ASTM E2837-2013 Standard Test Method for Determining the Fire Resistance of Continuity Head-of-Wall Joint Systems Installed Between Rated Wall Assemblies and Nonrated Horizontal As.pdf
《ASTM E2837-2013 Standard Test Method for Determining the Fire Resistance of Continuity Head-of-Wall Joint Systems Installed Between Rated Wall Assemblies and Nonrated Horizontal As.pdf》由会员分享,可在线阅读,更多相关《ASTM E2837-2013 Standard Test Method for Determining the Fire Resistance of Continuity Head-of-Wall Joint Systems Installed Between Rated Wall Assemblies and Nonrated Horizontal As.pdf(18页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E2837 11E2837 13 An American National StandardStandard Test Method forDetermining the Fire Resistance of Continuity Head-of-WallJoint Systems Installed Between Rated Wall Assemblies andNonrated Horizontal Assemblies1This standard is issued under the fixed designation E2837; the number i
2、mmediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.INTRODUCTIONW
3、all continuity is required by various model codes at joint openings, which are linear voids, gaps,openings, or other discontinuities between or bounded by a rated wall assembly and nonratedhorizontal assemblies, to ensure that the protected joint opening has the same fire resistance rating asthe rat
4、ed wall assembly. The joint opening at the termination at the top of the rated wall assemblybelow the nonrated horizontal assembly must be protected by a continuity head-of-wall joint system,which has a fire resistance rating, in order to maintain continuity established by the rated wallassembly. Th
5、is test method is not required when the rated wall assembly contacts nonrated horizontalassemblies when there is no joint opening. Normally such joint openings are denoted as “linear”because the length is normally greater than their width, which is defined by a typical ratio of at least10:1 as in pr
6、actice. Joint openings are present in buildings as a result of: (1) Design to accommodatevarious movements induced by thermal differentials, seismicity, and wind loads and exists as aclearance separation. (2) Acceptable dimensional tolerances between two or more building elements,for example, betwee
7、n non-loadbearing walls and roofs. (3) Inadequate design, inaccurate assembly,repairs or damage to the building. There are many unique applications for joint systems in buildings.To address this issue there are different types of continuity head-of-wall joint systems. It is not possibleto test all f
8、ire-resistive joints systems using the same test apparatus or method of test, for example,TestMethod E2307 employs the ISMAtest apparatus.Acontinuity head-of-wall joint system is a particulartype of fire-resistive joint system that provides fire resistance to prevent passage of fire fromcompartment
9、to compartment within the building at the joint opening between a rated wall assemblyand a nonrated horizontal assembly. A continuity head-of-wall joint system is a unique buildingconstruction detail not addressed by other fire test methods such as Test Method E1966 that tests jointsystems installed
10、 between two assemblies that are fire resistance rated.1. Scope1.1 This fire-test-response test method measures the performance of a unique fire resistive joint system called a continuityhead-of-wall joint system, which is designed to be used between a rated wall assembly and a nonrated horizontal a
11、ssembly duringa fire resistance test.1.2 This fire-test-response standard does not measure the performance of the following:1.2.1 The rated wall assembly, which is already established by other test methods, such as Test Method E119, or1.2.2 The nonrated horizontal assembly, which would be establishe
12、d by other test methods such as Test Method E119.NOTE 1Typically, rated wall assemblies obtain a fire resistance rating after being tested to Test Method E119, NFPA 251, UL 263, CAN/ULC-S101,or other similar fire resistive test methods.1.3 This fire-test-response standard is not intended to evaluate
13、 the connections between rated wall assemblies and nonratedhorizontal assemblies unless part of the continuity head-of-wall joint system.1.4 The fire resistive test end point is the period of time elapsing before the first performance criteria is reached when thecontinuity head-of-wall joint system
14、is subjected to one of two time-temperature fire exposures.1 This test method is under the jurisdiction of ASTM Committee E05 on Fire Standards and is the direct responsibility of Subcommittee E05.11 on Fire Resistance.Current edition approved Dec. 1, 2011July 15, 2013. Published December 2011August
15、 2013. Originally approved in 2011. Last previous edition approved in 2011 asE2837-11. DOI: 10.1520/E2837-11.10.1520/E2837-13.This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Becau
16、seit may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current versionof the standard as published by ASTM is to be considered the official document.Copyright ASTM International, 100 Ba
17、rr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States11.5 The fire exposure conditions used are either those specified by Test Method E119 for testing assemblies to standardtime-temperature exposures or Test Method E1529 for testing assemblies to rapid-temperature rise fires.
18、1.6 This test method specifies the heating conditions, methods of test, and criteria to establish a fire resistance rating only fora continuity head-of-wall joint system.1.7 Test results establish the performance of continuity head-of-wall joint systems to maintain continuity of fire resistance of t
19、herated wall assembly where the continuity head-of-wall joint system interfaces with a nonrated horizontal assembly during thefire-exposure period.1.8 Test results shall not be construed as having determined the continuity head-of-wall joint system,nonrated horizontalassembly and the rated wall asse
20、mblys suitability for use after that fire exposure.1.9 This test method does not provide quantitative information about the continuity head-of-wall joint system relative to the rateof leakage of smoke or gases or both. However, it requires that such phenomena be documented and reported when describi
21、ng thegeneral behavior of continuity head-of-wall joint systems during the fire resistive test but is not part of the conditions ofcompliance.1.10 Potentially important factors and fire characteristics not addressed by this test method include, but are not limited to:1.10.1 The performance of the co
22、ntinuity head-of-wall joint system constructed with components other than those tested.1.10.2 The cyclic movement capabilities of continuity head-of-wall joint systems other than the cycling conditions tested.1.11 The values stated in inch-pound units are to be regarded as standard. The values given
23、 in parentheses are mathematicalconversions to SI units that are provided for information only and are not considered standard.1.12 The text of this standard references notes and footnotes which provide explanatory material. These notes and footnotes(excluding those in tables and figures) shall not
24、be considered as requirements of the standard.1.13 This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame undercontrolled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the mat
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME28372013STANDARDTESTMETHODFORDETERMININGTHEFIRERESISTANCEOFCONTINUITYHEADOFWALLJOINTSYSTEMSINSTALLEDBETWEENRATEDWALLASSEMBLIESANDNONRATEDHORIZONTALASPDF

链接地址:http://www.mydoc123.com/p-531974.html