《ASTM E2257-2003 Standard Test Method for Room Fire Test of Wall and Ceiling Materials and Assemblies《墙壁和天花板材料和组件的房屋着火试验的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM E2257-2003 Standard Test Method for Room Fire Test of Wall and Ceiling Materials and Assemblies《墙壁和天花板材料和组件的房屋着火试验的标准试验方法》.pdf(19页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E 2257 03An American National StandardStandard Test Method forRoom Fire Test of Wall and Ceiling Materials andAssemblies1This standard is issued under the fixed designation E 2257; the number immediately following the designation indicates the year oforiginal adoption or, in the case of
2、 revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This is a fire-test-response standard.1.2 This test method is intended to evaluate, under spec
3、ifiedfire-exposure conditions, the contribution to room fire growthprovided by wall or ceiling materials and assemblies, or both.The method is not intended to evaluate the fire endurance ofassemblies or fires originating in the wall assembly. Themethod provides a means to evaluate the effectiveness
4、ofthermal barriers in restricting the contribution of combustiblematerials in the wall assembly to fire growth in a room fire.1.3 This test method, simulating a fire in the corner of a2420 by 3630 mm (8 by 12 ft) room containing a single opendoorway, provides a means to evaluate the relative perfor-
5、mance of specified wall and ceiling materials or assemblieswhen they are used together in the same relationship within anenclosure, and simulating the manner in which they will beused.1.4 This test method is intended to evaluate the contributionto fire growth provided by a surface product using a sp
6、ecifiedignition source. It shall, however, be noted that the type,position and heat output of the ignition source will consider-ably influence fire growth. The thermal exposure conditionsfrom the ignition source specified in this method will result inflashover during the 20 min duration for many com
7、mon finishmaterials, in particular if specimens are mounted on the wallsand the ceiling (standard configuration).1.5 This test method provides a means for evaluating walland ceiling finish materials and assemblies, including panels,tiles, boards, sprayed or brushed coatings, etc. This test methodis
8、not intended to evaluate flooring materials or furnishings.1.6 This method shall be used in conjunction with GuideE 603, which covers instrumentation and the general effect ofvarious parameters, and Guide E 2067, which deals withfull-scale oxygen consumption calorimetry.1.7 The values stated in SI u
9、nits are to be regarded as thestandard. The units given in parentheses are for informationonly.1.8 The text of this standard references notes and footnoteswhich provide explanatory information. These notes and foot-notes (excluding those in figures) shall not be considered asrequirements of the stan
10、dard.1.9 This standard is used to measure and describe theresponse of materials, products, or assemblies to heat and flameunder controlled conditions, but does not by itself incorporateall factors required for fire-hazard or fire-risk assessment of thematerials, products, or assemblies under actual
11、fire conditions.1.10 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to us
12、e.2. Referenced Documents2.1 ASTM Standards:E 84 Test Method for Surface Burning Characteristics ofBuilding Materials2E 136 Test Method for Behavior of Materials in a VerticalTube Furnace at 750C2E 603 Guide for Room Fire Experiments2E 2067 Practice for Full-Scale Oxygen Consumption Calo-rimetry Fir
13、e Tests22.2 ISO Standards:ISO 9705 Fire TestsReaction to FireRoom Fire Test3ISO 13943 Fire SafetyVocabulary32.3 NFPA Standards:NFPA 265 Standard Method of Tests for Evaluating RoomFire Growth Contribution of Textile Wall Coverings41This test method is under the jurisdiction of ASTM Committee E05 on
14、FireStandards and is the direct responsibility of Subcommittee E05.13 on Large ScaleFire Tests.Current edition approved May 10, 2003. Published July 2003.2Annual Book of ASTM Standards, Vol 04.07.3Available from International Organization for Standardization (ISO), 1 rue deVaremb, Case postale 56, C
15、H-1211, Geneva 20, Switzerland.4Available from National Fire Protection Association (NFPA), 1 BatterymarchPark, Quincy, MA 02269-9101.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.NFPA 286 Standard Method of Tests for Evaluating Co
16、ntri-bution of Wall and Ceiling Interior Finish to Room FireGrowth43. Terminology3.1 DefinitionsFor definitions of terms used in this stan-dard, see Terminology E 176 and ISO 13943. In case ofconflict, the definitions given in Terminology E 176 shallprevail.3.1.1 assembly, na unit or structure compo
17、sed of a com-bination of materials or products, or both. E 1763.1.2 flashover, nthe rapid transitionto a state of totalsurface involvement in a fire of combustible materials withinan enclosure. E 1763.1.3 heat flux, nheat transfer to a surface per unit area,per unit time. E 1763.1.4 heat release rat
18、e, nthe heat evolved from thespecimen per unit time. E 1763.1.5 optical density of smoke, na measure of the attenu-ation of a light beam through smoke, expressed as the commonlogarithm of the ratio of the incident flux, I0, to the transmittedflux, I. E 1763.1.6 oxygen consumption principle, nthe exp
19、ression ofthe relationship between the mass of oxygen consumed duringcombustion and the heat released. E 1763.1.7 smoke, nthe airborne solid and liquid particulatesand gases evolved when a material undergoes pyrolysis orcombustion. E 1763.1.8 smoke obscuration, nreduction of light transmissionby smo
20、ke as measured by light attenuation. E 1763.2 Definitions of Terms Specific to This Standard:3.2.1 specimen, nrepresentative piece of the product,which is to be tested together with any substrate or treatment.4. Summary of Test Method4.1 This method uses a gas burner to produce a diffusionflame in c
21、ontact with the walls and ceiling in the corner of a2420 by 3630 by 2420 mm (8 by 12 by 8 ft) high room. Theburner produces a prescribed net rate of heat output of 100 kW(5690 Btu/min) during the first 10 min, followed by 300 kW(17 060 Btu/min) during the next 10 min. The contribution ofthe wall and
22、 ceiling materials or assemblies to fire growth ismeasured in terms of the time history of the incident heat fluxon the center of the floor, the time history of the temperature ofthe gases in the upper part of the room, the time to flashover,and the rate of heat release. The test is conducted with n
23、aturalventilation to the room provided through a single doorway 780by 2015 mm (30 by 80 in.) in width and height. Thecombustion products are collected in a hood feeding into aplenum connected to an exhaust duct in which measurementsare made of the gas velocity, temperature, light obscuration,and con
24、centrations of oxygen, carbon dioxide, and carbonmonoxide.5. Significance and Use5.1 This fire test is applicable to a description of certain fireperformance characteristics in appraising wall and ceilingmaterials, products, or systems under specified fire-exposureconditions in an enclosure. The tes
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME22572003STANDARDTESTMETHODFORROOMFIRETESTOFWALLANDCEILINGMATERIALSANDASSEMBLIES 墙壁 天花板 材料 组件 房屋

链接地址:http://www.mydoc123.com/p-530707.html