《ASTM E162-2015 red 6891 Standard Test Method for Surface Flammability of Materials Using a Radiant Heat Energy Source《采用辐射热能源测定材料表面易燃性的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM E162-2015 red 6891 Standard Test Method for Surface Flammability of Materials Using a Radiant Heat Energy Source《采用辐射热能源测定材料表面易燃性的标准试验方法》.pdf(12页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: E162 13E162 15 An American National StandardStandard Test Method forSurface Flammability of Materials Using a Radiant HeatEnergy Source1This standard is issued under the fixed designation E162; the number immediately following the designation indicates the year oforiginal adoption or, i
2、n the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the U.S. Department of Defense.1. Scope
3、1.1 This fire-test-response standard describes the measurement of surface flammability of materials. It is not intended for useas a basis of ratings for building code purposes (see Appendix X1).1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses
4、are mathematicalconversions to SI units that are provided for information only and are not considered standard.1.3 This standard measures and describes the response of materials, products, or assemblies to heat and flame under controlledconditions, but does not by itself incorporate all factors requ
5、ired for fire hazard or fire risk assessment of the materials, products,or assemblies under actual fire conditions.1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibilityof the user of this standard to establish appropriate
6、safety and health practices and determine the applicability of regulatorylimitations prior to use.1.5 Fire testing of products and materials is inherently hazardous, and adequate safeguards for personnel and property shall beemployed in conducting these tests. This test method may involve hazardous
7、materials, operations, and equipment. Specificinformation about hazard is given in Section .NOTE 1There is no similar or equivalent ISO standard.2. Referenced Documents2.1 ASTM Standards:2D3675 Test Method for Surface Flammability of Flexible Cellular Materials Using a Radiant Heat Energy SourceE84
8、Test Method for Surface Burning Characteristics of Building MaterialsE176 Terminology of Fire StandardsE1546 Guide for Development of Fire-Hazard-Assessment Standards2.2 ISO Standards3ISO 13943 Fire SafetyVocabulary3. Terminology3.1 DefinitionsFor definitions of terms used in this test method, refer
9、 to the terminology contained in Terminology E176 andISO 13943. In case of conflict, the definitions given in Terminology E176 shall prevail.3.2 Definitions of Terms Specific to This Standard:3.2.1 flashing, nflame fronts of 3 seconds or less in duration.3.2.1.1 DiscussionAll flame fronts, however t
10、emporary, are to be taken into account.1 This test method is under the jurisdiction of ASTM Committee E05 on Fire Standards and is the direct responsibility of Subcommittee E05.22 on Surface Burning.Current edition approved May 15, 2013June 1, 2015. Published June 2013July 2015. Originally approved
11、in 1960. Last previous edition approved in 20122013 asE162 12a.E162 13. DOI: 10.1520/E0162-13.10.1520/E0162-15.2 For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at serviceastm.org. For Annual Book of ASTM Standardsvolume information, refer to the st
12、andards Document Summary page on the ASTM website.3 Available from International Organization for Standardization (ISO), 1, ch. de la Voie-Creuse, Case postale 56, CH-1211, Geneva 20, Switzerland, http:/www.iso.ch.This document is not an ASTM standard and is intended only to provide the user of an A
13、STM standard an indication of what changes have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current versionof the standard as publishe
14、d by ASTM is to be considered the official document.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States13.2.2 radiant panel index, Is, nthe radiant panel index is the product of the flame spread factor, Fs, and the heat evolutionfactor, Q
15、.4. Summary of Test Method4.1 This test method of measuring surface flammability of materials employs a radiant heat source consisting of a 12 by 18-in.(305 by 457-mm) panel, in front of which an inclined 6 by 18-in. (152 by 457 mm) specimen of the material is placed. Theorientation of the specimen
16、is such that ignition is forced near its upper edge and the flame front progresses downward.4.2 A factor derived from the rate of progress of the flame front and another derived from the rate of heat liberated by thematerial under test are combined to provide a radiant panel index.5. Significance an
17、d Use5.1 This test method provides a laboratory test procedure for measuring and comparing the surface flammability of materialswhen exposed to a prescribed level of radiant heat energy. It is intended for use in measurements of the surface flammability ofmaterials exposed to fire. The test is condu
18、cted using small specimens that are representative, to the extent possible, of the materialor assembly being evaluated. (Example: in terms of their thickness, layering, and any potential substrate.)5.2 The rate at which flames will travel along surfaces depends upon the physical and thermal properti
19、es of the material, productor assembly under test, the specimen mounting method and orientation, the type and level of fire or heat exposure, the availabilityof air, and properties of the surrounding enclosure.45.3 In this procedure, the specimens are subjected to one or more specific sets of labora
20、tory fire test conditions. If different testconditions are substituted or the end-use conditions are changed, it is not always possible by or from this test to predict changesin the fire-test-response characteristics measured.Therefore, the results are valid only for the fire test exposure condition
21、s describedin this procedure.5.4 If the test results obtained by this test method are to be considered as part of an overall assessment of fire hazard in a buildingor structure, then the example criteria, concepts and procedures incorporated into Guide E1546 shall be taken into consideration.6. Appa
22、ratus6.1 The apparatus shall be as shown in Fig. 1 and include the following:6.1.1 Radiant Panel with Air and Gas SupplyThe radiant panel shall consist of a porous refractory material vertically mountedin a cast iron frame, exposing a radiating surface of 12 by 18 in. (305 by 457 mm) and shall be ca
23、pable of operating at temperaturesup to 1500F (815C). The panel shall be equipped (see Fig. 1) with a venturi-type aspirator for mixing gas and air atapproximately atmospheric pressure; a centrifugal blower, or equivalent, capable of providing 1200 ft3/h (9.4 L/s) air at a pressureof 2.8 in. of wate
24、r (700 Pa); an air filter to prevent dust from obstructing the panel pores; a pressure regulator and a control andshut-off valve for the gas supply.6.1.2 Specimen HolderThe specimen holder shall conform in shape and dimension to Fig. 2 and be constructed fromheat-resistant chromium steel. Observatio
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTME1622015RED6891STANDARDTESTMETHODFORSURFACEFLAMMABILITYOFMATERIALSUSINGARADIANTHEATENERGYSOURCE 采用

链接地址:http://www.mydoc123.com/p-527004.html