1、Designation: E 2174 04Standard Practice forOn-Site Inspection of Installed Fire Stops1This standard is issued under the fixed designation E 2174; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number i
2、n parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice covers the establishing of procedures toinspect fire stops, including methods for field verification andinspection.1.2 This prac
3、tice addresses all types of fire stops installedthrough or into fire resistive assemblies.NOTE 1Fire stop is defined in E 814.1.3 This practice provides methods by which a qualifiedinspector can verify that all required fire stops on a project havebeen installed and that their installations are in a
4、ccordance withthe inspection documents.1.4 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory l
5、imitations prior to use.1.5 The text of this standard references notes and footnotesthat provide explanatory material. These notes and footnotes(excluding those in tables and figures) shall not be consideredas requirements of the standard.2. Referenced Documents2.1 ASTM Standards:2E 176 Terminology
6、of Fire StandardsE 631 Terminology of Building ConstructionsE 699 Criteria for Evaluation of Agencies Involved inTesting, Quality Assurance, and Evaluating Building Com-ponentsE 814 Test Method for Fire Tests of Through-PenetrationFire Stops2.2 Other Standards:3UL 1479-94 Fire Tests of Through-Penet
7、ration Fire Stops2.3 Other Documents:4International Building Code3. Terminology3.1 DefinitionsTerms defined in Terminology E 631, Ter-minology E 176, and Criteria E 699 will prevail for terms notdefined in this document.3.2 Definitions of Terms Specific to This Standard:3.2.1 authorizing authority (
8、AA)the designated person, ororganization, or their duly authorized representative, chargedwith the administration and enforcement of the provisions ofthis inspection document.NOTE 2Examples of the AA include the responsible architect, engi-neer, building owner, or their represntative.3.2.2 authority
9、 having jurisdiction (AHJ)the designatedauthority, or their duly authorized representative, charged withthe administration and enforcement of the local fire code orbuilding code, or both.3.2.3 accredited testing laboratorya company engaged inconducting testing and possesses a valid evaluation report
10、 fortesting services and is recognized by the AHJ.3.2.4 evaluation reportan approved document issued bythe Model Code Body Evaluation Service or by the AHJ.3.2.5 inspection documentany information provided tothe inspector by the AA that is to be used as the basis for theinspection process. This info
11、rmation shall include, but is notlimited to, project specifications, contract drawings, ListedDesigns, judgments, manufacturers instructions and designs,building codes, and other documentation.NOTE 3The approved fire stop submittal should have sufficient detailsincluding the fire stop manufacturers
12、product data, a design listing of thetested fire stop or the engineering judgment design with illustrateddrawings or descriptive text or both for the purpose of verifying eachinstallation and conducting the field-inspection procedures.3.2.6 inspection formthe document contained in this stan-dard pra
13、ctice that is used to record information obtained duringthe inspection(s).3.2.7 inspectoran individual meeting the qualificationsset forth in this document and who performs the inspection.1This practice is under the jurisdiction of ASTM Committee E06 on Perfor-mance of Buildings and is the direct re
14、sponsibility of Subcommittee E06.21 onServiceability.Current edition approved Oct 1, 2004. Published October 2004. Originallyapproved in 2001. Last previous edition approved in 2001 as E 2174 01.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at
15、serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from Underwriters Laboratories (UL), Corporate Progress, 333Pfingsten Rd., Northbrook, IL 60062.4Available from the International Code Council (ICC), 5203
16、Leesburg Pike,Suite 708, Falls Church, VA 22401.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.3.2.8 judgmentan evaluation of a field condition whichdoes not conform to an existing tested and listed system.3.2.8.1 DiscussionManufact
17、urers or an accredited testinglaboratory should only issue judgments based on engineeringprinciples or available testing that approximates the conditionencountered, or both.NOTE 4The judgment is commonly referred to as an “engineeringjudgment” in the fire stopping industry. It should be noted that t
18、hesejudgments are not always issued by engineers.NOTE 5Some AHJs allow a judgment by the manufacturer if there isno tested and listed system for the non-typical condition, others do not.Most AHJs will allow judgments by accredited testing laboratories.Accredited testing laboratories can verify judgm
19、ents by manufacturers forvalidity.3.2.9 listing labelidentification applied to the product thatincludes the name of a quality assurance agency indicating thata representative sample of the product or material has beentested and evaluated by the quality assurance agency.3.2.10 quality assurance agenc
20、ya company that is en-gaged in conducting inspections, or certification, or listing andlabeling services, or any combination, and possessing a validevaluation report for quality assurance and is recognized by theAHJ.4. Summary of Practice4.1 This practice sets forth the minimum requirements toqualif
21、y an inspector to use this practice.4.2 This practice identifies the types of fire stops subject tothe inspection procedures outlined in this practice.4.3 This practice provides the minimum information re-quired to verify compliance of installed fire stops with inspec-tion documents.4.4 This practic
22、e provides a standard inspection form that isto be used when inspecting fire stops.4.5 This practice provides a standard report format that is tobe used when reporting the inspection results.5. Significance and Use5.1 This practice is intended to provide a standard set ofguidelines that are to be fo
23、llowed when conducting andreporting on inspections of installed fire stops.5.2 This practice is intended to provide a means to verifycompliance of the installed fire stops to the inspection docu-ments.5.3 This practice is not intended to provide a basis forselecting installers or products or both.5.
24、4 This practice is not intended to establish any perfor-mance criteria of the inspected fire stops.6. Inspector6.1 QualificationsAn inspector shall be acceptable to theAHJ and shall meet at least one of the following requirements:6.1.1 Meet the criteria contained in E 699 for agenciesinvolved in qua
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME21742004STANDARDPRACTICEFORONSITEINSPECTIONOFINSTALLEDFIRESTOPS 安装 防火墙 现场 检验 标准 实施 规范 PDF

链接地址:http://www.mydoc123.com/p-530466.html