《ASTM E759-1992(2011) 9375 Standard Test Method for Effect of Deflection on Sprayed Fire-Resistive Material Applied to Structural Members《挠曲对结构构件上喷涂的防火材料影响的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM E759-1992(2011) 9375 Standard Test Method for Effect of Deflection on Sprayed Fire-Resistive Material Applied to Structural Members《挠曲对结构构件上喷涂的防火材料影响的标准试验方法》.pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E759 92 (Reapproved 2011)Standard Test Method forEffect of Deflection on Sprayed Fire-Resistive MaterialApplied to Structural Members1This standard is issued under the fixed designation E759; the number immediately following the designation indicates the year oforiginal adoption or, in
2、the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 Thi
3、s test method covers a procedure for determining theeffect of deflection on sprayed fire-resistive material (SFRM)applied to steel deck. These materials include sprayed fibrousand cementitious materials applied directly in contact with thestructural members. The test method is applicable only tolabo
4、ratory procedures.1.2 The values stated in SI units are to be regarded asstandard. The values given in parentheses are mathematicalconversions to inch-pound units that are provided for informa-tion only and are not considered standard.1.3 This standard does not purport to address all of thesafety co
5、ncerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2E84 Test Method for Surface Burning C
6、haracteristics ofBuilding MaterialsE119 Test Methods for Fire Tests of Building Constructionand MaterialsE605 Test Methods for Thickness and Density of SprayedFire-Resistive Material (SFRM) Applied to StructuralMembers3. Summary of Test Method3.1 In this test method, a cellular steel deck panel spra
7、yedwith fire-resistive material is subjected to bending by a verticalcenter load while supported horizontally at its ends.4. Significance and Use4.1 The intent of this test method is to determine propertiesof direct-applied SFRM that may be used to provide anindication of serviceability. Satisfactor
8、y performance of fire-resistive material applied to structural members and assembliesdepends upon its ability while in place to withstand the variousinfluences that may occur during the life of the structure, aswell as upon its satisfactory performance under fire tests.4.2 This test method measures
9、the behavior of SFRM whensubjected to deflection and evaluates such phenomena asspalling and delamination under bending stress. It is anindication of the ability of SFRM to remain in place and resistremoval during anticipated service conditions.5. Apparatus5.1 SupportsRigid base to provide at least
10、50 mm (2 in.)bearing and a clear span between supports of 3 m (10 ft).5.2 Bearing BlockApproximately 50 mm (2 in.) wide,minimum 600 mm (24 in.) long bearing surface designed todistribute the load across the width of the specimen.5.3 LoadAny form of weights or testing machine capableof applying a loa
11、d normal to the test surface and of developinga deflection of1120 of the clear span of the specimen.5.4 Deflection Gage A dial or digital micrometer gradu-ated to 0.01 mm (0.001 in.).6. Materials and Manufacture6.1 The specimen shall consist of cellular steel deck nomi-nal 40 mm (112 in.) deep, 600
12、mm (24 in.) wide, by 3600 mm(12 ft) long, consisting of a 1.5 mm (0.060 in. (18 ga.) thickgalvanized steel fluted top section and a 1.2-mm (0.048-in.)galvanized steel flat bottom section welded together to formfour cells 150 mm (6 in.) on center.6.2 This test method requires the application of SFRM
13、inaccordance with manufacturers published instructions. Theapparatus, materials, and procedures used to apply the SFRMfor this test shall be representative of application in the field.6.3 The density of the prepared sample shall be similar tothe density tested and reported during the Test Methods E8
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME759199220119375STANDARDTESTMETHODFOREFFECTOFDEFLECTIONONSPRAYEDFIRERESISTIVEMATERIALAPPLIEDTOSTRUCTURALMEMBERS

链接地址:http://www.mydoc123.com/p-533468.html