ASTM E2121-2008 Standard Practice for Installing Radon Mitigation Systems in Existing Low-Rise Residential Buildings.pdf
《ASTM E2121-2008 Standard Practice for Installing Radon Mitigation Systems in Existing Low-Rise Residential Buildings.pdf》由会员分享,可在线阅读,更多相关《ASTM E2121-2008 Standard Practice for Installing Radon Mitigation Systems in Existing Low-Rise Residential Buildings.pdf(13页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E 2121 08Standard Practice forInstalling Radon Mitigation Systems in Existing Low-RiseResidential Buildings1This standard is issued under the fixed designation E 2121; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, th
2、e year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice describes methods for reducing radonentry into existing attached and detached residential buil
3、dingsthree stories or less in height. This practice is intended for useby trained, certified or licensed, or both, or otherwise qualifiedindividuals.1.2 These methods are based on radon mitigation techniquesthat have been effective in reducing radon levels in a widerange of residential buildings and
4、 soil conditions. These fanpowered mitigation methods are listed in Appendix X1. Moredetailed information is contained in references cited throughoutthis practice.1.3 This practice is intended to provide radon mitigationcontractors with a uniform set of practices that will ensure ahigh degree of saf
5、ety and the likelihood of success in retrofit-ting low rise residential buildings with radon mitigationsystems.1.4 The methods described in this practice apply to cur-rently occupied or formerly occupied residential buildings,including buildings converted or being converted to residentialuse, as wel
6、l as residential buildings changed or being changedby addition(s) or alteration(s), or both. The radon reductionactivities performed on new dwellings, while under construc-tion, before occupancy, and for up to one year after occupancy,are covered by Guide E 1465.1.5 This practice also is intended as
7、 a model set of practices,which can be adopted or modified by state and local jurisdic-tions, to fulfill objectives of their specific radon contractorcertification or licensure programs. Radon mitigation per-formed in accordance with this practice is considered ordinaryrepair.1.6 The methods address
8、ed in this practice include thefollowing categories of contractor activity: general practices,building investigation, systems design, systems installation,materials, monitors and labeling, post-mitigation testing, anddocumentation.1.7 This standard does not purport to address all of thesafety concer
9、ns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. See Section 6 forspecific safety hazards.2. Referenced Documents2.1 ASTM Standards:
10、2E 631 Terminology of Building ConstructionsE 1465 Practice for Radon Control Options for the Designand Construction of New Low-Rise Residential Buildings3E 1745 Specification for Plastic Water Vapor RetardersUsed in Contact with Soil or Granular Fill under ConcreteSlabs2.2 Government Publications:E
11、PA “Asbestos School Hazard Abatement ReauthorizationAct,” regulation 40 CFR Part 763, Subpart E.4EPA “A Citizens Guide to Radon (Second Edition),” EPA402-K92-001, May 1992.4EPA “Consumers Guide to Radon Reduction,” EPA 402-K92-003, August 1992.4EPA “Handbook, Sub-Slab Depressurization for Low-Permea
12、bility Fill Material,” EPA/625/6-91/029, July1991.4EPA “Home Buyers and Sellers Guide,” EPA 402K-00008, July 2000.4EPA “National Emission Standard for Asbestos,” 40 CFR61, Subpart M.4EPA “ Radon Mitigation Standards,” EPA 402-R-93-078,April 1994.4EPA “Radon Reduction Techniques for Existing Detached
13、Houses, Technical Guidance (Second Edition),” EPA/625/587/019, revised January 1988.4EPA “Radon Reduction Techniques for Existing DetachedHouses, Technical Guidance (Third Edition) for ActiveSoil Depressurization Systems,” EPA/625/R-93-011, Oc-tober 1993.41This practice is under the jurisdiction of
14、ASTM Committee E06 on Perfor-mance of Buildings and is the direct responsibility of Subcommittee E06.41 on AirLeakage and Ventilation Performance.Current edition approved June 15, 2008. Published August 2008. Originallyapproved in 2001. Last previous edition approved in 2003 as E 2121 03.2For refere
15、nced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Withdrawn.4Available from United States Environmental Protection Agency
16、 (EPA), ArielRios Bldg., 1200 Pennsylvania Ave., NW, Washington, DC 20460, http:/www.epa.gov.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.NCRP “Measurement of Radon and Radon Daughters inAir,” NCRP Report No. 97, 1988.5NIOSH “Guid
17、e to Industrial Respiratory Protection,”NIOSH Publication No. 87116.6OSHA “Asbestos Standard for the Construction Indus-try” 29 CFR 1926.1102.7OSHA “Hazard Communication Standard for the Construc-tion Industry,” 29 CFR 1926.59.7OSHA “Occupational Safety and Health Regulations, Ioniz-ing Radiation,”
18、29 CFR 1910.96.7OSHA “Respiratory Protection Standard,” 29 CFR1920.134, 1998.7OSHA “Safety and Health Regulations for Construction,Ionizing Radiation,” 29 CFR 1926.53.73. Terminology3.1 DefinitionsDefinitions of terms used in this practiceare defined in accordance with Terminology E 631.3.2 Definiti
19、ons of Terms Specific to This Standard:3.2.1 active soil depressurization (ASD), na family ofradon mitigation systems involving mechanically-driven soildepressurization, including sub-slab depressurization (SSD),sump pit depressurization (SPD), drain tile depressurization(DTD), hollow block wall dep
20、ressurization (BWD), and sub-membrane depressurization (SMD) (see Appendix X2).3.2.2 backdrafting, na condition where the normal move-ment of combustion products up a flue (due to the buoyancy ofthe hot flue gases), is reversed, so that the combustion productsenter the building (see pressure-induced
21、 spillage).3.2.3 communication test, na diagnostic test to evaluatethe potential effectiveness of a sub-slab depressurization sys-tem by applying a vacuum beneath the slab and measuring,either with a micromanometer or with a heatless smoke device,the extension of the vacuum field. Also called pressu
22、re-fieldextension test.3.2.4 contractor, nfor the purposes of this practice, acontractor is one who contracts to performs radon reductionactivities or is an employee of one who contracts to perform orperforms radon reduction activities, with the expectation thatpayment will be received for the work
23、performed. A personwho does radon reduction activities as an employee of abuilding owner is also a contractor for purposes of this standardpractice. Persons whose normal activity is not radon reduction,but who do work related to radon reduction like indoor airquality consultants, radon consultants,
24、plumbers, building con-tractors, or employees of these persons are all viewed ascontractors when performing radon reduction activities cov-ered by this practice.3.2.5 crawlspace depressurization (CSD) (active), na ra-don mitigation technique designed to achieve lower air pres-sure in the crawlspace
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME21212008STANDARDPRACTICEFORINSTALLINGRADONMITIGATIONSYSTEMSINEXISTINGLOWRISERESIDENTIALBUILDINGSPDF

链接地址:http://www.mydoc123.com/p-530326.html