ASTM E502-2007 Standard Test Method for Selection and Use of ASTM Standards for the Determination of Flash Point of Chemicals by Closed Cup Methods《用闭杯法测定化学制品闪点时选择和使用ASTM标准的标准试验方法》.pdf
《ASTM E502-2007 Standard Test Method for Selection and Use of ASTM Standards for the Determination of Flash Point of Chemicals by Closed Cup Methods《用闭杯法测定化学制品闪点时选择和使用ASTM标准的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM E502-2007 Standard Test Method for Selection and Use of ASTM Standards for the Determination of Flash Point of Chemicals by Closed Cup Methods《用闭杯法测定化学制品闪点时选择和使用ASTM标准的标准试验方法》.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E 502 07Standard Test Method forSelection and Use of ASTM Standards for the Determinationof Flash Point of Chemicals by Closed Cup Methods1This standard is issued under the fixed designation E 502; the number immediately following the designation indicates the year oforiginal adoption o
2、r, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method covers the determination of the flashpoint of liquid and sol
3、id chemical compounds flashing frombelow 10 to 370C (16 to 700F). The procedures andapparatus in Test Methods D 56, D 93, D 3278, D 3828, andD 3941 are to be used. Modification to these procedures arespecified for tests on solids and viscous liquids. The signifi-cance of the results obtained is disc
4、ussed along with possiblesources of error and factors that might cause interference.1.2 Suggestions for adapting this procedure to mixtures ofchemicals are included (see Appendix X2).1.3 This test method should be used to measure and describethe properties of materials, products, or assemblies in re
5、sponseto heat and flame under controlled laboratory conditions andshould not be used to describe or appraise the fire hazard or firerisk of materials or assemblies under actual fire conditions.However, results of this test method may be used as elementsof a fire risk assessment that take into accoun
6、t all of the factorsthat are pertinent to an assessment of the fire hazard of aparticular end use.1.4 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health
7、 practices and determine the applica-bility of regulatory limitations prior to use. See also Section 8.2. Referenced Documents2.1 ASTM Standards:2D56 Test Method for Flash Point by Tag Closed Cup TesterD92 Test Method for Flash and Fire Points by ClevelandOpen Cup TesterD93 Test Methods for Flash Po
8、int by Pensky-MartensClosed Cup TesterD 270 Method of Sampling Petroleum and Petroleum Prod-ucts3D 1310 Test Method for Flash Point and Fire Point ofLiquids by Tag Open-Cup ApparatusD 3278 Test Methods for Flash Point of Liquids by SmallScale Closed-Cup ApparatusD 3827 Test Method for Estimation of
9、Solubility of Gasesin Petroleum and Other Organic LiquidsD 3828 Test Methods for Flash Point by Small Scale ClosedCup TesterD 3934 Test Method for Flash/No Flash TestEquilibriumMethod by a Closed-Cup ApparatusD 3941 Test Method for Flash Point by the EquilibriumMethod With a Closed-Cup ApparatusE 68
10、1 Test Method for Concentration Limits of Flammabil-ity of Chemicals (Vapors and Gases)E 1232 Test Method for Temperature Limit of Flammabilityof Chemicals3. Terminology3.1 Definition:3.1.1 flash pointthe lowest temperature, corrected to apressure of 760 mm Hg (101.3 kPa) (1013 mbar) at whichapplica
11、tion of an ignition source causes the vapors of aspecimen to ignite under specified conditions of test.4. Summary of Test Method4.1 The specimen is placed in a closed cup and in the smallscale method equilibrated at a test temperature, in the Pensky-Martens Method heated at a controlled rate with st
12、irring, and inthe Tag Method also heated at a controlled rate but withoutstirring. A small flame is directed into the vapor space of eachcup at specified intervals, with simultaneous interruption ofstirring in the Pensky-Martens Method, to determine whether aflash occurs or not. In Test Method D 394
13、1, the specimen is1This test method is under jurisdiction of ASTM Committee E27 on HazardPotential of Chemicals and is the direct responsibility of Subcommittee E27.04 onFlammability and Ignitability of Chemicals.Current edition approved Jan. 15, 2007. Published March 2007. Originallyapproved in 198
14、4. Last previous edition approved in 2006 as E 50206a.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Withdr
15、awn.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.heated at a slower rate than in the other controlled heatingmethods, maintaining a small temperature differential betweenbath and specimen.5. Significance and Use5.1 The flash point
16、 measures the response of the sample toheat and flame under controlled laboratory conditions. It isonly one of a number of properties that must be considered inassessing the overall flammability hazard of a material.5.2 As a result of physical factors inherent in the apparatusand procedure, the clos
17、ed cup flash point does not necessarilyrepresent the minimum temperature at which a material canevolve flammable vapors, and the absence of a flash point doesnot guarantee nonflammability (see Appendix X1 and Appen-dix X2).5.3 Flash point is used in shipping and safety regulations todefine flammable
18、 and combustible materials. Test MethodsD 56, D 93, and D 3278 are specified as test methods fordetermining the flash point of these materials.5.4 If the process or handling conditions dictate the usage ofa flammable material at temperatures ranging upward from 5 to10C below the closed-cup flash poi
19、nt, then a flammable vapormight be present above the liquid. In such cases, it may bemore appropriate to use the temperature limit of flammability(as determined by Test Method E 1232) instead of flash point.5.5 Small scale methods involving equilibrium proceduresand only one flame pass per specimen
20、are preferred.6. Interferences6.1 Incorrect flash points can be obtained when testingchemicals corrosive to the materials of construction of the cup.(For example, certain amines and acid chlorides react with thestandard aluminum small scale cup causing erroneously lowflash points, perhaps due to hyd
21、rogen formation.) Cups em-ploying alternative materials of construction, electroplating orplastic coating can provide corrosion resistance. Results innon-standard cups, particularly in non-equilibrium tests, maydiffer slightly from those obtained in this test method.7. Apparatus7.1 Tag Closed-Cup Te
22、ster, including thermometers, shallbe as shown in Test Methods D 56 and D 3941.7.2 Penksy-Martens Closed-Cup Tester, including ther-mometers, shall be as shown in Test Methods D93.7.3 Small scale Closed Tester, including thermometers, shallbe as shown in Test Methods D 3278 or D 3828.NOTE 1Some auto
23、matic flash point testers may save testing time andpermit the use of small samples. If automatic testers are used, the usermust be certain that all instructions for calibration and operation arefollowed to ensure that the results are equivalent to those obtained on theASTM standard equipment. For re
24、gulation purposes or in cases of dispute,the flash point as determined on the manual tester shall be the acceptedvalue.NOTE 2ASTM thermometers 33C or 33F may be used in the TagTester instead of those specified in Test Method D56when conductingtests at temperatures below 10C (14F). Slight stem correc
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME5022007STANDARDTESTMETHODFORSELECTIONANDUSEOFASTMSTANDARDSFORTHEDETERMINATIONOFFLASHPOINTOFCHEMICALSBYCLOSEDCUPMETHODS

链接地址:http://www.mydoc123.com/p-532898.html