1、Designation: E1514 98 (Reapproved 2011)Standard Specification forStructural Standing Seam Steel Roof Panel Systems1This standard is issued under the fixed designation E1514; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year
2、of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers the design, construction, andweatherability of structural standing seam steel roof panels
3、ystems. It includes performance requirements for the follow-ing elements only: panels, concealed panel clips, panel/clipanchorage, and panel joint sealers.NOTE 1These systems are used on both low-slope and steep-sloperoof applications. They also are used with or without an underlying deckor sheathin
4、g.1.2 The objective of this specification is to provide for theoverall performance of the structural standing seam steel roofpanel system as defined in 3.2.6 during its service life in orderto provide weather protection, carry the specified design loads,and allow proper access over the roof surface
5、in order toprovide for periodic maintenance of equipment by the owner.1.3 In addition to structural, the specifier shall evaluateother characteristics beyond the scope of this specification thataffect the final choice of roof construction. These include, butare not limited to, functional, legal, ins
6、urance, and economicconsiderations. See Appendix X1 for specifiers checklist.1.4 The specification is not intended to exclude products orsystems not covered by the referenced documents.1.5 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathem
7、aticalconversions to SI units that are provided for information onlyand are not considered standard.1.6 The text of this specification contains notes and foot-notes that provide explanatory information and are not require-ments of this specification.2. Referenced Documents2.1 ASTM Standards:2A463/A4
8、63M Specification for Steel Sheet, Aluminum-Coated, by the Hot-Dip ProcessA653/A653M Specification for Steel Sheet, Zinc-Coated(Galvanized) or Zinc-Iron Alloy-Coated (Galvannealed)by the Hot-Dip ProcessA792/A792M Specification for Steel Sheet, 55 %Aluminum-Zinc Alloy-Coated by the Hot-Dip ProcessA87
9、5/A875M Specification for Steel Sheet, Zinc-5 % Alu-minum Alloy-Coated by the Hot-Dip ProcessC711 Test Method for Low-Temperature Flexibility andTenacity of One-Part, Elastomeric, Solvent-Release TypeSealantsC765 Test Method for Low-Temperature Flexibility of Pre-formed Tape SealantsC879 Test Method
10、s for Release Papers Used with Pre-formed Tape SealantsD1667 Specification for Flexible Cellular MaterialsPoly(Vinyl Chloride) Foam (Closed-Cell)D3310 Test Method for Determining Corrosivity of Adhe-sive MaterialsE631 Terminology of Building ConstructionsE1592 Test Method for Structural Performance
11、of SheetMetal Roof and Siding Systems by Uniform Static AirPressure DifferenceE1646 Test Method for Water Penetration of Exterior MetalRoof Panel Systems by Uniform Static Air PressureDifferenceE1680 Test Method for Rate of Air Leakage ThroughExterior Metal Roof Panel SystemsG21 Practice for Determi
12、ning Resistance of Synthetic Poly-meric Materials to Fungi2.2 FM Approvals LLC Standard:3Approval Standard for Class 1 Panel Roofs, Class Number44712.3 UL Standard:4UL 580 Standard for Safety, Tests for Uplift Resistance ofRoof Assemblies2.4 AISI Document:5S100 North American Specification for the D
13、esign of Cold-Formed Steel Structure Members1This specification is under the jurisdiction of ASTM Committee E06 onPerformance of Buildings and is the direct responsibility of Subcommittee E06.57on Performance of Metal Roof Systems.Current edition approved Aug. 15, 2011. Published October 2011. Origi
14、nallyapproved in 1993. Last previous edition approved in 2003 as E1514 98 (2003).DOI: 10.1520/E1514-98R11.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standa
15、rds Document Summary page onthe ASTM website.3Available from FM Approvals LLC, 1151 Boston Providence Turnpike, P.O.Box 9102, Norwood, MA 02062, http:/.4Available from Underwriters Laboratories (UL), 2600 N.W. Lake Rd., Camas,WA 98607-8542, http:/.5Available from American Iron and Steel Institute (A
16、ISI), 1140 ConnecticutAve., NW, Suite 705, Washington, DC 20036, http:/www.steel.org.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.2.5 MBMA Document:6MBMA Low Rise Building Systems Manual, Latest Edition2.6 ASHRAE Document:71997 AS
17、HRAE Handbook of Fundamentals3. Terminology3.1 Definitions:3.1.1 Refer to the latest edition of MBMA Low RiseBuilding Systems Manual and Terminology E631 for defini-tions of terms used in this specification.3.2 Descriptions of Terms Specific to This Standard:3.2.1 construction loads, nthose loads en
18、countered duringthe erection of the roof system only.3.2.2 fixing line, na line or adjacent lines of fixed points.3.2.3 maintenance loads, nloads including, but not lim-ited to, personnel, equipment, and materials required to main-tain functionality of the building.3.2.4 oil canning, na waviness tha
19、t occurs in flat areas ofmetal.3.2.5 sealer, nany material that is used to seal cracks,joints, or laps.3.2.6 structural standing seam steel roof panel system, nasteel roof system designed to resist positive and negative loadsapplied normal to the panel surface without the benefit of asupporting deck
20、 or sheathing.3.2.7 thermal movement, nthe reaction of the roof systemin response to changes in the panel temperature.4. Performance Requirements4.1 DesignThe roof system shall be designed for specifieddesign loads and thermal effects.4.1.1 Minimum design loads shall be determined by thegoverning co
21、de or the design professional.4.1.2 The finished roof system shall be capable of sustaininga minimum 200-lb (0.9-kN) concentrated load on any 12-in. by12-in. (300-mm by 300-mm) area of finished roof withoutcausing seam separation, permanent panel buckling, or loss ofweathertightness.4.1.3 Thermal mo
22、vement shall be provided for in accor-dance with Sections 7 and 8. Temperature differentials formany localities are found in documents referenced in 2.5, 2.6,and Footnote 13.84.1.4 The standing seam roof system clips do not alwaysprovide full lateral support to secondary structural members.The degre
23、e of lateral support provided to the secondarystructural members by the panel system shall be determined byan appropriate test, or in the absence of such test, the panelmust be assumed to provide no lateral support.NOTE 2The Base Test Method for Purlins Supporting a StandingSeam Roof System in the A
24、ISI S100 Cold-Formed Steel Design Manualis used to evaluate lateral support when the secondary structural iscold-formed Zee or Cee purlins.4.2 Protection of Incompatible MaterialsComponentsconstructed of incompatible materials shall not be placedtogether without an effective separating material.4.3
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME151419982011STANDARDSPECIFICATIONFORSTRUCTURALSTANDINGSEAMSTEELROOFPANELSYSTEMS 结构 固定 接缝 屋面 钢板 系统

链接地址:http://www.mydoc123.com/p-528847.html