ASTM E1386-2010 Standard Practice for Separation of Ignitable Liquid Residues from Fire Debris Samples by Solvent Extraction《溶剂萃取法从火场碎屑样品中分离可燃液态残留物的标准实施规程》.pdf
《ASTM E1386-2010 Standard Practice for Separation of Ignitable Liquid Residues from Fire Debris Samples by Solvent Extraction《溶剂萃取法从火场碎屑样品中分离可燃液态残留物的标准实施规程》.pdf》由会员分享,可在线阅读,更多相关《ASTM E1386-2010 Standard Practice for Separation of Ignitable Liquid Residues from Fire Debris Samples by Solvent Extraction《溶剂萃取法从火场碎屑样品中分离可燃液态残留物的标准实施规程》.pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E1386 10Standard Practice forSeparation of Ignitable Liquid Residues from Fire DebrisSamples by Solvent Extraction1This standard is issued under the fixed designation E1386; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revisi
2、on, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice covers the procedure for removing smallquantities of ignitable liquid residue from sampl
3、es of fire debrisusing solvent to extract the residue.1.2 This practice is suitable for successfully extractingignitable liquid residues over the entire range of concentra-tions.1.3 Alternate separation and concentration procedures arelisted in the referenced documents (Practices E1388, E1412,E1413,
4、 and E2154).1.4 The values stated in SI units are to be regarded asstandard. No other units of measurement are included in thisstandard.1.5 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to es
5、tablish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. For a specifichazard statement, see 5.5.2. Referenced Documents2.1 ASTM Standards:2E1388 Practice for Sampling of Headspace Vapors fromFire Debris SamplesE1412 Practice for Separ
6、ation of Ignitable Liquid Residuesfrom Fire Debris Samples by Passive Headspace Concen-tration With Activated CharcoalE1413 Practice for Separation and Concentration of Ignit-able Liquid Residues from Fire Debris Samples by Dy-namic Headspace ConcentrationE1459 Guide for Physical Evidence Labeling a
7、nd RelatedDocumentationE1492 Practice for Receiving, Documenting, Storing, andRetrieving Evidence in a Forensic Science LaboratoryE1618 Test Method for Ignitable Liquid Residues in Ex-tracts from Fire Debris Samples by Gas Chromatography-Mass SpectrometryE2154 Practice for Separation and Concentrati
8、on of Ignit-able Liquid Residues from Fire Debris Samples by PassiveHeadspace Concentration with Solid Phase Microextrac-tion (SPME)E2451 Practice for Preserving Ignitable Liquids and Ignit-able Liquid Residue Extracts from Fire Debris Samples3. Summary of Practice3.1 A sample of fire debris is extr
9、acted with an organicsolvent. The extract is filtered and concentrated using drynitrogen, filtered air, or inert gas.4. Significance and Use4.1 This practice is useful for preparing extracts from firedebris for later analysis by gas chromatography-mass spec-trometry (GC/MS).4.2 This is a very sensit
10、ive separation procedure, capable ofisolating quantities smaller than 1 L of ignitable liquid residuefrom a sample.4.3 This practice is particularly useful when the potential forfractionation during separation must be reduced, as whenattempting to distinguish between various grades of fuel oil.4.4 T
11、his practice is particularly useful for the extraction ofnonporous surfaces such as glass, or the interior of burnedcontainers. It is also particularly well suited to the extraction ofmaterials from very small samples.4.5 This practice can be hampered by coincident extractionof interfering compounds
12、 present in the fire debris samples.4.6 This practice may not be useful for the extraction ofsome extremely volatile ignitable liquids, which may evaporateduring the concentration step.4.7 This is a destructive technique. Whenever possible, thistechnique should only be used when a representative por
13、tion ofthe sample can be reserved for reanalysis. Those portions of thesample subjected to this procedure may not be suitable for1This practice is under the jurisdiction of ASTM Committee E30 on ForensicSciences and is the direct responsibility of E30.01 on CriminalisticsCurrent edition approved Feb
14、. 1, 2010 Published March 2010. Originallyapproved in 1990. Last previous edition approved in 2009 as E1386 09. DOI:10.1520/E1386-10.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume infor
15、mation, refer to the standards Document Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.resampling. If destruction of the sample is an issue, considerusing passive headspace concentration as described
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME13862010STANDARDPRACTICEFORSEPARATIONOFIGNITABLELIQUIDRESIDUESFROMFIREDEBRISSAMPLESBYSOLVENTEXTRACTION

链接地址:http://www.mydoc123.com/p-528593.html