《ASTM E1998-2011(2018) Standard Guide for Assessing Depressurization-Induced Backdrafting and Spillage from Vented Combustion Appliances.pdf》由会员分享,可在线阅读,更多相关《ASTM E1998-2011(2018) Standard Guide for Assessing Depressurization-Induced Backdrafting and Spillage from Vented Combustion Appliances.pdf(14页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E1998 11 (Reapproved 2018)Standard Guide forAssessing Depressurization-Induced Backdrafting andSpillage from Vented Combustion Appliances1This standard is issued under the fixed designation E1998; the number immediately following the designation indicates the year oforiginal adoption or
2、, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This guide describes and compares different methods forassessing the potential
3、for, or existence of, depressurization-induced backdrafting and spillage from vented residentialcombustion appliances.1.2 Assessment of depressurization-induced backdraftingand spillage is conducted under either induced depressurizationor natural conditions.1.3 Residential vented combustion applianc
4、es addressed inthis guide include hot water heaters and furnace. The guide alsois applicable to boilers.1.4 The methods given in this guide are applicable toCategory I (draft-hood- and induced-fan-equipped) furnaces.The guide does not apply to Category III (power-vent-equipped) or Category IV (direc
5、t-vent) furnaces.1.5 The methods in this guide are not intended to identifybackdrafting or spillage due to vent blockage or heat-exchanger leakage.1.6 This guide is not intended to provide a basis fordetermining compliance with code requirements on applianceand venting installation, but does include
6、 a visual assessmentof the installation. This assessment may indicate the need for athorough inspection by a qualified technician.1.7 Users of the methods in this guide should be familiarwith combustion appliance operation and with making house-tightness measurements using a blower door. Some method
7、sdescribed in this guide require familiarity with differential-pressure measurements and use of computer-based data-logging equipment.1.8 The values stated in SI units are to be regarded asstandard. No other units of measurement are included in thisstandard.1.9 This guide does not purport to address
8、 all safetyconcerns, if any, associated with its use. It is the responsibilityof the user to establish appropriate safety, health, and envi-ronmental practices and to determine the applicability ofregulatory limitations prior to use. Carbon monoxide (CO)exposure or flame roll-out may occur when perf
9、orming certainprocedures given in this guide. See Section 7, for precautionsthat must be taken in conducting such procedures.1.10 This international standard was developed in accor-dance with internationally recognized principles on standard-ization established in the Decision on Principles for theD
10、evelopment of International Standards, Guides and Recom-mendations issued by the World Trade Organization TechnicalBarriers to Trade (TBT) Committee.2. Referenced Documents2.1 ASTM Standards:2D1356 Terminology Relating to Sampling and Analysis ofAtmospheresE631 Terminology of Building ConstructionsE
11、779 Test Method for DeterminingAir Leakage Rate by FanPressurization2.2 CAN/CGSB Standard:3CAN/CGSB 51.71 The Spillage TestMethod to Determinethe Potential for Pressure-Induced Spillage from Vented,Fuel-Fired; Space HeatingAppliances; Water Heaters, andFireplaces2.3 ANSI Standard:4ANSI Z21.47 Gas-fi
12、red Central Furnace2.4 NFPA Standard:5NFPA 54 National Fuel Gas Code1This guide is under the jurisdiction of ASTM Committee E06 on Performanceof Buildings and is the direct responsibility of Subcommittee E06.41 on AirLeakage and Ventilation Performance.Current edition approved July 1, 2018. Publishe
13、d July 2018. Originally approvedin 1999. Last previous edition approved in 2011 as E1998 11. DOI: 10.1520/E1998-11R18.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer t
14、o the standards Document Summary page onthe ASTM website.3Available from Canadian General Standards Board (CGSB), 11 Laurier St.,Phase III, Place du Portage, Gatineau, Quebec K1A 0S5, Canada, http:/www.tpsgc-pwgsc.gc.ca/ongc-cgsb.4Available from American National Standards Institute (ANSI), 25 W. 43
15、rd St.,4th Floor, New York, NY 10036, http:/www.ansi.org.5Available from National Fire Protection Association (NFPA), 1 BatterymarchPark, Quincy, MA 02169-7471, http:/www.nfpa.org.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United StatesThis in
16、ternational standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT)
17、Committee.13. Terminology3.1 Definitions:3.1.1 For definitions of general terms related to buildingconstruction used in this specification, refer to TerminologyE631, and for general terms related to sampling and analysis ofatmospheres, refer to Terminology D1356.3.2 Definitions of Terms Specific to
18、This Standard:3.2.1 air leakage, nthe movement or flow of air throughthe building envelope which is driven by a pressure differentialacross the envelope.3.2.2 air leakage rate, nthe volume of air movement perunit time across the building envelope.3.2.3 airtightness, nthe degree to which the building
19、envelope resists flow of air.3.2.4 blower door, na fan pressurization device incorpo-rating a controllable fan and instruments for airflow measure-ment and building pressure difference measurement thatmounts securely in a door or other opening.3.2.5 Category 1 appliance, nan appliance that operatesw
20、ith non-positive static pressure and with a vent gas tempera-ture that avoids excessive condensate production in the vent(see NFPA 54).3.2.6 Category III appliance, nan appliance that operateswith a positive vent pressure and with a vent gas temperaturethat avoids excessive condensate production in
21、the vent (seeNFPA 54).3.2.7 Category IV appliance, nan appliance that operateswith a positive vent pressure and with a vent gas temperaturethat may cause excessive condensate production in the vent(see NFPA 54).3.2.8 combustion system spillage, nentry of combustionproducts into a building from dilut
22、ion air inlets, vent connectorjoints, induced draft fan case opening, combustion air inlets, orother locations in the combustion or venting system of a ventedcombustion appliance (boiler, fireplace, furnace, or waterheater), caused by backdrafting, vent blockage, or leaks in theventing system.3.2.9
23、continuous pressure differential, nthe incrementalhouse depressurization due to fans that can be operatedcontinuously, such as furnace blower or supply/exhaust venti-lator.3.2.10 downdrafting, nthe reversal of the ordinary (up-ward) direction of air flow in a chimney or flue when no ventedcombustion
24、 appliances are operating (as opposed tobackdrafting, which occurs when vented combustion appli-ances are operating).3.2.11 house depressurization, nthe situation, pertainingto a specific location in a house, whereby the static pressure atthat location is lower than the static pressure in the immedi
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME199820112018STANDARDGUIDEFORASSESSINGDEPRESSURIZATIONINDUCEDBACKDRAFTINGANDSPILLAGEFROMVENTEDCOMBUSTIONAPPLIANCESPDF

链接地址:http://www.mydoc123.com/p-530015.html