1、Designation: E2257 16E2257 17 An American National StandardStandard Test Method forRoom Fire Test of Wall and Ceiling Materials andAssemblies1This standard is issued under the fixed designation E2257; the number immediately following the designation indicates the year oforiginal adoption or, in the
2、case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope Scope*1.1 This is a fire-test-response standard.1.2 This test method is intended to evaluat
3、e, under specified fire-exposure conditions, the contribution to room fire growthprovided by wall or ceiling materials and assemblies, or both. The method is not intended to evaluate the fire endurance ofassemblies or fires originating in the wall assembly. The method provides a means to evaluate th
4、e effectiveness of thermal barriersin restricting the contribution of combustible materials in the wall assembly to fire growth in a room fire.1.3 This test method, simulating a fire in the corner of a 2420 by 3630 mm (8 by 12 ft) room containing a single open doorway,provides a means to evaluate th
5、e relative performance of specified wall and ceiling materials or assemblies when they are usedtogether in the same relationship within an enclosure, and simulating the manner in which they will be used.1.4 This test method is intended to evaluate the contribution to fire growth provided by a surfac
6、e product using a specifiedignition source. It shall, however, be noted that the type, position and heat output of the ignition source will considerably influencefire growth. The thermal exposure conditions from the ignition source specified in this method will result in flashover during the20 min d
7、uration for many common finish materials, in particular if specimens are mounted on the walls and the ceiling (standardconfiguration).1.5 This test method provides a means for evaluating wall and ceiling finish materials and assemblies, including panels, tiles,boards, sprayed or brushed coatings, et
8、c. This test method is not intended to evaluate flooring materials or furnishings.1.6 This method shall be used in conjunction with Guide E603, which covers instrumentation and the general effect of variousparameters, and Guide E2067, which deals with full-scale oxygen consumption calorimetry.1.7 Th
9、e values stated in SI units are to be regarded as the standard. The units given in parentheses are for information only.1.8 The text of this standard references notes and footnotes which provide explanatory information. These notes and footnotes(excluding those in figures) shall not be considered as
10、 requirements of the standard.1.9 This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame undercontrolled conditions, but does not by itself incorporate all factors required for fire-hazard or fire-risk assessment of the materials,products,
11、or assemblies under actual fire conditions.1.10 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibilityof the user of this standard to establish appropriate safety and health practices and determine the applicability of regulato
12、rylimitations prior to use.1.11 Fire testing is inherently hazardous. Adequate safeguards for personnel and property shall be employed in conductingthese tests.1.12 This international standard was developed in accordance with internationally recognized principles on standardizationestablished in the
13、 Decision on Principles for the Development of International Standards, Guides and Recommendations issuedby the World Trade Organization Technical Barriers to Trade (TBT) Committee.1 This test method is under the jurisdiction ofASTM Committee E05 on Fire Standards and is the direct responsibility of
14、 Subcommittee E05.21 on Smoke and CombustionProducts.Current edition approved Feb. 1, 2016April 15, 2017. Published March 2016April 2017. Originally approved in 2003. Last previous edition approved in 20132016 asE2257-13a.-16. DOI: 10.1520/E2257-16.10.1520/E2257-17.This document is not an ASTM stand
15、ard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases
16、 only the current versionof the standard as published by ASTM is to be considered the official document.*A Summary of Changes section appears at the end of this standardCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States12. Referenced Doc
17、uments2.1 ASTM Standards:2E84 Test Method for Surface Burning Characteristics of Building MaterialsE136 Test Method for Behavior of Materials in a Vertical Tube Furnace at 750CE176 Terminology of Fire StandardsE603 Guide for Room Fire ExperimentsE2067 Practice for Full-Scale Oxygen Consumption Calor
18、imetry Fire Tests2.2 ISO Standards:ISO 9705 Fire TestsReaction to FireRoom Fire Test3ISO 13943 Fire SafetyVocabulary32.3 NFPA Standards:NFPA 265 Standard Method of Tests for Evaluating Room Fire Growth Contribution of Textile Wall Coverings4NFPA 286 Standard Method of Tests for Evaluating Contributi
19、on of Wall and Ceiling Interior Finish to Room Fire Growth43. Terminology3.1 DefinitionsFor definitions of terms used in this standard, see Terminology E176 and ISO 13943. In case of conflict, thedefinitions given in Terminology E176 shall prevail.3.1.1 assembly, na unit or structure composed of a c
20、ombination of materials or products, or both. E1763.1.2 flashover, nthe rapid transitionto a state of total surface involvement in a fire of combustible materials within anenclosure. E1763.1.3 heat flux, nheat transfer to a surface per unit area, per unit time. E1763.1.4 heat release rate, nthe heat
21、 evolved from the specimen per unit time. E1763.1.5 optical density of smoke, na measure of the attenuation of a light beam through smoke, expressed as the commonlogarithm of the ratio of the incident flux, I0, to the transmitted flux, I. E1763.1.6 oxygen consumption principle, nthe expression of th
22、e relationship between the mass of oxygen consumed duringcombustion and the heat released. E1763.1.7 smoke, nthe airborne solid and liquid particulates and gases evolved when a material undergoes pyrolysis or combustion.E1763.1.8 smoke obscuration, nreduction of light transmission by smoke as measur
23、ed by light attenuation. E1763.2 Definitions of Terms Specific to This Standard:3.2.1 specimen, nrepresentative piece of the product, which is to be tested together with any substrate or treatment.4. Summary of Test Method4.1 This method uses a gas burner to produce a diffusion flame in contact with
24、 the walls and ceiling in the corner of a 2420by 3630 by 2420 mm (8 by 12 by 8 ft) high room. The burner produces a prescribed net rate of heat output of 100 kW (5690Btu/min) during the first 10 min, followed by 300 kW (17 060 Btu/min) during the next 10 min. The contribution of the wall andceiling
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME22572017STANDARDTESTMETHODFORROOMFIRETESTOFWALLANDCEILINGMATERIALSANDASSEMBLIES 墙壁 天花板 材料 组件 房间

链接地址:http://www.mydoc123.com/p-530712.html