened metal block firmlyattached at the center of the upper head of the machine. Thecenter of the sphere shall lie at the center of the surface held inits spherical seat, but shall be free to turn in any direction, andits perimeter shall have at least 6-mm 14-in. clearance fromthe head to a
13、llow for specimens whose bearing surfaces are notexactly parallel (see Fig. 1).1This test method is under the jurisdiction of ASTM Committee E06 onPerformance of Buildings and is the direct responsibility of Subcommittee E06.21on Serviceability.Current edition approved Aug. 1, 2015. Published August
14、 2015. Originallyapproved in 1980. Last previous edition approved in 2011 as E761 92 (2011).DOI: 10.1520/E0761-92R15E01.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer
15、 to the standards Document Summary page onthe ASTM website.3The last approved version of this historical standard is referenced onwww.astm.org.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States15.3 Drying Oven, capable of maintaining tem
16、perature andhumidity conditions during the specimen curing cycle, inaccordance with the SFRM manufacturers published require-ments.6. Materials and Manufacture6.1 This test method requires the application of SFRM inaccordance with manufacturers published instructions. Theapparatus, materials, and pr
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME761E761M19922015E10526STANDARDTESTMETHODFORCOMPRESSIVESTRENGTHOFSPRAYEDFIRERESISTIVEMATERIALAPPLIEDTOSTRUCTURALMEMBERS

链接地址:http://www.mydoc123.com/p-533472.html