《ASTM E2307-2015b Standard Test Method for Determining Fire Resistance of Perimeter Fire Barriers Using Intermediate-Scale Multi-story Test Apparatus《使用中型多层试验设备测定周边防火墙系统防火性的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM E2307-2015b Standard Test Method for Determining Fire Resistance of Perimeter Fire Barriers Using Intermediate-Scale Multi-story Test Apparatus《使用中型多层试验设备测定周边防火墙系统防火性的标准试验方法》.pdf(21页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E2307 15b An American National StandardStandard Test Method forDetermining Fire Resistance of Perimeter Fire BarriersUsing Intermediate-Scale, Multi-story Test Apparatus1This standard is issued under the fixed designation E2307; the number immediately following the designation indicates
2、 the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.INTRODUCTIONA perimeter fire barrier is the perimeter joint
3、 protection that provides fire resistance to preventpassage of fire from floor to floor within the building at the opening between the exterior wallassembly and the floor assembly. A perimeter fire barrier is a unique building construction detail notaddressed by other fire test methods.Among its oth
4、er functions, a perimeter fire barrier impedes the vertical spread of fire from the floorof origin to the floor(s) above, at the buildings exterior perimeter and accommodates variousmovements such as those induced by thermal differentials, seismicity, and wind loads.This test method describes criter
5、ia and test methods used to determine the fire resistance ofperimeter fire barriers when subjected to standard fire exposure conditions using the intermediate-scale, multistory test apparatus (ISMA). The use of the multi-story test apparatus and this test methodare intended to simulate a possible fi
6、re exposure on a perimeter fire barrier.1. Scope1.1 This test method measures the performance of theperimeter fire barrier and its ability to maintain a seal toprevent fire spread during the deflection and deformation of theexterior wall assembly and floor assembly during the fire test,while resisti
7、ng fire exposure from an interior compartment fireas well as from the flame plume emitted from the windowburner below. The end point of the fire-resistance test is theperiod of time elapsing before the first condition of complianceis reached as the perimeter fire barrier is subjected to atime-temper
8、ature fire exposure.1.2 The fire exposure conditions used are those specified bythis test method for the first 30 min of exposure and thenconform to the Test Methods E119 time-temperature curve forthe remainder of the test in the test room.1.3 This test method specifies the heating conditions, meth-
9、ods of test, and criteria for evaluation of the ability of aperimeter fire barrier to maintain the fire resistance where afloor and exterior wall assembly are juxtaposed to a perimeterjoint.1.4 Test results establish the performance of perimeter firebarriers during the fire-exposure period and shall
10、 not beconstrued as having determined the suitability of perimeter firebarriers for use after that exposure.1.5 This test method does not provide quantitative informa-tion about the perimeter fire barrier relative to the rate ofleakage of smoke or gases or both. While it requires that suchphenomena
11、be noted and reported when describing the generalbehavior of perimeter fire barrier during the fire-resistance test,such phenomena are not part of the conditions of compliance.1.6 Potentially important factors and fire characteristics notaddressed by this test method include, but are not limited to:
12、1.6.1 The performance of the perimeter fire barrier con-structed with components other than those tested, and1.6.2 The cyclic movement capabilities of perimeter firebarriers other than the cycling conditions tested.1.7 This test method is used to measure and describe theresponse of materials, produc
13、ts or assemblies to heat and flameunder controlled conditions but does not by itself incorporateall factors required for the fire-hazard or fire-risk assessment ofthe materials, products, or assemblies under actual fire condi-tions.1.8 The values stated in inch-pound units are to be regardedas stand
14、ard. The values given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1This test method is under the jurisdiction of ASTM Committee E05 on FireStandards and is the direct responsibility of Subcommittee E05.11 on FireResista
15、nce.Current edition approved Oct. 1, 2015. Published November 2015. Originallyapproved in 2004. Last previous edition approved in 2015 as E2307-15a. DOI:10.1520/E2307-15B.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States11.9 The text of
16、 this test method references notes andfootnotes which provide explanatory material. These notes andfootnotes (excluding those in tables and figures) shall not beconsidered as requirements of the standard.1.10 This standard does not purport to address all of thesafety concerns, if any, associated wit
17、h its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2E84 Test Method for Surface Burning Characteristics ofBuilding Mate
18、rialsE108 Test Methods for Fire Tests of Roof CoveringsE119 Test Methods for Fire Tests of Building Constructionand MaterialsE176 Terminology of Fire StandardsE511 Test Method for Measuring Heat Flux Using a Copper-Constantan Circular Foil, Heat-Flux TransducerE631 Terminology of Building Constructi
19、onsE1529 Test Methods for Determining Effects of Large Hy-drocarbon Pool Fires on Structural Members and Assem-bliesE1966 Test Method for Fire-Resistive Joint Systems2.2 Other Documents:Uniform Building Code Standard No. 26-9 Method of Testfor the Evaluation of Flammability Characteristics ofExterio
20、r, Non-Loadbearing Wall Assemblies ContainingCombustible Components Using the Intermediate-ScaleMultistory Test Apparatus3NFPA 285 Standard Method of Test for the Evaluation ofFlammability Characteristics of Exterior Non-Load-Bearing Wall Assemblies Containing Combustible Com-ponents Using the Inter
21、mediate-Scale, Multistory TestApparatus4The 14th Edition of the Gypsum Associations Fire Resis-tance Design Manual (GA 600 94)53. Terminology3.1 Terms defined in Terminology E176 and E631 shallprevail for fire standard and building terms not defined in thisdocument.3.2 Definitions:3.2.1 blockout, na
22、 recess formed in the floor assembly toaccommodate the installation of the perimeter joint protection,flush with the wearing surface of the floor assembly.3.2.2 curtain wall assembly, neither a rated or non-rated,nonbearing exterior wall assembly secured to and supported bythe structural members of
23、the building.3.2.3 exterior wall assembly, na curtain wall or a load-bearing exterior wall that is either fire resistance rated or onethat is not.3.2.4 floor assembly, na fire resistance rated loadbearinghorizontal separating element adjacent to and separate from thefloor of the observation room.3.2
24、.4.1 DiscussionFloor assemblies tested in accordancewith Test Methods E119 are required to be loadbearing.3.2.5 integrity, nthe ability of a perimeter fire barrier,when exposed to fire from two sides, to prevent the passage offlame and hot gases through it and the occurrence of flames onits unexpose
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME23072015BSTANDARDTESTMETHODFORDETERMININGFIRERESISTANCEOFPERIMETERFIREBARRIERSUSINGINTERMEDIATESCALEMULTISTORYTESTAPPARATUS

链接地址:http://www.mydoc123.com/p-530835.html