ASTM E1003-2013(2018) 9375 Standard Practice for Hydrostatic Leak Testing.pdf
《ASTM E1003-2013(2018) 9375 Standard Practice for Hydrostatic Leak Testing.pdf》由会员分享,可在线阅读,更多相关《ASTM E1003-2013(2018) 9375 Standard Practice for Hydrostatic Leak Testing.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E1003 13 (Reapproved 2018)Standard Practice forHydrostatic Leak Testing1This standard is issued under the fixed designation E1003; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in
2、parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice covers the testing of components for leaksby pressurizing them inside with a liquid.1.2 This practice can be used on piping, valves
3、, and con-tainers with welded or fitted sections which can be sealed attheir ends and which are designed for internal pressure.1.3 Basic procedures are described based on the type ofinspection used. These procedures should be limited to findingleakage indications of 4.5 109mol/s (1 104Std cm3/s)2orl
4、arger.1.4 UnitsThe values stated in SI units are to be regardedas standard. The values given in parentheses are mathematicalconversions to inch-pound units that are provided for informa-tion only and are not considered standard.1.5 This standard does not purport to address the safetyconcerns, if any
5、, associated with its use. It is the responsibilityof the user of this standard to establish appropriate safety,health, and environmental practices and determine the appli-cability of regulatory limitations prior to use.1.6 This international standard was developed in accor-dance with internationall
6、y recognized principles on standard-ization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recom-mendations issued by the World Trade Organization TechnicalBarriers to Trade (TBT) Committee.2. Referenced Documents2.1 ASTM Standards:3E543 Specifica
7、tion for Agencies Performing NondestructiveTestingE1316 Terminology for Nondestructive Examinations2.2 ASNT Documents:4SNT-TC-1A Recommended Practice for Personal Qualifica-tion and Certification in Nondestructive TestingANSI/ASNT CP-189 ASNT Standard for Qualification andCertification of Nondestruc
8、tive Testing Personnel42.3 AIA Standard:5NAS-410 Certification and Qualification of NondestructiveTest Personnel3. Terminology3.1 DefinitionsFor definitions of terms used in thispractice, see Terminology E1316, Section E.4. Summary of Practice4.1 Hydrostatic testing requires that a component be com-
9、pletely filled with a liquid, such as water. Pressure is slowlyapplied to the liquid until the required pressure is reached. Thispressure is held for the required time at which point thecomponent is inspected visually to locate leaks or the pressureon the gauge is recorded to determine the component
10、s totalleakage.4.2 The two basic procedures are described together withmethods for improving their sensitivity.4.2.1 Pressure Drop IndicationThis procedure is usedprimarily to measure total system leakage.4.2.2 Visual Inspection for Leakage This procedure isintended primarily to locate leaks.4.3 Ult
11、rasonic pretesting for gross leaks is described.5. Basis of Application5.1 The following items are subject to contractual agree-ment between the parties using or referencing this practice:5.2 Personnel Qualification5.2.1 If specified in the contractual agreement. Personnelperforming examinations to
12、this practice shall be qualified inaccordance with a nationally or internationally recognizedNDT personnel qualification practice or standard such as1This practice is under the jurisdiction of ASTM Committee E07 on Nonde-structive Testing and is the direct responsibility of Subcommittee E07.08 on Le
13、akTesting Method.Current edition approved June 1, 2018. Published July 2018. Originally approvedin 1984. Last previous edition approved in 2013 as E1003 - 13. DOI: 10.1520/E1003-13R18.2The gas temperature is referenced to 0C. To convert to another gas referencetemperature, Tref, multiply the leak ra
14、te by (Tref+ 273) 273.3For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.4Available fromAmerican Society for Non
15、destructive Testing (ASNT), P.O. Box28518, 1711 Arlingate Ln., Columbus, OH 43228-0518, http:/www.asnt.org.5Available from Aerospace Industries Association of America, Inc. (AIA), 1000Wilson Blvd., Suite 1700,Arlington, VA22209-3928, http:/www.aia-aerospace.org.Copyright ASTM International, 100 Barr
16、 Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United StatesThis international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for theDevelopment of International Standards, Guides and Recomme
17、ndations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.1ANSI/ASNT CP-189, SNT-TC-1A, NAS-410, or similar docu-ment and certified by the employer or certifying agency, asapplicable. The practice or standard used and its applicablerevision shall be identified in th
18、e contractual agreement.5.3 Qualification of Nondestructive AgenciesIf specifiedin the contractual agreement, NDT agencies shall be qualifiedand evaluated as described in Practice E543. The applicableedition of Practice E543 shall be specified in the contractualagreement.5.4 Re-examination of Repair
19、ed/Reworked ItemsRe-examination of repaired/reworked items is not addressed in thispractice, they shall be specified in the contractual agreement.6. Significance and Use6.1 This practice is useful for quality control testing andfield inspection of piping systems, pipelines, valves, andcontainers tha
20、t are expected to retain liquids. It is not sensitiveenough for leak testing when toxic or explosive gas is expectedto be retained under pressure.7. Interferences7.1 The interior and exterior welds and joints where leaksare often found must be free of oil, grease, flux, slag, or othercontaminants th
21、at might temporarily block or mask leakage.New systems should be tested prior to painting, where practi-cal.7.2 Hydrostatic testing should not be performed before aleak test using air or a tracer gas. The liquid test media mayclog small leaks causing later tests to be inaccurate.7.3 Test liquid must
22、 be equal or above atmosphere tempera-ture or droplets will form on the outside. The minimumtemperature of the liquid should be 16C (61F).7.4 If the container to be tested has parts made of stainlesssteel, nickel, or chromium alloys, the liquid or any additivesused must have a sulfur and halogen con
23、tent of less than 50ppm of each. If water is used as a test fluid it should bedeionized.7.5 To avoid brittle fracture, the test pressure must not beapplied until the metal and the test fluid are approximately thesame temperature. The metal should be a minimum of 16C(61F) prior to the application of
24、pressure.7.6 If a test liquid other than water is used, the liquids flashpoint should be 93C (200F) or above.7.7 If plastic parts are used in the test container, the fluidshould not promote stress cracking or softening on the plastic.7.8 When the test container has carbon steel components, arust inh
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME1003201320189375STANDARDPRACTICEFORHYDROSTATICLEAKTESTINGPDF

链接地址:http://www.mydoc123.com/p-527711.html