《ASTM E1725-2008 Standard Test Methods for Fire Tests of Fire-Resistive Barrier Systems for Electrical System Components《电气系统元件耐火阻挡层系统耐火试验的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM E1725-2008 Standard Test Methods for Fire Tests of Fire-Resistive Barrier Systems for Electrical System Components《电气系统元件耐火阻挡层系统耐火试验的标准试验方法》.pdf(11页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E 1725 08An American National StandardStandard Test Methods forFire Tests of Fire-Resistive Barrier Systems for ElectricalSystem Components1This standard is issued under the fixed designation E 1725; the number immediately following the designation indicates the year oforiginal adoption
2、 or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 These test methods cover fire-test-response.1.2 These fire-test-response te
3、st methods provide informa-tion on the temperatures recorded on the electrical systemcomponent within a fire-resistive barrier system during theperiod of exposure.1.3 This standard is used to measure and describe theresponse of materials, products, or assemblies to heat andflame under controlled con
4、ditions, but does not by itselfincorporate all factors required for fire hazard or fire riskassessment of the materials, products, or assemblies underactual fire conditions.1.4 Potentially important factors and fire characteristics notaddressed by these test methods include, but are not limited to:1
5、.4.1 The performance of the fire-resistive barrier systemconstructed with components other than those tested.1.4.2 An evaluation of the functionality of the electricalsystem within the fire-resistive barrier system.1.4.3 An evaluation of the ampacity of the electrical systemwithin the fire-resistive
6、 barrier system.1.4.4 An evaluation of the smoke, toxic gases, corrosivity,or other products of heating.1.4.5 A measurement of the flame spread characteristicsover the surface of the fire-resistive barrier system.1.4.6 An evaluation of through-penetration sealing methods.1.4.7 Combustibility of mate
7、rials in the fire-resistive barriersystem or of the electrical system components.1.4.8 The need for supports beyond those normally re-quired.1.4.9 Environmental conditions in the area of service.1.5 The values stated in inch-pound units are to be regardedas the standard. The SI units given in parent
8、heses are forinformation only.1.6 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitation
9、s prior to use.2. Referenced Documents2.1 ASTM Standards:2E119 Test Methods for Fire Tests of Building Constructionand MaterialsE 1529 Test Methods for Determining Effects of LargeHydrocarbon Pool Fires on Structural Members and As-semblies3. Terminology3.1 Definitions:3.1.1 air droplengths of open
10、run conductors or cablessupported only at each end.3.1.2 electrical system componentscable trays, conduitsand other raceways, open run cables and conductors, cables,conductors, cabinets, and other components, as defined or usedin the National Electrical Code, and air drops as defined in3.1.1.3.1.3 f
11、ire-resistive barrier systema specific constructionof devices, materials, or coatings installed around, or appliedto, the electrical system components.3.1.4 specimena construction consisting of electrical sys-tem components and a fire-resistive barrier system.3.1.5 test assemblyhorizontal or vertica
12、l construction onwhich test specimens are to be mounted together with associ-ated instrumentation.4. Significance and Use4.1 These fire-test-response test methods evaluate, under thespecified test conditions, the ability of a fire-resistive barriersystem to inhibit thermal transmission to the electr
13、ical systemcomponent within.4.2 In these procedures, the specimens are subjected to oneor more specific sets of laboratory test conditions. If differenttest conditions are substituted or the end-use conditions are1These test methods are under the jurisdiction of ASTM Committee E05 on FireStandards a
14、nd are the direct responsibility of Subcommittee E05.11 on FireResistance.Current edition approved Jan. 1, 2008. Published February 2008. Originallyapproved in 1995. Last previous edition approved in 2007 as E 1725072For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM
15、 Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.changed, it is not always poss
16、ible by or from these test methodsto predict changes in the fire test response characteristicsmeasured. Therefore, the results are valid only for the fire testexposure conditions described in these procedures.4.3 These test methods provide a measurement of thetransmission of heat to the electrical s
17、ystem components withinthe barrier system.4.4 These test methods provide qualification of a fireresis-tive barrier system as one element of an electrical systemdesigned to maintain continuous operation of critical functionsand processes for a specific fire resistance rating.4.4.1 In addition to the
18、temperature data provided by thesetest methods, numerous other factors, such as referenced in 1.4shall be considered in specifying such a system.5. Control of Fire Test5.1 Fire Test Exposure Conditions:5.1.1 Time-Temperature CurveMaintain the fire environ-ment within the furnace in accordance with t
19、he standardtime-temperature curve shown in Test Method E119 or therapid temperature rise curve shown in Test Method E 1529.5.2 Furnace Temperatures:5.2.1 The temperature fixed by the curve shall be theaverage temperature obtained from readings of thermocouplesdistributed within the test furnace. Dis
20、perse the thermocouplesas symmetrically as possible within the furnace to measure thetemperature near all exterior surfaces of the specimen. Do notplace the thermocouples at locations where temperature read-ings would be effected by drafts within the furnace.5.2.2 Measure and report the temperatures
21、 at intervals notexceeding 1 min.5.3 Furnace Thermocouples:5.3.1 Test Method E 119Enclose the thermocouples insealed protection tubes of such materials and dimensions thatthe time constant of the protected thermocouple assembly lieswithin the range from 300 to 400 s3. The exposed length of thepyrome
22、ter tube and thermocouple in the furnace chamber shallbe not less than 12 in. (305 mm).5.3.2 Test Methods E 1529Measure the temperature of thegases adjacent to and impinging on the test specimens usingfactory manufactured 0.25-in. (6-mm) outside diameter (OD),Inconel4-sheathed, Type K, chromel-alume
23、l4thermocouples.The time constant, in air, of the thermocouple assemblies shallbe less than 60 s. Use standard calibration thermocouples withan accuracy of 6 0.75 %. A minimum length of 20 diameters(125 mm) of the sheathed junction end of the thermocoupleshall be mounted parallel to the surface of t
24、he test specimen.5.4 Furnace Thermocouple LocationsPosition the furnacecontrol thermocouples before the start of the fire exposure test.It shall be permitted to move the thermocouple to avoidtouching the specimen as a result of its deflection during thetest.5.4.1 Place the junction of each thermocou
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME17252008STANDARDTESTMETHODSFORFIRETESTSOFFIRERESISTIVEBARRIERSYSTEMSFORELECTRICALSYSTEMCOMPONENTS

链接地址:http://www.mydoc123.com/p-529314.html