《ASTM E502-2007(2013) 1250 Standard Test Method for Selection and Use of ASTM Standards for the Determination of Flash Point of Chemicals by Closed Cup Methods《采用密闭杯测定化学品闪点用ASTM标准的选.pdf》由会员分享,可在线阅读,更多相关《ASTM E502-2007(2013) 1250 Standard Test Method for Selection and Use of ASTM Standards for the Determination of Flash Point of Chemicals by Closed Cup Methods《采用密闭杯测定化学品闪点用ASTM标准的选.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E502 07 (Reapproved 2013)Standard Test Method forSelection and Use of ASTM Standards for the Determinationof Flash Point of Chemicals by Closed Cup Methods1This standard is issued under the fixed designation E502; the number immediately following the designation indicates the year ofori
2、ginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method covers the determination of the flashpoint of
3、 liquid and solid chemical compounds flashing frombelow 10 to 370C (16 to 700F). The procedures andapparatus in Test Methods D56, D93, D3278, D3828, andD3941 are to be used. Modification to these procedures arespecified for tests on solids and viscous liquids. The signifi-cance of the results obtain
4、ed is discussed along with possiblesources of error and factors that might cause interference.1.2 Suggestions for adapting this procedure to mixtures ofchemicals are included (see Appendix X2).1.3 This test method should be used to measure and describethe properties of materials, products, or assemb
5、lies in responseto heat and flame under controlled laboratory conditions andshould not be used to describe or appraise the fire hazard or firerisk of materials or assemblies under actual fire conditions.However, results of this test method may be used as elementsof a fire risk assessment that take i
6、nto account all of the factorsthat are pertinent to an assessment of the fire hazard of aparticular end use.1.4 WarningMercury has been designated by EPA andmany state agencies as a hazardous material that can causecentral nervous system, kidney and liver damage. Mercury, orits vapor, may be hazardo
7、us to health and corrosive tomaterials. Caution should be taken when handling mercury andmercury containing products. See the applicable product Ma-terial Safety Data Sheet (MSDS) for details and EPAs website http:/www.epa.gov/mercury/faq.htm - for additional infor-mation. Users should be aware that
8、 selling mercury and/ormercury containing products into your state may be prohibitedby state law.1.5 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health
9、practices and determine the applica-bility of regulatory limitations prior to use. See also Section 8.2. Referenced Documents2.1 ASTM Standards:2D56 Test Method for Flash Point by Tag Closed Cup TesterD92 Test Method for Flash and Fire Points by ClevelandOpen Cup TesterD93 Test Methods for Flash Poi
10、nt by Pensky-MartensClosed Cup TesterD270 Methods of Sampling Petroleum and Petroleum Prod-ucts (Withdrawn 1984)3D1310 Test Method for Flash Point and Fire Point of Liquidsby Tag Open-Cup ApparatusD3278 Test Methods for Flash Point of Liquids by SmallScale Closed-Cup ApparatusD3827 Test Method for E
11、stimation of Solubility of Gases inPetroleum and Other Organic LiquidsD3828 Test Methods for Flash Point by Small Scale ClosedCup TesterD3934 Test Method for Flash/No Flash TestEquilibriumMethod by a Closed-Cup ApparatusD3941 Test Method for Flash Point by the EquilibriumMethod With a Closed-Cup App
12、aratusE681 Test Method for Concentration Limits of Flammabilityof Chemicals (Vapors and Gases)E1232 Test Method for Temperature Limit of Flammabilityof Chemicals3. Terminology3.1 Definitions:3.1.1 flash pointthe lowest temperature, corrected to apressure of 760 mm Hg (101.3 kPa) (1013 mbar) at which
13、application of an ignition source causes the vapors of aspecimen to ignite under specified conditions of test.1This test method is under jurisdiction of ASTM Committee E27 on HazardPotential of Chemicals and is the direct responsibility of Subcommittee E27.04 onFlammability and Ignitability of Chemi
14、cals.Current edition approved Oct. 1, 2013. Published October 2013. Originallyapproved in 1984. Last previous edition approved in 2007 as E502 071. DOI:10.1520/E0502-07R13.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For An
15、nual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3The last approved version of this historical standard is referenced onwww.astm.org.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. Unite
16、d States14. Summary of Test Method4.1 The specimen is placed in a closed cup and in the smallscale method equilibrated at a test temperature, in the Pensky-Martens Method heated at a controlled rate with stirring, and inthe Tag Method also heated at a controlled rate but withoutstirring. A small fla
17、me is directed into the vapor space of eachcup at specified intervals, with simultaneous interruption ofstirring in the Pensky-Martens Method, to determine whether aflash occurs or not. In Test Method D3941, the specimen isheated at a slower rate than in the other controlled heatingmethods, maintain
18、ing a small temperature differential betweenbath and specimen.5. Significance and Use5.1 The flash point measures the response of the sample toheat and flame under controlled laboratory conditions. It isonly one of a number of properties that must be considered inassessing the overall flammability h
19、azard of a material.5.2 As a result of physical factors inherent in the apparatusand procedure, the closed cup flash point does not necessarilyrepresent the minimum temperature at which a material canevolve flammable vapors, and the absence of a flash point doesnot guarantee nonflammability (see App
20、endix X1 and Appen-dix X2).5.3 Flash point is used in shipping and safety regulations todefine flammable and combustible materials. Test MethodsD56, D93, and D3278 are specified as test methods fordetermining the flash point of these materials.5.4 If the process or handling conditions dictate the us
21、age ofa flammable material at temperatures ranging upward from 5 to10C below the closed-cup flash point, then a flammable vapormight be present above the liquid. In such cases, it may bemore appropriate to use the temperature limit of flammability(as determined by Test Method E1232) instead of flash
22、 point.5.5 Small scale methods involving equilibrium proceduresand only one flame pass per specimen are preferred.6. Interferences6.1 Incorrect flash points can be obtained when testingchemicals corrosive to the materials of construction of the cup.(For example, certain amines and acid chlorides rea
23、ct with thestandard aluminum small scale cup causing erroneously lowflash points, perhaps due to hydrogen formation.) Cups em-ploying alternative materials of construction, electroplating orplastic coating can provide corrosion resistance. Results innon-standard cups, particularly in non-equilibrium
24、 tests, maydiffer slightly from those obtained in this test method.7. Apparatus7.1 Tag Closed-Cup Tester, including thermometers, shall beas shown in Test Methods D56 and D3941.7.2 Penksy-Martens Closed-Cup Tester, includingthermometers, shall be as shown in Test Methods D93.7.3 Small scale Closed T
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME502200720131250STANDARDTESTMETHODFORSELECTIONANDUSEOFASTMSTANDARDSFORTHEDETERMINATIONOFFLASHPOINTOFCHEMICALSBYCLOSEDCUPMETHODS

链接地址:http://www.mydoc123.com/p-532899.html