1、Designation: E2047 10 (Reapproved 2015)Standard Test Method forWet Insulation Integrity Testing of Photovoltaic Arrays1This standard is issued under the fixed designation E2047; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the y
2、ear of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method covers a procedure to determine theinsulation resistance of a photovoltaic (PV) array (or itsc
3、omponent strings), that is, the electrical resistance betweenthe arrays internal electrical components and is exposed,electrically conductive, non-current carrying parts and surfacesof the array.1.2 This test method does not establish pass or fail levels.The determination of acceptable or unacceptab
4、le results isbeyond the scope of this test method.1.3 The values stated in SI units are to be regarded asstandard. No other units of measurement are included in thisstandard.1.4 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibil
5、ity of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2E772 Terminology of Solar Energy ConversionE1328 Terminology Relating to Photovoltaic Solar Energy
6、Conversion (Withdrawn 2012)3E1462 Test Methods for Insulation Integrity and GroundPath Continuity of Photovoltaic Modules3. Terminology3.1 DefinitionsDefinitions of terms used in this testmethod may be found in Terminologies E772 and E1328.3.2 Definitions of Terms Specific to This Standard:3.2.1 ins
7、ulation resistance, nthe electrical resistance of aphotovoltaic arrays insulation, measured between the photo-voltaic circuit and exposed, electrically conductive non-current-carrying parts and surfaces of the array.3.2.2 metal oxide varistor MOV, na surge protectiondevice.3.2.3 photovoltaic circuit
8、the active electrical circuit thatconducts the photovoltaic generated power.4. Summary of Test Method4.1 A procedure is provided for testing the electrical isola-tion between the arrays internal electrical components and itsexposed, electrically conductive, non-current carrying partsand surfaces of
9、the array.4.2 The procedure offers two ways to connect the arrayduring the test, either open-circuited or short-circuited. Eachoption has advantages and disadvantages (see 5.5).4.3 A wetting solution is applied to the array, then a voltageis applied between the PV circuit and the exposed, electrical
10、lyconductive, non-current carrying parts and surfaces of thearray, while monitoring the current or resistance, to findlocalized regions where the insulation resistance is signifi-cantly reduced by the wetting solution. The array is theninspected for evidence of possible arcing.5. Significance and Us
11、e5.1 The design of a PV module or system intended toprovide safe conversion of the suns radiant energy into usefulelectricity must take into consideration the possibility of hazardshould the user come into contact with the electrical potentialof the array. In addition, the insulation system provides
12、 abarrier to electrochemical corrosion, and insulation flaws canresult in increased corrosion and reliability problems. This testmethod describes a procedure for verifying that the design andconstruction of the array provides adequate electrical isolationthrough normal installation and use.At no loc
13、ation on the arrayshould the PV-generated electrical potential be accessible, withthe obvious exception of the output leads. The isolation isnecessary to provide for safe and reliable installation, use, andservice of the PV system.5.2 This test method describes a procedure for determiningthe ability
14、 of the array to provide protection from electrical1This test method is under the jurisdiction of ASTM Committee E44 on Solar,Geothermal and OtherAlternative Energy Sources, and is the direct responsibility ofSubcommittee E44.09 on Photovoltaic Electric Power Conversion.Current edition approved Marc
15、h 1, 2015. Published April 2015. Originallyapproved in 1999. Last previous edition approved in 2010 as E204710. DOI:10.1520/E2047-10R15.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume in
16、formation, refer to the standards Document Summary page onthe ASTM website.3The last approved version of this historical standard is referenced onwww.astm.org.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States1hazards. Its primary use is
17、 to find insulation flaws that could bedangerous to persons who may come into contact with thearray. Corrective action taken to address such flaws is beyondthe scope of this test method.5.3 This procedure may be specified as part of a series ofacceptance tests involving performance measurements andd
18、emonstration of functional requirements. Large arrays can betested in smaller segments. The size of the array segment to betested (called “circuit under test” in this test method) is usuallyselected at a convenient break point and sized such that theexpected resistance or current reading is within t
19、he middlethird of the meters range.5.4 Insulation leakage resistance and insulation leakagecurrent leakage are strong functions of array dimensions,ambient relative humidity, absorbed water vapor, and otherfactors. For this reason, it is the responsibility of the user of thistest method to specify t
20、he minimum acceptable leakage resis-tance for this test.5.4.1 Even though a numerical quantity is specified, actualresults are often pass-fail in that when a flaw is found, theleakage current changes from almost nothing to the full scalevalue on the meter.5.5 The user of this test method must specif
21、y the optionused for connection to the array during the test. The short-circuited option requires a shorting device with leads toconnect the positive and negative legs of the circuit under test.For larger systems, where the shorting device may have to berated for high current and voltage levels, the
22、 open-circuitedoption may be preferred. The open-circuited option requiresthe user to correct readings to account for the PV-generatedvoltage, and the procedure for making such corrections isbeyond the scope of this test method. The short-circuitedoption may be easier for small systems where the vol
23、tage andcurrent levels are low and the distance between the plus andminus leads of the circuit under test are small. The short-circuited option minimizes the chance of exposing arraycomponents to voltage levels above those for which they arerated.6. Apparatus6.1 Choose one of the following, dependin
24、g on the optionselected (see 4.2 and 5.5):6.1.1 Variable dc Voltage Power SupplyA dc voltagepower supply capable of providing a nominal test voltage of500 V, as specified in Test Method E1462. A common term forthis apparatus is insulation tester.6.1.2 MegohmmeterA high-impedance ohmmeter, orsimilar
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME204720102015STANDARDTESTMETHODFORWETINSULATIONINTEGRITYTESTINGOFPHOTOVOLTAICARRAYS 光电 阵列 绝缘 完整性

链接地址:http://www.mydoc123.com/p-530149.html