ASTM E2393-2010a Standard Practice for On-Site Inspection of Installed Fire Resistive Joint Systems and Perimeter Fire Barriers《对已安装的防火连接系统和四周挡火墙进行现场检查的标准实施规程》.pdf
《ASTM E2393-2010a Standard Practice for On-Site Inspection of Installed Fire Resistive Joint Systems and Perimeter Fire Barriers《对已安装的防火连接系统和四周挡火墙进行现场检查的标准实施规程》.pdf》由会员分享,可在线阅读,更多相关《ASTM E2393-2010a Standard Practice for On-Site Inspection of Installed Fire Resistive Joint Systems and Perimeter Fire Barriers《对已安装的防火连接系统和四周挡火墙进行现场检查的标准实施规程》.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E2393 10aStandard Practice forOn-Site Inspection of Installed Fire Resistive Joint Systemsand Perimeter Fire Barriers1This standard is issued under the fixed designation E2393; the number immediately following the designation indicates the year oforiginal adoption or, in the case of rev
2、ision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice covers the establishment of procedures toinspect fire resistive joint systems, includ
3、ing methods for fieldverification and inspection.1.2 This practice addresses all types of fire resistive jointsystems and of perimeter joint protection.NOTE 1Fire resistive joint system and joint are defined in TestMethod E1966 and UL 2079.NOTE 2Perimeter joint protection is defined in Test Method E
4、2307.NOTE 3Fire resistive joint systems include joints between two fireresistive assemblies, and perimeter joints between a fire resistive floorassembly and a non-fire-resistive wall assembly. The application of thesesystems are sometimes extended based on an evaluation to other types ofconstruction
5、.1.3 This practice provides methods by which qualifiedinspectors verify that required fire resistive joint systems on aproject have been installed and that their installations are inaccordance with the inspection documents.1.4 The values stated in inch-pound units are to be regardedas standard. No o
6、ther units of measurement are included in thisstandard.1.5 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility
7、 of regulatory limitations prior to use.1.6 The text of this standard references notes and footnoteswhich provide explanatory material. These notes and footnotes(excluding those in tables and figures) shall not be consideredas requirements of the standard.2. Referenced Documents2.1 ASTM Standards:2E
8、176 Terminology of Fire StandardsE631 Terminology of Building ConstructionsE699 Practice for Evaluation of Agencies Involved in Test-ing, Quality Assurance, and Evaluating of Building Com-ponentsE1966 Test Method for Fire-Resistive Joint SystemsE2307 Test Method for Determining Fire Resistance ofPer
9、imeter Fire Barriers Using Intermediate-Scale, Multi-story Test Apparatus2.2 Other Standard:UL 2079 Fire Tests of Fire Resistive Joints32.3 Other Documents:International Building Code4NFPA 5000 Building Code53. Terminology3.1 DefinitionsTerms defined in Terminology E631, Ter-minology E176, and Pract
10、ice E699 will prevail for terms notdefined in this document.3.2 Definitions of Terms Specific to This Standard:3.2.1 authorizing authority (AA)the designated person, ororganization, or their duly authorized representative, chargedwith the administration and enforcement of the provisions ofthis inspe
11、ction document.NOTE 4Examples of the AA include the responsible Architect, Engi-neer, Building Owner, or their representatives.3.2.2 authority having jurisdiction (AHJ)the designatedauthority, or their duly authorized representative, charged withthe administration and enforcement of the local fire c
12、ode orbuilding code, or both.3.2.3 accredited testing laboratorya company engaged inconducting testing and possesses a valid evaluation report fortesting services and is recognized by the AHJ.3.2.4 evaluation reportan approved document issued bythe Model Code Body Evaluation Service or by the AHJ.3.
13、2.5 inspection documentany information provided tothe inspector by the AA that is to be used as the basis for the1This practice is under the jurisdiction of ASTM Committee E06 on Perfor-mance of Buildings and is the direct responsibility of Subcommittee E06.21 onServiceability.Current edition approv
14、ed April 1, 2010. Published August 2010. Originallyapproved in 2004. Last previous edition approved in 2010 as E2393 10. DOI:10.1520/E2393-10A.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards vo
15、lume information, refer to the standards Document Summary page onthe ASTM website.3Available from Underwriters Laboratories (UL), Corporate Progress, 333Pfingsten Rd., Northbrook, IL 60062, http:/.4Available from International Code Council (ICC), 500 New Jersey Ave., NW,6th Floor, Washington, DC 200
16、01-2070, http:/www.iccsafe.org.5Available from National Fire Protection Association (NFPA), 1 BatterymarchPark, Quincy, MA 02169-7471, http:/www.nfpa.org.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.inspection process. This inform
17、ation shall include, but is notlimited to, project specifications, contract drawings, ListedDesigns, judgments, manufacturers instructions and designs,building codes and other documentation.NOTE 5The approved fire resistive joint system submittal should havesufficient details including the manufactu
18、rers product data, a designlisting of the tested fire resistive joint system or the engineering judgmentdesign with illustrated drawings or descriptive text, or both, for thepurpose of verifying each installation and conducting the field-inspectionprocedures.3.2.6 inspection formthe document contain
19、ed in this prac-tice that is used to record information obtained during theinspection(s).3.2.7 inspectoran individual meeting the qualificationsset forth in this document and who performs the inspection.3.2.8 judgmentan evaluation of a field condition whichdoes not conform to an existing tested and
20、listed system.3.2.8.1 DiscussionJudgments are expected to be issued bya manufacturer or an accredited testing laboratory on the basisof an appropriate combination of engineering principles andtesting.NOTE 6The judgment is commonly referred to as an “EngineeringJudgment” in the fire stopping industry
21、. These judgments are not alwaysissued by Engineers.NOTE 7Some AHJs allow a judgment by a manufacturer if there is notested and listed system for the non-typical condition, others do not. MostAHJs will allow judgments by accredited testing laboratories.3.2.9 listing labelidentification applied to th
22、e product thatincludes the name of a quality assurance agency indicating thata representative sample of the product or material has beentested and evaluated by the quality assurance agency.3.2.10 quality assurance agencya company that is en-gaged in conducting inspections, or certification, or listi
23、ng andlabeling services, or any combination, and possessing a validevaluation report for quality assurance and is recognized by theAHJ.4. Summary of Practice4.1 This practice sets forth the minimum requirements toqualify an inspector to use this practice.4.2 This practice identifies the types of fir
24、e resistive jointsystems subject to the inspection procedures outlined in thispractice.4.3 This practice provides the minimum information re-quired to verify compliance of installed fire resistive joints withinspection documents.4.4 This practice provides a standard inspection form that isto be used
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME23932010ASTANDARDPRACTICEFORONSITEINSPECTIONOFINSTALLEDFIRERESISTIVEJOINTSYSTEMSANDPERIMETERFIREBARRIERS

链接地址:http://www.mydoc123.com/p-531034.html