ASTM E1105-2000 Standard Test Method for Field Determination of Water Penetration of Installed Exterior Windows Skylights Doors and Curtain Walls by Uniform or Cyclic Static Air Pr.pdf
《ASTM E1105-2000 Standard Test Method for Field Determination of Water Penetration of Installed Exterior Windows Skylights Doors and Curtain Walls by Uniform or Cyclic Static Air Pr.pdf》由会员分享,可在线阅读,更多相关《ASTM E1105-2000 Standard Test Method for Field Determination of Water Penetration of Installed Exterior Windows Skylights Doors and Curtain Walls by Uniform or Cyclic Static Air Pr.pdf(5页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E 1105 00Standard Test Method forField Determination of Water Penetration of InstalledExterior Windows, Skylights, Doors, and Curtain Walls, byUniform or Cyclic Static Air Pressure Difference1This standard is issued under the fixed designation E 1105; the number immediately following th
2、e designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method covers
3、 the determination of the resis-tance of installed exterior windows, curtain walls, skylights,and doors to water penetration when water is applied to theoutdoor face and exposed edges simultaneously with a static airpressure at the outdoor face higher than the pressure at theindoor face.1.2 This tes
4、t method is applicable to any curtain-wall area orto windows, skylights, or doors alone. It is intended primarilyfor determining the resistance to water penetration throughsuch assemblies for compliance with specified performancecriteria, but it may also be used to determine the resistance topenetra
5、tion through the joints between the assemblies and theadjacent construction. Other procedures may be appropriate toidentify sources of leakage.1.3 This test method addresses water penetration through amanufactured assembly. Water that penetrates the assembly,but does not result in a failure as defin
6、ed herein, may haveadverse effects on the performance of contained materials suchas sealants and insulating or laminated glass. This test methoddoes not address these issues.1.4 The proper use of this test method requires a knowledgeof the principles of pressure measurement.1.5 The values stated in
7、SI units are to be regarded as thestandard. The inch-pound equivalents of SI units may beapproximate.1.6 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and hea
8、lth practices and determine the applica-bility of regulatory limitations prior to use. For specific hazardstatements, see 7.1.2. Referenced Documents2.1 ASTM Standards:E 631 Terminology of Building Constructions23. Terminology3.1 DefinitionsFor definitions of general terms relating tobuilding constr
9、uction used in this test method, see TerminologyE 631.3.2 Definitions of Terms Specific to This Standard:3.2.1 specimen, nthe entire assembled unit submitted fortest as installed in the exterior wall of a building.3.2.1.1 DiscussionThe test specimen consists of the majorcomponents of the assembly, i
10、ncluding all joints, cracks, oropenings between such components and any panning, recep-tors, extenders, sills, mullions, or other parts or componentsused for assembling any installation. The joints betweenassemblies and the openings into which they are mounted(masonry openings, for example) are not
11、part of the testspecimen. However, these joints may be tested by this proce-dure.3.2.2 test pressure difference, nthe specified difference instatic air pressure across the closed and locked or fixedspecimen expressed in pascals (lbf/ft2).3.2.3 water penetration, npenetration of water beyond aplane p
12、arallel to the glazing (the vertical plane) intersecting theinnermost projection of the test specimen, not includinginterior trim and hardware, under the specified conditions of airpressure difference across the specimen. For products withnon-planer surfaces (domes, vaults, pyramids, etc.) the plane
13、defining water penetration is the plane defined by the innermostedges of the unit frame.4. Summary of Test Method4.1 This test method consists of sealing a chamber to theinterior or exterior face of specimen to be tested, supplying airto a chamber mounted on the exterior or exhausting air from a1Thi
14、s test method is under the jurisdiction of ASTM Committee E06 onPerformance of Buildings and is the direct responsibility of Subcommittee E06.51on Component Performance of Windows, Curtain Walls, and Doors.Current edition approved Oct. 10, 2000. Published December 2000. Originallypublished as E 1105
15、 86. Last previous edition E 1105 96.2Annual Book of ASTM Standards, Vol 04.11.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.chamber mounted on the interior, at the rate required tomaintain the test pressure difference across the s
16、pecimen whilespraying water onto the outdoor face of the specimen at therequired rate and observing any water penetration.5. Significance and Use5.1 This test method is a standard procedure for determiningthe resistance to water penetration under uniform or cyclicstatic air pressure differences of i
17、nstalled exterior windows,skylights, curtain walls, and doors. The air-pressure differencesacting across a building envelope vary greatly. These factorsshould be considered fully prior to specifying the test pressuredifference to be used.NOTE 1In applying the results of tests by this test method, no
18、te thatthe performance of a wall or its components, or both, may be a functionof proper installation and adjustment. In service, the performance will alsodepend on the rigidity of supporting construction and on the resistance ofcomponents to deterioration by various causes, vibration, thermal expan-
19、sion and contraction, and so forth. It is difficult to simulate the identicalcomplex wetting conditions that can be encountered in service, with largewind-blown water drops, increasing water drop impact pressures withincreasing wind velocity, and lateral or upward moving air and water.Some designs a
20、re more sensitive than others to this upward moving water.NOTE 2This test method does not identify unobservable liquid waterwhich may penetrate into the test specimen.5.2 Laboratory tests are designed to give an indication of theperformance of an assembly. Field performance may vary fromlaboratory p
21、erformance since the supporting structure for thetest specimen, methods of mounting, and sealing in thelaboratory can only simulate the actual conditions that willexist in the building. Shipping, handling, installation, acts ofsubsequent trades, aging, and other environmental conditionsall may have
22、an adverse effect upon the performance of theinstalled product. This field test procedure provides a meansfor determining the performance of a product once installed inthe building.5.3 The field test may be made at the time the window,skylight, curtain-wall, or door assemblies are initially installe
23、dand before the interior of the building is finished. At this time,it is generally easier to check the interior surfaces of theassemblies for water penetration and to identify the points ofpenetration. The major advantage of testing when assembliesare initially installed is that errors in fabricatio
24、n or installationcan be readily discovered and corrections made before theentire wall with its component assemblies is completed atwhich time the expense of corrective work may be increasedmany times.5.4 The field test may also be made after the building iscompleted and in service to determine wheth
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME11052000STANDARDTESTMETHODFORFIELDDETERMINATIONOFWATERPENETRATIONOFINSTALLEDEXTERIORWINDOWSSKYLIGHTSDOORSANDCURTAINWALLSBYUNIFORMORCYCLICSTATICAIRPRPDF

链接地址:http://www.mydoc123.com/p-527913.html