ASTM E741-2000(2006) Standard Test Method for Determining Air Change in a Single Zone by Means of a Tracer Gas Dilution《用示踪气体稀释法测定单区内空气变化的标准测试方法》.pdf
《ASTM E741-2000(2006) Standard Test Method for Determining Air Change in a Single Zone by Means of a Tracer Gas Dilution《用示踪气体稀释法测定单区内空气变化的标准测试方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM E741-2000(2006) Standard Test Method for Determining Air Change in a Single Zone by Means of a Tracer Gas Dilution《用示踪气体稀释法测定单区内空气变化的标准测试方法》.pdf(17页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E 741 00 (Reapproved 2006)Standard Test Method forDetermining Air Change in a Single Zone by Means of aTracer Gas Dilution1This standard is issued under the fixed designation E 741; the number immediately following the designation indicates the year oforiginal adoption or, in the case o
2、f revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method covers techniques using tracer gasdilution for determining a single zones ai
3、r change with theoutdoors, as induced by weather conditions and by mechanicalventilation. These techniques are: (1) concentration decay, (2)constant injection, and (3) constant concentration.1.2 This test method is restricted to any single tracer gas.The associated data analysis assumes that one can
4、 characterizethe tracer gas concentration within the zone with a single value.The zone shall be a building, vehicle, test cell, or anyconforming enclosure.1.3 Use of this test method requires a knowledge of theprinciples of gas analysis and instrumentation. Correct use ofthe formulas presented here
5、requires consistent use of units,especially those of time.1.4 Determination of the contribution to air change byindividual components of the zone enclosure is beyond thescope of this test method.1.5 The results from this test method pertain only to thoseconditions of weather and zonal operation that
6、 prevailed duringthe measurement. The use of the results from this test to predictair change under other conditions is beyond the scope of thistest method.1.6 The text of this test method references notes andfootnotes which provide explanatory material. These notes andfootnotes (excluding those in t
7、ables and figures) shall not beconsidered requirements of this test method.1.7 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determin
8、e the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2D 4480 Test MEthod for MEasuring Surface Wind byMeans of Wind Vanes and Rotating Anemometers3E 260 Practice for Packed Column Gas ChromatographyE 779 Test Method for Determining Air Leakage Rate by
9、Fan PressurizationE 1186 Practices forAir Leakage Site Detection in BuildingEnvelopes and Air Barrier Systems2.2 Other Documents:ASHRAE Handbook of Fundamentals, Chapter 234ASHRAE Standard 6243. Terminology3.1 Definitions of Terms Specific to This Standard:3.1.1 air change flow, Q, nthe total volume
10、 of air passingthrough the zone to and from the outdoors per unit time (m3/s,m3/h, ft3/h).3.1.2 air change rate, A, nthe ratio of the total volume ofair passing through the zone to and from the outdoors per unitof time to the volume of the zone (1/s, 1/h).53.1.3 envelope, nthe system of barriers bet
11、ween a condi-tioned building zone and the outdoors.3.1.3.1 DiscussionThis includes exterior doors, windows,roofs, walls, floors and ductwork. It excludes interior parti-tions, ducts, and so forth, that separate conditioned zones.3.1.4 tracer gas, na gas that is mixed with air andmeasured in very sma
12、ll concentrations in order to study airmovement.3.1.5 tracer gas analyzer, na device used to measure theconcentration of tracer gas in an air sample.1This test method is under the jurisdiction of ASTM Committee E06 onPerformance of Buildings and is the direct responsibility of Subcommittee E06.41on
13、Air Leakage and Ventilation.Current edition approved Oct. 1, 2006. Published October 2006. Originallyapproved in 1980. Last previous edition approved in 2000 as E 741 00.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annu
14、al Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Withdrawn.4Available from American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. (ASHRAE), 1791 Tullie Circle, NE, Atlanta, GA30329, http:/www.ashrae.org.5A common
15、way of expressing air change rate units is ACH = air changes perhour = 1/h.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.3.1.6 tracer gas concentration, C, nthe ratio of thequantity of tracer gas in air to the quantity of that air(
16、moles/mole or m3/m3).3.1.7 single zone, na space or set of spaces wherein theconcentration of a tracer gas is maintained uniformly through-out and that only exchanges air with the outside.3.1.7.1 DiscussionMultizone buildings are difficult totreat as single zones and meet the uniformity of tracer ga
17、sconcentration required in this test method. Single zones withinmultizone buildings are difficult to isolate such that theyexchange air only with the outside and not to other zoneswithin the building via ventilation ducts, electrical conduits,elevator shafts, stairs, and other pathways.3.2 Symbols:3
18、.2.1 Variables:A = air change rate (1/s, 1/h).C = concentration (dimensionless).CONF = confidence limit value (units of the variable mea-sured).d = desired precision (dimensionless).ESE = estimated standard error.i = location number.k = constant.n = number of data points.N = number of sampling locat
19、ions in the zone.Q = flow (m3/s, m3/h, ft3/h).s = sample standard deviation (units of the variableestimated).t = a specific time (s, h).T = a period of time (s, h).V = volume (m3,ft3).a = probability (dimensionless).e = error (units of the variable estimated).n = coefficient of variation (dimensionl
20、ess).3.2.2 Superscripts:8 = value at the end of the test. = mean value.3.2.3 Subscripts:A = pertaining to air change rate.avg = average.bias = pertaining to bias.C = pertaining to concentration.est = estimated.GA = pertaining to the gas analyzer.i = pertaining to time or location.inj = pertaining to
21、 the injection period.lower = lower limit.meas = pertaining to the measurement.mix = pertaining to the mixing period.precis = pertaining to precision.rep = pertaining to replicates.sample = pertaining to a discrete tracer gas or air sample.target = pertaining to the desired level of tracer gas.test
22、= pertaining to the test period.twt = weighted according to tracer gas flow.tracer = pertaining to the tracer gas.upper = upper limit.vol = pertaining to the volume of the zone.zone = pertaining to the zone under study.1 = first occurrence under discussion.2 = last occurrence under discussion.3.2.4
23、Other Notations:Dt = time interval between periodic samples.(t) = function of time.(t, i) = function of time, t, and location, i.t(n,1a)= t-distribution value for n degrees of freedomand a two-sided probability of a.4. Summary of Test Method4.1 This test method uses the measurement of tracer gasdilu
24、tion to determine air change within a building or otherenclosure that is characterized as a single zone. The measure-ment of the concentration, and sometimes the volume rate ofthe tracer gas that is injected into the zone, allows calculationof the volume rate of outgoing air from the zone. From this
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME74120002006STANDARDTESTMETHODFORDETERMININGAIRCHANGEINASINGLEZONEBYMEANSOFATRACERGASDILUTION 用示踪

链接地址:http://www.mydoc123.com/p-533433.html