《ASTM E2768-2011 Standard Test Method for Extended Duration Surface Burning Characteristics of Building Materials (30 min Tunnel Test)《建筑材料延时表面燃烧特性的标准试验方法(30 min坑道试验)》.pdf》由会员分享,可在线阅读,更多相关《ASTM E2768-2011 Standard Test Method for Extended Duration Surface Burning Characteristics of Building Materials (30 min Tunnel Test)《建筑材料延时表面燃烧特性的标准试验方法(30 min坑道试验)》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E2768 11An American National StandardStandard Test Method forExtended Duration Surface Burning Characteristics ofBuilding Materials (30 min Tunnel Test)1This standard is issued under the fixed designation E2768; the number immediately following the designation indicates the year oforigi
2、nal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 The purpose of this fire-test-response standard is toevaluate th
3、e ability of a product to limit the surface spread offlame when evaluated for 30 min. This fire-test-responsestandard uses the apparatus and procedure of Test Method E84with the total test period extended to 30 min.1.2 Building applications affecting fire and life safety oftenrequire products with s
4、pecific criteria for surface spread offlame and flame spread index. The resulting performancecharacteristics included in the conditions of classification forthis fire-test-response standard are intended to be used forregulatory purposes to determine the suitability of materials orproducts for use in
5、 buildings under specified conditions wheresignificantly reduced surface burning characteristics are re-quired.1.3 Materials and products that are beyond the scope of TestMethod E84 are beyond the scope of this standard.1.4 Materials or products which melt, drip or delaminate tothe extent that the c
6、ontinuity of the flame front is destroyed arebeyond the scope of this standard.NOTE 1Testing of materials that melt, drip, or delaminate to such adegree that the continuity of the flame-front is destroyed, results in lowflame spread indices that do not relate directly to indices obtained bytesting m
7、aterials that remain in place. Materials or products that melt, drip,or delaminate, or that cannot support their own weight, have the potentialfor demonstrating reduced flame spread results as compared to the flamespread results where the materials or products remain in place duringtesting.1.5 The v
8、alues stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.6 The text of this standard references notes and footnotesthat provide explanatory informati
9、on. These notes and foot-notes, excluding tables and figures, shall not be considered asrequirements of the standard.1.7 This standard is used to measure and describe theresponse of materials, products, or assemblies to heat andflame under controlled conditions, but does not by itselfincorporate all
10、 factors required for fire hazard or fire riskassessment of the materials, products, or assemblies underactual fire conditions1.8 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish ap
11、pro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.1.9 Fire testing is inherently hazardous. Adequate safe-guards for personnel and property shall be employed inconducting these tests.2. Referenced Documents2.1 ASTM Standards:2E84 Test Meth
12、od for Surface Burning Characteristics ofBuilding MaterialsE176 Terminology of Fire Standards2.2 ICC Codes3IBC International Building CodeIWUIC International Wildland Urban Interface CodeIRC International Residential Code2.3 NFPA Code4NFPA 101 Life Safety Code2.4 California Building Code5CBC Califor
13、nia Building Code3. Terminology3.1 DefinitionsFor definitions of terms used in this testmethod, refer to Terminology E176 and Test Method E84. The1This test method is under the jurisdiction of ASTM Committee E05 on FireStandards and is the direct responsibility of Subcommittee E05.22 on SurfaceBurni
14、ng.Current edition approved July 1, 2011. Published August 2011. DOI: 10.1520/E2768-11.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summar
15、y page onthe ASTM website.3ICC codes are available from International Code Council, 4051 W. FlossmoorRd., Country Club Hills, IL 60478.4NFPA Codes are available from National Fire Protection Association, 1Batterymarch Park, Quincy, MA, 02269.5CBC codes are available from http:/ ASTM International, 1
16、00 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.terms surface flame spread, flame spread index, and smokedeveloped index are of particular interest to this standard.4. Summary of Test Method4.1 This test method is conducted using the same equip-ment, apparatus, cal
17、ibration, and calculation of flame spreadindex and smoke developed index as Test Method E84.4.2 Test Method E84 exposes a nominal 24-ft long by 20-inwide (7.32 m by 508 mm) specimen to a controlled air flow andflaming fire exposure adjusted to spread the flame along theentire length of the select gr
18、ade red oak specimen in 5.5 min(615 s). Test Method E84 measures the flame spread distancefrom a point beginning 4.5 ft (1.4 m) beyond the centerline ofthe burners.4.3 The flame spread index is determined during the initial10 min of the test period and calculated as described in TestMethod E84.4.4 I
19、n this test method, the Test Method E84 test is extendedby 20 min to a 30 min test period. Determination is made of thedistance traveled by the flame front (surface spread of flame) asmeasured from the centerline of the burners during the 30 mintest period.4.5 The test method has conditions for clas
20、sification inSection 13.5. Significance and Use5.1 This standard is useful to establish the relative surfaceburning characteristics of materials or products under labora-tory conditions for a 30 min test period.5.2 The performance characteristics in the conditions ofclassification are intended to be
21、 used in specific applications asrequired by building codes or other regulatory requirements orspecifications.5.3 This test method does not provide the measurement ofheat transmission through the tested surface.5.4 This test method does not provide the classification ordefinition of a material or pr
22、oduct as noncombustible, bymeans of the results from this standard test or flame spreadindex by itself.6. Apparatus/Test Equipment6.1 The apparatus, equipment, recording devices, and sys-tems are to be the same as those detailed in Test Method E84.7. Hazards7.1 This test is conducted using the equip
23、ment, apparatus,and procedure of Test Method E84. The hazards described inTest Method E84 are applicable.8. Sampling, Test Specimens and Test Units8.1 The test specimens shall be representative of the mate-rial or product being evaluated.8.2 Materials or products that are not homogeneous or arenot s
24、ymmetrical about their longitudinal axis shall have eachsurface evaluated separately.8.2.1 Surfaces of the material or product that, due to theirsmall surface area, are impractical to test in accordance withTest Method E84 (for example, the edges of a piece ofplywood) are excluded from this requirem
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME27682011STANDARDTESTMETHODFOREXTENDEDDURATIONSURFACEBURNINGCHARACTERISTICSOFBUILDINGMATERIALS30MINTUNNELTEST

链接地址:http://www.mydoc123.com/p-531855.html