ASTM E1008-2003 Standard Practice for Installation Inspection and Maintenance of Valve-body Pressure-relief Methods for Geothermal and Other High-Temperature Liquid Applications《地热.pdf
《ASTM E1008-2003 Standard Practice for Installation Inspection and Maintenance of Valve-body Pressure-relief Methods for Geothermal and Other High-Temperature Liquid Applications《地热.pdf》由会员分享,可在线阅读,更多相关《ASTM E1008-2003 Standard Practice for Installation Inspection and Maintenance of Valve-body Pressure-relief Methods for Geothermal and Other High-Temperature Liquid Applications《地热.pdf(2页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E 1008 03Standard Practice forInstallation, Inspection, and Maintenance of Valve-bodyPressure-relief Methods for Geothermal and Other High-Temperature Liquid Applications1This standard is issued under the fixed designation E 1008; the number immediately following the designation indicat
2、es the year oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice covers installation, inspectio
3、n, and main-tenance of valve body cavity pressure relief methods for valvesused in geothermal and other high-temperature liquid service.The valve type covered by this practice is a design with anisolated body cavity such that when the valve is in either theopen or closed position pressure is trapped
4、 in the isolatedcavity, and there is no provision to relieve the excess pressureinternally.1.2 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practi
5、ces and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 API Standard:6DSpecifications for Pipe Line Valves, End Closures,Connectors and Swivels22.2Proposed specification ISO/DIS 143133. Definitions3.1 relief devicea spring loaded valve or rupture disk t
6、hatwill relieve excessive pressure from the body cavity at apredetermined pressure.4. Installation4.1 Any valve conforming to the description in 1 of thispractice shall have a body cavity pressure relief deviceinstalled in a manner to relieve excessive pressure from thebody cavity. The relief pressu
7、re setting shall not exceed 700kPa (101.5 psi) above the rated working pressure of the valveassembly at 40 C (104 F) as defined in the latest edition ofAPI 6D.4.2 The installation shall be such that direct access to thebody cavity is maintained and that the pressure relief devicemay be periodically
8、removed, cleaned, inspected, and rein-stalled without endangering the operating personnel or remov-ing the valve from its functional application.4.2.1 The relief device may be mounted with an automaticshutoff, such as a check valve held in the open position by therelief device. An example of such an
9、 assembly is shown in Fig.1. The shutoff device will not be rendered inoperative.5. Cold-Weather Considerations5.1 Temperatures below freezing are considered due to iceformation within the body cavity and the associated expansion.5.2 The recommended procedures for winterizing (for ex-ample, for temp
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME10082003STANDARDPRACTICEFORINSTALLATIONINSPECTIONANDMAINTENANCEOFVALVEBODYPRESSURERELIEFMETHODSFORGEOTHERMALANDOTHERHIGHTEMPERATURELIQUIDAPPLICATIONS

链接地址:http://www.mydoc123.com/p-527730.html