ASTM E2393-2004 Standard Practice for On-Site Inspection of Installed Fire Resistive Joint Systems and Perimeter Fire Barriers《安装的防火接头系统和周围防火壁的现场检验的标准实施规程》.pdf
《ASTM E2393-2004 Standard Practice for On-Site Inspection of Installed Fire Resistive Joint Systems and Perimeter Fire Barriers《安装的防火接头系统和周围防火壁的现场检验的标准实施规程》.pdf》由会员分享,可在线阅读,更多相关《ASTM E2393-2004 Standard Practice for On-Site Inspection of Installed Fire Resistive Joint Systems and Perimeter Fire Barriers《安装的防火接头系统和周围防火壁的现场检验的标准实施规程》.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E 2393 04Standard Practice forOn-Site Inspection of Installed Fire Resistive Joint Systemsand Perimeter Fire Barriers1This standard is issued under the fixed designation E 2393; the number immediately following the designation indicates the year oforiginal adoption or, in the case of re
2、vision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice covers the establishment of procedures toinspect fire resistive joint systems, incl
3、uding methods for fieldverification and inspection.1.2 This standard practice addresses all types of fire resis-tive joint systems and of perimeter joint protection.NOTE 1Fire resistive joint system and joint are defined in TestMethod E 1966.NOTE 2Perimeter joint protection is defined in Test Method
4、 E 2307.NOTE 3Fire resistive joint systems include joints between two fireresistive assemblies, and perimeter joints between a fire resistive floorassembly and a non-fire-resistive wall assembly. The application of thesesystems may be extended based on an evaluation to other types ofconstruction.1.3
5、 This standard practice provides methods by whichqualified inspectors can verify that all required fire resistivejoint systems on a project have been installed and that theirinstallations are in accordance with the inspection documents.1.4 This standard does not purport to address all of thesafety c
6、oncerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.1.5 The text of this standard references notes and footnoteswhich provide expla
7、natory material. These notes and footnotes(excluding those in tables and figures) shall not be consideredas requirements of the standard.2. Referenced Documents2.1 ASTM Standards:2E 176 Terminology of Fire StandardsE 631 Terminology of Building ConstructionsE 699 Criteria for Evaluation of Agencies
8、Involved inTesting, Quality Assurance, and Evaluating Building Com-ponents in Accordance with Test Methods Promulgated byASTM Committee E06E 1966 Test Method for Fire Tests of Fire Resistive JointSystemsE 2307 Test Method for Determining Fire Resistance ofPerimeter Fire Barrier Using Intermediate-Sc
9、ale Multi-Story Test Apparatus2.2 Other Standard:UL 2079 Fire Tests of Fire Resistive Joints32.3 Other Documents:International Building Code4NFPA 5000 Building Code53. Terminology3.1 DefinitionsTerms defined in Terminology E 631, Ter-minology E 176, and Criteria E 699 will prevail for terms notdefin
10、ed in this document.3.2 Definitions of Terms Specific to This Standard:3.2.1 authorizing authority (AA)the designated person, ororganization, or their duly authorized representative, chargedwith the administration and enforcement of the provisions ofthis inspection document.NOTE 4Examples of the AA
11、include the responsible Architect, Engi-neer, Building Owner, or their representatives.3.2.2 authority having jurisdiction (AHJ)the designatedauthority, or their duly authorized representative, charged withthe administration and enforcement of the local fire code orbuilding code or both.3.2.3 accred
12、ited testing laboratorya company engaged inconducting testing and possesses a valid evaluation report fortesting services and is recognized by the AHJ.3.2.4 evaluation reportan approved document issued bythe Model Code Body Evaluation Service or by the AHJ.3.2.5 inspection documentany information pr
13、ovided tothe inspector by the AA that is to be used as the basis for theinspection process. This information shall include, but is notlimited to, project specifications, contract drawings, Listed1This practice is under the jurisdiction of ASTM Committee E06 on Perfor-mance of Buildings and is the di
14、rect responsibility of Subcommittee E06.21 onServiceability.Current edition approved Nov. 1, 2004. Published November 2004.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, re
15、fer to the standards Document Summary page onthe ASTM website.3Available from Underwriters Laboratories (UL), Corporate Progress, 333Pfingsten Rd., Northbrook, IL 60062.4Available from International Code Council (ICC), 5203 Leesburg Pike, Suite600, Falls Church, VA 22041.5Available from National Fir
16、e Protection Association (NFPA), 1 BatterymarchPark, Quincy, MA 02269-9101.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.Designs, judgments, manufacturers instructions and designs,building codes and other documentation.NOTE 5The ap
17、proved fire resistive joint system submittal should havesufficient details including the manufacturers product data, a designlisting of the tested fire resistive joint system or the engineering judgmentdesign with illustrated drawings or descriptive text or both for the purposeof verifying each inst
18、allation and conducting the field-inspection proce-dures.3.2.6 inspection formthe document contained in this stan-dard practice that is used to record information obtained duringthe inspection(s).3.2.7 inspectoran individual meeting the qualificationsset forth in this document and who performs the i
19、nspection.3.2.8 judgmentan evaluation of a field condition whichdoes not conform to an existing tested and listed system.3.2.8.1 DiscussionManufacturers or an accredited TestingLaboratory should only issue judgments based on EngineeringPrinciples or available testing that approximates the conditione
20、ncountered, or both.NOTE 6The judgment is commonly referred to as an “EngineeringJudgment” in the fire stopping industry. It should be noted that thesejudgments are not always issued by Engineers.NOTE 7Some AHJs allow a judgment by a manufacturer if there is notested and listed system for the non-ty
21、pical condition, others do not. MostAHJs will allow judgments by accredited testing laboratories. Accreditedtesting laboratories can verify judgments by manufacturers for validity.3.2.9 listing labelidentification applied to the product thatincludes the name of a quality assurance agency indicating
22、thata representative sample of the product or material has beentested and evaluated by the quality assurance agency.3.2.10 quality assurance agencya company that is en-gaged in conducting inspections, or certification, or listing andlabeling services, or any combination, and possessing a validevalua
23、tion report for quality assurance and is recognized by theAHJ.4. Summary of Practice4.1 This standard practice sets forth the minimum require-ments to qualify an inspector to use this standard practice.4.2 This standard practice identifies the types of fire resis-tive joint systems subject to the in
24、spection procedures outlinedin this standard practice.4.3 This standard practice provides the minimum informa-tion required to verify compliance of installed fire resistivejoints with inspection documents.4.4 This standard practice provides a standard inspectionform that is to be used when inspectin
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME23932004STANDARDPRACTICEFORONSITEINSPECTIONOFINSTALLEDFIRERESISTIVEJOINTSYSTEMSANDPERIMETERFIREBARRIERS

链接地址:http://www.mydoc123.com/p-531031.html