ASTM E2270-2014 Standard Practice for Periodic Inspection of Building Facades for Unsafe Conditions《不安全条件下建筑物正面周期性检验的标准实施规程》.pdf
《ASTM E2270-2014 Standard Practice for Periodic Inspection of Building Facades for Unsafe Conditions《不安全条件下建筑物正面周期性检验的标准实施规程》.pdf》由会员分享,可在线阅读,更多相关《ASTM E2270-2014 Standard Practice for Periodic Inspection of Building Facades for Unsafe Conditions《不安全条件下建筑物正面周期性检验的标准实施规程》.pdf(6页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E2270 14Standard Practice forPeriodic Inspection of Building Facades for UnsafeConditions1This standard is issued under the fixed designation E2270; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revi
2、sion. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This standard practice covers methods and proceduresfor inspection, evaluation, and reporting for periodic inspectionof buildin
3、g facades for unsafe conditions. In the context of thispractice, unsafe conditions are hazards caused by or resultingfrom loss of facade material.1.2 This standard practice does not purport to address thenature of deterioration of various building facade materials northe performance of their assembl
4、ies. It is the responsibility ofthe owner to retain a qualified professional who can demon-strate expertise in the evaluation of various facade materialsand their assemblies.1.3 Investigative techniques discussed may be intrusive,disruptive, or destructive. It is the responsibility of the qualifiedp
5、rofessional to anticipate, advise on the nature of procedures,and to plan for implementing repair as necessary.1.4 It is the responsibility of the specifying authority toestablish the usage of this standard practice and to supplementthis practice with additional requirements suitable to its localjur
6、isdiction. It is also the responsibility of the specifyingauthority to determine compliance with local licensing regula-tions and customary practices.1.5 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that
7、are provided for information onlyand are not considered standard.1.6 This standard may involve hazardous materials,operations, and equipment. This standard does not purport toaddress all of the safety concerns, if any, associated with itsuse. It is the responsibility of the user of this standard toe
8、stablish appropriate safety and health practices and deter-mine the applicability of regulatory limitations prior to use.Awareness of safety and familiarity with safe procedures areparticularly important for above-ground operations on facadesand destructive investigative procedures, which typically
9、areassociated with the work described.2. Referenced Documents2.1 ASTM Standards:2E631 Terminology of Building Constructions3. Terminology3.1 Refer to Terminology E631.3.2 Definitions:3.2.1 categories of facade conditions:3.2.1.1 ordinary maintenancea condition identified at thetime of inspection tha
10、t is not characterized as an “unsafecondition” or “requires repair/stabilization,” but requires main-tenance.3.2.1.2 requires repair/stabilizationa condition identifiedat the time of inspection that shall be repaired or stabilized inorder to prevent progression into an “unsafe condition” prior tothe
11、 next scheduled inspection.NOTE 1The immediacy of actions to address conditions requiringrepair other than unsafe conditions is highly variable and should bedetermined by the owner. Such determination may require more detailedinvestigation than addressed herein to assess the urgency of such action.3
12、.2.1.3 unsafe conditiona condition identified at the timeof inspection of a component or system that presents animminent threat of harm, injury, damage, or loss to persons orproperty.3.2.2 facadeall areas on the exterior of the building,except for horizontal roof areas. The facade includes allexteri
13、or walls, windows, balconies, cornices, parapets, andappurtenances. The facade also includes walls supported atroof level, such as penthouse walls, chimneys, and so forth.3.2.3 facade agenumber of years since the original Cer-tificate of Occupancy for building was issued, or since entirefacade repla
14、cement.1This practice is under the jurisdiction of ASTM Committee E06 on Perfor-mance of Buildings and is the direct responsibility of Subcommittee E06.55 onPerformance of Building Enclosures.Current edition approved Sept. 1, 2014. Published October 2014. Originallyapproved in 2003. Last previous ed
15、ition approved in 2013 as E2270 13. DOI:10.1520/E2270-14.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.Copy
16、right ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States13.2.4 facade inspection categorycategory assigned tobuilding facade based on the facade material, construction, age,and inspection level/extent required, as outlined in Annex A1of this docum
17、ent.3.2.5 facade inspection reporta detailed documentation ofqualified professionals findings, observations, discussions,conclusions, and recommendations about the subject buildingfacades.3.2.6 levels of facade inspections:3.2.6.1 detailed inspectionvisual observation from lessthan 6 ft (1.8 m) and
18、tactile evaluation of facade components,including probing and non-destructive testing to observe con-cealed conditions of wall construction.3.2.6.2 general inspectionvisual observation of facadecomponents from distances equal to or greater than 6 ft (1.8 m)with or without magnification or remote opt
19、ical devices.3.2.7 maintenance personnelpersonnel who have beeninvolved in maintenance of the subject building facades.3.2.8 non-destructive testing (NDT)a test that causes nosignificant structural damage to building components.3.2.9 ownerthe owner, agent, manager, or person incharge, of possession,
20、 operation, or management of thebuilding, or any combination thereof.3.2.10 probedisassembly/removal of selective portions ofa facade to observe concealed conditions of wall construction.3.2.11 public access areaany sidewalk, street, alley, park,plaza, playground, schoolyard or other area that is op
21、en andaccessible to the public, regardless of whether it is publicly orprivately owned.3.2.12 qualified inspectora qualified professional or aperson working under the direct supervision of a qualifiedprofessional.3.2.13 qualified professionalan architect or civil/structuralengineer duly licensed. Th
22、e qualified professional must beknowledgeable of the design, construction, and inspection ofbuilding facades, stability, and deterioration mechanisms relat-ing to the specific materials and assemblies particular to thefacade being inspected.3.2.14 specifying authorityparty requiring inspection of ab
23、uilding facade.NOTE 2The specifying authority may be a governmental body.3.2.15 watertight integritythe means a facade employs toprevent water intrusion to areas or materials where waterintrusion is not intended.4. Significance and Use4.1 IntentThis standard practice is intended to establishthe mini
24、mum requirements for conducting periodic inspectionsof building facades to identify unsafe conditions that couldcause harm to persons and property. It addresses the requiredcontent of the facade inspection to convey to the specifyingauthority the condition of the facade and allow comparisons offacad
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME22702014STANDARDPRACTICEFORPERIODICINSPECTIONOFBUILDINGFACADESFORUNSAFECONDITIONS 不安全 条件下 建筑物 正面

链接地址:http://www.mydoc123.com/p-530744.html