ASTM E336-2017a red 4375 Standard Test Method for Measurement of Airborne Sound Attenuation between Rooms in Buildings《建筑物房间之间气载声衰减率测量的标准试验方法》.pdf
《ASTM E336-2017a red 4375 Standard Test Method for Measurement of Airborne Sound Attenuation between Rooms in Buildings《建筑物房间之间气载声衰减率测量的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM E336-2017a red 4375 Standard Test Method for Measurement of Airborne Sound Attenuation between Rooms in Buildings《建筑物房间之间气载声衰减率测量的标准试验方法》.pdf(20页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E336 17E336 17aStandard Test Method forMeasurement of Airborne Sound Attenuation betweenRooms in Buildings1This standard is issued under the fixed designation E336; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the y
2、ear of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the U.S. Department of Defense.INTRODUCTIONThis test method is part
3、of a set of standards for evaluating the sound-insulating properties ofbuilding elements. It is designed to measure the sound isolation between two rooms or to estimatelower limits for sound transmission through a partition element installed as an interior part of abuilding. Others in the set cover
4、the airborne sound transmission loss of an isolated partition elementin a controlled laboratory environment (Test Method E90), the laboratory measurement of impactsound transmission through floors (Test Method E492), the measurement of impact sound transmis-sion in buildings (Test Method E1007), the
5、 measurement of sound transmission through buildingfacades and facade elements (Guide E966), the measurement of sound transmission through acommon plenum between two rooms (Test Method E1414/E1414M), and measurement of thenormalized insertion loss of doors (Test Method E2964).1. Scope1.1 The sound i
6、solation between two spaces in a building is influenced most strongly by a combination of the direct transmissionthrough the nominally separating building element (as normally measured in a laboratory) and any transmission along a numberof indirect paths, usually referred to as flanking paths. Fig.
7、1 illustrates the direct paths (D) and some possible structural flankingpaths. paths (F). Additional non-structural flanking paths may include transmission through common air ducts between rooms, ordoors to the corridor from adjacent rooms. Sound isolation is also influenced by the size of the separ
8、ating partition between spacesand absorption in the receiving space, and in the case of small spaces by modal behavior of the space and close proximity tosurfaces.1.2 The main part of this test method defines procedures and metrics to assess the sound isolation between two rooms or portionsthereof i
9、n a building separated by a common partition or the apparent sound insulation of the separating partition, including bothdirect and flanking transmission paths in all cases. Appropriate measures and their single number ratings are the noise reduction(NR) and noise isolation class (NIC) which indicat
10、e the isolation with the receiving room furnished as it is during the test, thenormalized noise reduction (NNR) and normalized noise isolation class (NNIC) which indicate the expected isolation when thereceiving room is a normally furnished living or office space that is at least 25 m3 (especially u
11、seful when the test must be donewith the receiving room unfurnished), and the apparent transmission loss (ATL) and apparent sound transmission class (ASTC)which indicate the apparent sound insulating properties of a separating partition. partition including both the direct transmissionand flanking t
12、ransmission through the support structure. The measurement of ATL is limited to spaces of at least 25 m3 wheremodal effects create fewer problems. With the exception of theATL andASTC under specified conditions, these procedures in themain part of the test method are only applicable when both room v
13、olumes are less than 150 m3.NOTE 1The word “partition” in this test method includes all types of walls, floors, or any other boundaries separating two spaces. The boundariesmay be permanent, operable, or movable.1.3 The NR and NIC between two locations may always be measured and reported though cond
14、itions present will influence howmeasurements are made. Restrictions such as minimum room volume or dimensions or maximum room absorption are imposedfor all other measures and ratings in this standard. Thus, conditions may exist that will not allow NNR (NNIC), (NNIC) or ATL1 This test method is unde
15、r the jurisdiction of ASTM Committee E33 on Building and Environmental Acoustics and is the direct responsibility of Subcommittee E33.03on Sound Transmission.Current edition approved July 1, 2017Nov. 15, 2017. Published November 2017. Originally approved in 1971. Last previous edition approved in 20
16、162017 asE336 16a.E336 17. DOI: 10.1520/E0336-17.10.1520/E0336-17A.This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Becauseit may not be technically possible to adequately depict a
17、ll changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current versionof the standard as published by ASTM is to be considered the official document.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2
18、959. United States1(ASTC) or FTL (FSTC) to be reported. Where a partition between rooms is composed of parts that are constructed differently, orcontains an element such as a door, it is not possible to measure the ATL and ASTC of the individual elements or portions of thepartition. To evaluate the
19、field performance of a door less than 6 m2 in area, use Test Method E2964. The various metrics areinherently different quantities, so that NIC cannot be used instead of NNIC or ASTC when specifications are written in terms ofone of those metrics that cannot be reported with the conditions present.1.
20、4 Annex A1 provides methods to assess the sound transmission through a partition or partition element with the influence offlanking transmission reduced. These methods may be used when it must be demonstrated that a partition has achieved a specifiedminimum sound attenuation. The results are the fie
21、ld transmission loss (FTL) and field sound transmission class (FSTC).1.4 Annex A2A1 provides methods to measure the sound isolation between portions of two rooms in a building separated bya common partition including both direct and flanking paths when at least one of the rooms has a volume of 150 m
22、3 or more. Theresults are the noise reduction (NR) and noise isolation class (NIC).1.5 The values stated in SI units are to be regarded as standard. No other units of measurement are included in this standard.1.6 The text of this test method references notes and footnotes which provide explanatory m
23、aterial. These notes and footnotes(excluding those in tables and figures) shall not be considered as requirements of the standard.1.7 This standard may involve hazardous materials, operations, and equipment. This standard does not purport to address allof the safety concerns, if any, associated with
24、 its use. It is the responsibility of the user of this standard to establish appropriatesafety, health, and environmental practices and determine the applicability of regulatory limitations prior to use.1.8 This international standard was developed in accordance with internationally recognized princ
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME3362017ARED4375STANDARDTESTMETHODFORMEASUREMENTOFAIRBORNESOUNDATTENUATIONBETWEENROOMSINBUILDINGS

链接地址:http://www.mydoc123.com/p-527441.html