ASTM E580 E580M-2006 Standard Practice for Application of Ceiling Suspension Systems for Acoustical Tile and Lay-in Panels in Areas Requiring Seismic Restraint.pdf
《ASTM E580 E580M-2006 Standard Practice for Application of Ceiling Suspension Systems for Acoustical Tile and Lay-in Panels in Areas Requiring Seismic Restraint.pdf》由会员分享,可在线阅读,更多相关《ASTM E580 E580M-2006 Standard Practice for Application of Ceiling Suspension Systems for Acoustical Tile and Lay-in Panels in Areas Requiring Seismic Restraint.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E 580/E 580M 06Standard Practice forApplication of Ceiling Suspension Systems for AcousticalTile and Lay-in Panels in Areas Requiring Seismic Restraint1This standard is issued under the fixed designation E 580/E 580M; the number immediately following the designation indicates the yearof
2、 original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval.A superscript epsilon (e) indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department
3、 of Defense.1. Scope1.1 This practice covers acoustical ceiling suspension sys-tems and their additional requirements for application in areassubject to light to moderate seismic disturbance such asUniform Building Code Seismic Zone 2, the BOCA BasicNational Building Code where Avis less than 0.20 b
4、ut greaterthan 0.10, and the Standard Building Code (SBC) where Avisless than 0.20 but greater than 0.05. This practice also coversareas subject to moderate to severe seismic disturbance such asUniform Building Code Seismic Zones 3 and 4, the BOCABasic National Building Code where Avis greater than
5、0.20,and the SBC where Avis greater than 0.20. The application ofthis practice is to be determined by local authorities. Currentseismic maps published by recognized authorities such as thosepreviously mentioned, should be consulted. Related materialsuch as Open File 82-10332and MS-812 Seismicity Map
6、3mayalso be consulted.1.2 Specification C 635 and Practice C 636 cover suspen-sion systems and their application without special regard toseismic restraint needs. They remain applicable and should befollowed when this practice is specified.1.3 This practice is not intended to stifle research anddeve
7、lopment of new products or methods which may simplifythis specified application method. A variation, however, mustbe substantiated by verifiable engineering data.1.4 A ceiling area of 144 ft213m2 or less, surrounded bywalls that connect directly to the structure above shall beexempt from this practi
8、ce.1.5 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.1.6 The valu
9、es stated in either inch-pound or SI units are tobe regarded as standard. Within the text, the SI units are shownin brackets. The values stated in each system are not exactequivalents; therefore, each system must be used indepen-dently of the other. Combining values from the two systemsmay result in
10、 nonconformance with the specification.2. Referenced Documents2.1 ASTM Standards:4C 635 Specification for the Manufacture, Performance, andTesting of Metal Suspension Systems for Acoustical Tileand Lay-in Panel CeilingsC 636 Practice for Installation of Metal Ceiling SuspensionSystems for Acoustical
11、 Tile and Lay-In Panels2.2 Other Standards:National Electric Code, 19935Uniform Building Code, 19946BOCA Basic Building Code, 199373. Areas Subject to Light to Moderate SeismicDisturbance3.1 Suspension System Components:3.1.1 The actual average weight of the ceiling system,including grid, panel or t
12、ile, light fixtures, and air terminalsmust be 2.5 lb/ft212 N/m2 or less. All other services must besupported independently from the ceiling system. For ceilingsthat have an average weight greater than 2.5 lb/ft212 N/m2,the ceiling may be installed as specified in Section 4. Otherdeviations or variat
13、ions must be substantiated by verifiableengineering data.3.1.2 The main runners and cross runners of the ceilingsystem and their splices, intersection connectors, and expan-sion devices shall be designed and constructed to carry a mean1This practice is under the jurisdiction of ASTM Committee E33 on
14、 Environ-mental Acoustics and is the direct responsibility of Subcommittee E33.04 onApplication.Current edition approved July 15, 2006. Published July 2006. Originallyapproved in 1976. Last previous edition approved in 2002 as E 580 02e1.2Open File 82-1033 Probabilistic Estimate of Maximum Accelerat
15、ion in Rockpublished by United States Geological Survey.3MS-8125 Seismicity Map of the Conterminous United States and AdjacentAreas, 19651974 published by United States Geological Survey.4For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at servicea
16、stm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.5Available from National Fire Protection Association, Batterymarch Park,Quincy, MA 02269.6Available from International Conference of Building Officials, 5360 S. Work-man Mill
17、 Rd., Whittier, CA 90601.7Available from Building Officials and Code Administrators International, 4051W. Flossmoor Rd., Country Club Hills, IL 60477.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.ultimate test load of not less than
18、 60 lb 27 kg in tension witha 5 misalignment of the members in any direction and incompression. Instead of a 5 misalignment, the load may beapplied with a 1-in. 25mm eccentricity on a sample not morethan 24 in. 600 mm long on each side of the splice.3.1.3 Evaluation of test results shall be made on
19、the basis ofthe mean values resulting from tests of not fewer than threeidentical specimens, provided the deviation of any individualtest result from the mean value does not exceed 610 %.3.2 Suspension System Application:3.2.1 All perimeter closure angles or channels shall providea support ledge of
20、approximately78 in. 22 mm or greater.3.2.2 The end of a grid member (or tile) that rests on theledge or molding shall have at least38-in. 10 mm clearancefrom an edge or wall as shown in Fig. 1. Reveal (shadow) edgewall closures should accommodate these clearances as shownin Fig. 2. Ends of main runn
21、ers and cross members shall be tiedtogether to prevent their spreading.3.2.3 Direct concealed suspended ceiling systems shall havepositively connected stabilizer struts or mechanically con-nected cross runner at a maximum spacing of 60 in. 1500 mmperpendicular to the main runners (see Fig. 3). Stabi
22、lizer barsshall occur within 24 in. 600 mm of each wall.3.2.4 Suspension Wire Application:3.2.4.1 Suspension wires of soft, annealed, galvanized steelwire shall not be smaller than No. 12 gage 2.70 mm spacedat 4 ft 1200 mm on center or No. 10 gage 3.40 mm at 5 ft1500 mm on center along each main run
23、ner unless calcula-tions justifying the increased spacing are provided.3.2.4.2 Each vertical wire shall be attached to the ceilingsuspension member and to the support above with a minimumof three turns with a connection device capable of carrying notless than a 100-lb 45 kg allowable load.3.2.4.3 Su
24、spension wires shall not hang more than one in sixout of plumb unless countersloping wires are provided.3.2.4.4 Wires shall not attach to or bend around interferingmaterial or equipment. A trapeze or equivalent device shall beused where obstructions preclude direct suspension. Trapezesuspensions sha
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME580E580M2006STANDARDPRACTICEFORAPPLICATIONOFCEILINGSUSPENSIONSYSTEMSFORACOUSTICALTILEANDLAYINPANELSINAREASREQUIRINGSEISMICRESTRAINTPDF

链接地址:http://www.mydoc123.com/p-533080.html