ASTM E1934-1999a(2010) Standard Guide for Examining Electrical and Mechanical Equipment with Infrared Thermography《用红外线温度记录法检查电气及机械设备的标准指南》.pdf
《ASTM E1934-1999a(2010) Standard Guide for Examining Electrical and Mechanical Equipment with Infrared Thermography《用红外线温度记录法检查电气及机械设备的标准指南》.pdf》由会员分享,可在线阅读,更多相关《ASTM E1934-1999a(2010) Standard Guide for Examining Electrical and Mechanical Equipment with Infrared Thermography《用红外线温度记录法检查电气及机械设备的标准指南》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E1934 99a (Reapproved 2010)Standard Guide forExamining Electrical and Mechanical Equipment withInfrared Thermography1This standard is issued under the fixed designation E1934; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revi
2、sion, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This guide lists the responsibilities of the end user andthe infrared thermographer when examining e
3、lectrical andmechanical systems.1.2 This guide outlines the specific content required todocument qualitative and quantitative infrared examinations ofelectrical and mechanical equipment.21.3 This guide may involve use of equipment and materialsin the presence of heated, moving or all of these or ele
4、ctricallyenergized equipment.1.4 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations
5、 prior to use.2. Referenced Documents2.1 ASTM Standards:3E1316 Terminology for Nondestructive Examinations3. Terminology3.1 Definitions:3.1.1 end userthe person responsible for using the infor-mation provided by an infrared examination.3.1.2 exceptionan abnormally warm or cool connector,conductor or
6、 component.3.1.3 infrared examinationthe use of an infrared imagingsystem to provide thermal data about a structure, system, objector process.3.1.4 inventory lista list of the equipment by the infraredthermographer.3.1.5 qualified assistanta person provided and authorizedby the end user to perform t
7、he tasks required by the infraredthermographer. He/she shall be knowledgeable of the operationand history of the equipment to be examined and of all safetypractices and rules of the end user.3.1.6 qualitative infrared inspectionan infrared examina-tion that provides images of exceptions but not temp
8、eraturedata.3.1.7 quantitative infrared inspectionan infrared exami-nation that provides both images of exceptions and temperaturedata.3.2 See also Terminology E1316.4. Significance and Use4.1 This guide can be used by an end user to specify infraredexaminations of electrical and mechanical equipmen
9、t and aninfrared thermographer to perform them.4.2 This guide lists the joint responsibilities of the end userand the infrared thermographer when using infrared thermog-raphy.4.3 The purpose of an infrared examination is to identifyand document exceptions in the end users electrical ormechanical sys
10、tems, or both.4.3.1 In electrical equipment, warm exceptions are usuallycreated by an increase in resistance caused by loose ordeteriorated connections, short circuits, overloads, load imbal-ances or faulty, mismatched or improperly installed compo-nents. Cool exceptions are usually caused by failed
11、 compo-nents.4.3.2 In mechanical equipment, warm exceptions are usu-ally created by friction caused by improper lubrication, mis-alignment, worn components or mechanical loading anomalies.Cool exceptions are usually caused by failed components.4.3.3 Exceptions in insulation systems are usually cause
12、d bymissing or deteriorated materials, improper installation orinsufficient amounts of material.4.4 Providing opinions about the causes of exceptions, theintegrity of the equipment or recommendations for correctiveactions require knowledge and skills beyond those of infraredthermography.1This guide
13、is under the jurisdiction of ASTM Committee E07 on Nondestruc-tive Testing and is the direct responsibility of Subcommittee E07.10 on SpecializedNDT Methods.Current edition approved June 1, 2010. Published November 2010. Originallyapproved in 1997. Last previous edition approved in 2005 as E1934 - 9
14、9a (2005)1.DOI: 10.1520/E1934-99AR10.2This guide is adapted from the Guideline for Infrared Inspection and Mechani-cal Systems developed by Infraspection Institute, 425 Ellis Street, Burlington, NJ08016.3For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Ser
15、vice at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.4.5 Infrared examinations provide data abou
16、t equipment atthe time of examination only.4.6 Infrared examinations are not remedial.4.7 An infrared examination of electrical and mechanicalequipment does not assure its proper operation. Other tests andproper maintenance are necessary to ensure their reliableperformance.5. Personnel Responsibilit
17、ies5.1 The infrared thermographer shall:5.1.1 Have sufficient knowledge of the components, con-struction and theory of electrical or mechanical equipment, orboth, to understand the observed patterns of radiation,5.1.2 Be knowledgeable of, and comply with, the safetypractices and rules of the end use
18、r, and5.1.3 Use an infrared imaging system with imaging orradiometric capabilities, or both, sufficient to meet the exami-nation requirements.5.2 Unless he/she is a licensed electrician, professionalengineer or has other equivalent qualifications, the infraredthermographer:5.2.1 Shall not perform an
19、y tasks that are normally done bythese personnel. Unless so qualified and authorized by the enduser, the infrared thermographer,5.2.2 Shall not remove or replace covers or open or closecabinets containing electrical or mechanical equipment,5.2.3 Shall not measure electric loads of equipment, and5.2.
20、4 Shall not touch any equipment and shall maintain asafe distance from it.5.3 The qualified assistant shall fulfill the responsibilitieslisted in 3.1.5, 6.1, 6.2, 6.4 through 6.4.3, 6.7.1, and 6.8.5.4 The end user shall assume full responsibility for conse-quences resulting from actions taken, or no
21、t taken, as a resultof data provided by an infrared examination.6. Procedure6.1 The end user shall provide, to accompany the infraredthermographer, a qualified assistant who is knowledgeable ofthe operation and history of the equipment to be examined.6.2 With the assistance of the qualified assistan
22、t, the infra-red thermographer shall develop an inventory list of theequipment to be examined in a logical, efficient and safe routethrough the facility.6.3 The infrared thermographer shall perform a calibrationtest(s), before each quantitative infrared examination, to ensurethat all temperature-mea
23、suring equipment is within the manu-facturers standard specifications for accuracy.6.4 The qualified assistant shall prepare the equipment forexamination by:6.4.1 Obtaining authorization necessary to gain access tothe equipment to be examined and notifying operations per-sonnel of the examination ac
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME19341999A2010STANDARDGUIDEFOREXAMININGELECTRICALANDMECHANICALEQUIPMENTWITHINFRAREDTHERMOGRAPHY 红外线

链接地址:http://www.mydoc123.com/p-529854.html