ASTM E1321-2009 Standard Test Method for Determining Material Ignition and Flame Spread Properties《测量材料引燃和火焰蔓延性能的试验方法》.pdf
《ASTM E1321-2009 Standard Test Method for Determining Material Ignition and Flame Spread Properties《测量材料引燃和火焰蔓延性能的试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM E1321-2009 Standard Test Method for Determining Material Ignition and Flame Spread Properties《测量材料引燃和火焰蔓延性能的试验方法》.pdf(16页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E 1321 09An American National StandardStandard Test Method forDetermining Material Ignition and Flame Spread Properties1This standard is issued under the fixed designation E 1321; the number immediately following the designation indicates the year oforiginal adoption or, in the case of
2、revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This fire test response standard determines materialproperties related to piloted ignition of a
3、vertically orientedsample under a constant and uniform heat flux and to lateralflame spread on a vertical surface due to an externally appliedradiant-heat flux.1.2 The results of this test method provide a minimumsurface flux and temperature necessary for ignition ( q9o,ig, Tig)and for lateral sprea
4、d ( q9o,s, Ts,min), an effective materialthermal inertia value (krc), and a flame-heating parameter (F)pertinent to lateral flame spread.1.3 The results of this test method are potentially useful topredict the time to ignition, tig, and the velocity, V, of lateralflame spread on a vertical surface u
5、nder a specified externalflux without forced lateral airflow. Use the equations inAppendix X1 that govern the ignition and flame-spread pro-cesses and which have been used to correlate the data.1.4 This test method is potentially useful to obtain results ofignition and flame spread for materials. Da
6、ta are reported inunits for convenient use in current fire growth models.1.5 SI units are used throughout the standard.1.6 This standard is used to measure and describe theresponse of materials, products, or assemblies to heat andflame under controlled conditions, but does not by itselfincorporate a
7、ll factors required for fire hazard or fire riskassessment of the materials, products, or assemblies underactual fire conditions.1.7 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish
8、 appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. For specific hazardstatements, see Section 7.2. Referenced Documents2.1 ASTM Standards:2E84 Test Method for Surface Burning Characteristics ofBuilding MaterialsE 162 Test Method for Sur
9、face Flammability of MaterialsUsing a Radiant Heat Energy SourceE 176 Terminology of Fire StandardsE 286 Method of Test for Surface Flammability of BuildingMaterials Using an 8-ft. (2.44 m) Tunnel Furnace3E 648 Test Method for Critical Radiant Flux of Floor-Covering Systems Using a Radiant Heat Ener
10、gy SourceE 970 Test Method for Critical Radiant Flux of ExposedAttic Floor Insulation Using a Radiant Heat Energy SourceE 1317 Test Method for Flammability of Marine SurfaceFinishes2.2 ASTM Adjuncts:ASTMDetailed drawings (19), construction information, and partslist (Adjunct to E 1317)43. Terminolog
11、y3.1 DefinitionsFor definitions of terms used in this testmethod, refer to Terminology E 176.3.2 Definitions of Terms Specific to This Standard:3.2.1 backing board, na noncombustible insulating board,mounted behind the specimen during actual testing to satisfythe theoretical analysis assumption of n
12、o heat loss through thespecimen. It shall be roughly 25 6 5 mm thick with a densityno greater than 200 6 50 kg/m3.3.2.2 dummy specimen, na noncombustible insulatingboard used for stabilizing the operating condition of theequipment, roughly 20 6 5 mm in thickness with a density of750 6 100 kg/m3.3.2.
13、2.1 DiscussionThe dummy specimen is mounted inthe apparatus in the position of the test specimen and removedonly when a test specimen is to be inserted. For the ignition1This test method is under the jurisdiction of ASTM Committee E05 on FireStandards and is the direct responsibility of Subcommittee
14、 E05.22 on SurfaceBurning.Current edition approved May 1, 2009. Published September 2009. Originallyapproved in 1990. Last previous edition approved in 2008 as E 1321 08.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annu
15、al Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Withdrawn.4Available from ASTM Headquarters. Order ADJE1317.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.tests, the dumm
16、y specimen board shall have a hole at the50-mm position, for mounting the fluxmeter.3.2.3 effective thermal property, nthermal properties de-rived from heat-conduction theory applied to ignition/ flame-spread data treating the material as homogenous in structure.3.2.4 mirror assembly, na mirror, mar
17、ked and alignedwith the viewing rakes, used as an aid for quickly identifyingand tracking the flame-front progress.3.2.5 special calibration board, na specially assemblednoncombustible insulating board used for standardizing theoperating condition of the equipment which is used only tomeasure the fl
18、ux distribution at specified intervals along thespecimen surface. It shall be roughly 206 5 mm in thicknesswith a density of 750 6 100 kg/m3.3.2.6 thermally thick, nthe thickness of a medium that islarge enough to have the predominate thermal (temperature)effects experienced within that distance, th
19、at is, negligible heatis lost from its unexposed side.3.2.7 thermal operating level, nthe operating condition atwhich the radiance of the heat source produces a specifiedconstant heat flux to some specified position at the specimensurface.3.2.8 viewing rakes, na set of bars with wires spaced at50-mm
20、 intervals for the purpose of increasing the precision oftiming flame-front progress along the specimen.3.3 Symbols:Symbols:b = ignition correlation parameter, s1/2.C = flame heat transfer factor, ms/2/kWs1/2.CF = ratio of radiation pyrometer signal to flux inci-dent on dummy specimen as measured du
21、ringcalibration; a linear correlation is assumed, mV/(kW/m2).F(t) = specimen thermal response function.F(x) = surface flux configuration invariant, (kW/m2)/mV.h = heat loss coefficient, kW/m2K.q9e= measured incident flux, kW/m2.q9o,ig = critical flux for ignition, kW/m2.q9o,s = critical flux for spr
22、ead, kW/m2.t = time, s.t* = characteristic equilibrium time, s.t1= time at sample insertion, s.t2= time at ignition, s.tig= ignition time under incident flux, s.Tig= ignition temperature, C.Ts, min= minimum temperature for spread, C.T= ambient and initial temperature, C.V = flame (pyrolysis front) v
23、elocity, m/s.x = longitudinal position along centerline of speci-men, m.F = flame heating parameter, (kW)2/m3.krc = thermal heating property, (kW/m2K)2s. = surface emissivity.s = Stefan-Boltzmann constant, kW/m2K4.4. Summary of Test Method4.1 This test method consists of two procedures; one tomeasur
24、e ignition and one to measure lateral-flame spread.Vertically mounted specimens are exposed to the heat from avertical air-gas fueled radiant-heat energy source inclined at15 to the specimen (see Fig. 1).4.1.1 For the ignition test, a series of 155, + 0, 5 mm by155, + 0, 5 mm specimens (see Fig. 1)
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME13212009STANDARDTESTMETHODFORDETERMININGMATERIALIGNITIONANDFLAMESPREADPROPERTIES 测量 材料 引燃 火焰 蔓延

链接地址:http://www.mydoc123.com/p-528429.html