ASTM E2837-2013(2017) Standard Test Method for Determining the Fire Resistance of Continuity Head-of-Wall Joint Systems Installed Between Rated Wall Assemblies and Nonrated Horizon.pdf
《ASTM E2837-2013(2017) Standard Test Method for Determining the Fire Resistance of Continuity Head-of-Wall Joint Systems Installed Between Rated Wall Assemblies and Nonrated Horizon.pdf》由会员分享,可在线阅读,更多相关《ASTM E2837-2013(2017) Standard Test Method for Determining the Fire Resistance of Continuity Head-of-Wall Joint Systems Installed Between Rated Wall Assemblies and Nonrated Horizon.pdf(16页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E2837 13 (Reapproved 2017) An American National StandardStandard Test Method forDetermining the Fire Resistance of Continuity Head-of-WallJoint Systems Installed Between Rated Wall Assemblies andNonrated Horizontal Assemblies1This standard is issued under the fixed designation E2837; th
2、e number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.INT
3、RODUCTIONWall continuity is required by various model codes at joint openings, which are linear voids, gaps,openings, or other discontinuities between or bounded by a rated wall assembly and nonratedhorizontal assemblies, to ensure that the protected joint opening has the same fire resistance rating
4、 asthe rated wall assembly. The joint opening at the termination at the top of the rated wall assemblybelow the nonrated horizontal assembly must be protected by a continuity head-of-wall joint system,which has a fire resistance rating, in order to maintain continuity established by the rated wallas
5、sembly. This test method is not required when the rated wall assembly contacts nonrated horizontalassemblies when there is no joint opening. Normally such joint openings are denoted as “linear”because the length is normally greater than their width, which is defined by a typical ratio of at least10:
6、1 as in practice. Joint openings are present in buildings as a result of: (1) Design to accommodatevarious movements induced by thermal differentials, seismicity, and wind loads and exists as aclearance separation. (2) Acceptable dimensional tolerances between two or more building elements,for examp
7、le, between non-loadbearing walls and roofs. (3) Inadequate design, inaccurate assembly,repairs or damage to the building. There are many unique applications for joint systems in buildings.To address this issue there are different types of continuity head-of-wall joint systems. It is not possibleto
8、test all fire-resistive joints systems using the same test apparatus or method of test, for example, TestMethod E2307 employs the ISMAtest apparatus.A continuity head-of-wall joint system is a particulartype of fire-resistive joint system that provides fire resistance to prevent passage of fire from
9、compartment to compartment within the building at the joint opening between a rated wall assemblyand a nonrated horizontal assembly.Acontinuity head-of-wall joint system is a unique buildingconstruction detail not addressed by other fire test methods such as Test Method E1966 that tests jointsystems
10、 installed between two assemblies that are fire resistance rated.1. Scope1.1 This fire-test-response test method measures the perfor-mance of a unique fire resistive joint system called a continuityhead-of-wall joint system, which is designed to be usedbetween a rated wall assembly and a nonrated ho
11、rizontalassembly during a fire resistance test.1.2 This fire-test-response standard does not measure theperformance of the following:1.2.1 The rated wall assembly, which is already establishedby other test methods, such as Test Method E119,or1.2.2 The nonrated horizontal assembly, which would beesta
12、blished by other test methods such as Test Method E119.NOTE 1Typically, rated wall assemblies obtain a fire resistance ratingafter being tested to Test Method E119, NFPA 251, UL 263, CAN/ULC-S101, or other similar fire resistive test methods.1.3 This fire-test-response standard is not intended to ev
13、alu-ate the connections between rated wall assemblies and non-rated horizontal assemblies unless part of the continuityhead-of-wall joint system.1This test method is under the jurisdiction of ASTM Committee E05 on FireStandards and is the direct responsibility of Subcommittee E05.11 on FireResistanc
14、e.Current edition approved April 1, 2017. Published April 2017. Originallyapproved in 2011. Last previous edition approved in 2013 as E2837-13. DOI:10.1520/E2837-13R17.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United StatesThis international
15、standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.11
16、.4 The fire resistive test end point is the period of timeelapsing before the first performance criteria is reached whenthe continuity head-of-wall joint system is subjected to one oftwo time-temperature fire exposures.1.5 The fire exposure conditions used are either thosespecified by Test Method E1
17、19 for testing assemblies tostandard time-temperature exposures or Test Method E1529 fortesting assemblies to rapid-temperature rise fires.1.6 This test method specifies the heating conditions, meth-ods of test, and criteria to establish a fire resistance rating onlyfor a continuity head-of-wall joi
18、nt system.1.7 Test results establish the performance of continuityhead-of-wall joint systems to maintain continuity of fire resis-tance of the rated wall assembly where the continuity head-of-wall joint system interfaces with a nonrated horizontal assem-bly during the fire-exposure period.1.8 Test r
19、esults shall not be construed as having determinedthe continuity head-of-wall joint system, nonrated horizontalassembly and the rated wall assemblys suitability for use afterthat fire exposure.1.9 This test method does not provide quantitative informa-tion about the continuity head-of-wall joint sys
20、tem relative tothe rate of leakage of smoke or gases or both. However, itrequires that such phenomena be documented and reportedwhen describing the general behavior of continuity head-of-wall joint systems during the fire resistive test but is not part ofthe conditions of compliance.1.10 Potentially
21、 important factors and fire characteristicsnot addressed by this test method include, but are not limitedto:1.10.1 The performance of the continuity head-of-wall jointsystem constructed with components other than those tested.1.10.2 The cyclic movement capabilities of continuity head-of-wall joint s
22、ystems other than the cycling conditions tested.1.11 The values stated in inch-pound units are to be re-garded as standard. The values given in parentheses aremathematical conversions to SI units that are provided forinformation only and are not considered standard.1.12 The text of this standard ref
23、erences notes and footnoteswhich provide explanatory material. These notes and footnotes(excluding those in tables and figures) shall not be consideredas requirements of the standard.1.13 This standard is used to measure and describe theresponse of materials, products, or assemblies to heat andflame
24、 under controlled conditions, but does not by itselfincorporate all factors required for fire hazard or fire riskassessment of the materials, products, or assemblies underactual fire conditions.1.14 This standard does not purport to address all of thesafety concerns, if any, associated with its use.
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME283720132017STANDARDTESTMETHODFORDETERMININGTHEFIRERESISTANCEOFCONTINUITYHEADOFWALLJOINTSYSTEMSINSTALLEDBETWEENRATEDWALLASSEMBLIESANDNONRATEDHORIZONPDF

链接地址:http://www.mydoc123.com/p-531975.html