《ASTM D7094-2004 Standard Test Method for Flash Point by Modified Continuously Closed Cup (MCCCFP) Tester《用改良的连续闭杯试验仪测量闪点的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM D7094-2004 Standard Test Method for Flash Point by Modified Continuously Closed Cup (MCCCFP) Tester《用改良的连续闭杯试验仪测量闪点的标准试验方法》.pdf(9页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D 7094 04An American National StandardStandard Test Method forFlash Point by Modified Continuously Closed Cup(MCCCFP) Tester1This standard is issued under the fixed designation D 7094; the number immediately following the designation indicates the year oforiginal adoption or, in the cas
2、e of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method covers the determination of the flashpoint of fuels, lube oils, solvents
3、and other liquids by acontinuously closed cup tester utilizing a specimen size of 2mL, cup size of 7 mL, with a heating rate of 2.5C per minute.1.1.1 Apparatus requiring a specimen size of 1 mL, cup sizeof 4 mL, and a heating rate of 5.5C per minute must be runaccording to Test Method D 6450.1.2 Thi
4、s flash point test method is a dynamic method anddepends on definite rates of temperature increase. It is one ofthe many flash point test methods available and every flashpoint test method, including this one, is an empirical method.NOTE 1Flash point values are not a constant physical chemicalproper
5、ty of materials tested. They are a function of the apparatus design,the condition of the apparatus used, and the operational procedure carriedout. Flash point can, therefore, only be defined in terms of a standard testmethod and no general valid correlation can be guaranteed between resultsobtained
6、by different test methods or where different test apparatus isspecified.1.3 This test method utilizes a closed but unsealed cup withair injected into the test chamber.1.4 This test method is suitable for testing samples with aflash point from 35 to 225C.NOTE 2Flash point determinations below 35C and
7、 above 225C maybe performed; however, the precision has not been determined below andabove these temperatures.1.5 If the users specification requires a defined flash pointmethod other than this method, neither this method nor anyother test method should be substituted for the prescribed testmethod w
8、ithout obtaining comparative data and an agreementfrom the specifier.1.6 The values stated in SI are to be regarded as standard.Temperatures are in degrees Celsius, pressure in kilo-Pascals.1.7 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It i
9、s theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. For specificwarning statements, see 7.2, 8.5, and 10.1.2.2. Referenced Documents2.1 ASTM Standards:2D93 Test Methods for Fla
10、sh Point by Pensky-MartensClosed Cup TesterD 4057 Practice for Manual Sampling for Petroleum andPetroleum ProductsD 4177 Test Method for Automatic Sampling of Petroleumand Petroleum ProductsD 6450 Test Method for Flash Point by ContinuouslyClosed Cup (CCCFP) TesterD 6708 Practice for Statistical Ass
11、essment and Improve-ment of the Expected Agreement Between Two TestMethods that Purport to Measure the Same Property of aMaterialE 300 Practice for Sampling Industrial Chemicals2.2 ISO Standards:3ISO Guide 34 Quality Systems Guidelines for the Produc-tion of Reference MaterialsISO Guide 35 Certifica
12、tion of Reference MaterialsGeneral and Statistical Principles3. Terminology3.1 Definitions:3.1.1 flash point, nthe lowest temperature corrected to apressure of 101.3 kPa at which application of an ignition1This test method is under the jurisdiction of ASTM Committee D02 onPetroleum Products and Lubr
13、icants and is the direct responsibility of SubcommitteeD02.08 on Volatility.Current edition approved Nov. 1, 2004. Published November 2004.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume
14、 information, refer to the standards Document Summary page onthe ASTM website.3Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
15、source causes the vapors of a specimen of the sample to ignitemomentarily under specified conditions of the test.3.1.1.1 DiscussionFor the purpose of this test method, thetest specimen is deemed to have flashed when the hot flame ofthe ignited vapor causes an instantaneous pressure increase ofat lea
16、st 20 kPa inside the closed measuring chamber.43.1.2 dynamic, adjthe condition where the vapor abovethe test specimen and the test specimen are not in temperatureequilibrium at the time at which the ignition source is applied.4. Summary of Test Method4.1 The lid of the test chamber is regulated to a
17、 temperatureat least 18C below the expected flash point.A2 6 0.2 mL testspecimen of a sample is introduced into the sample cup. Bothspecimen and cup are at a temperature at least 18C below theexpected flash point; cooled if necessary. The cup is then raisedand pressed onto the lid of specified dimen
18、sions to form thecontinuously closed but unsealed test chamber with an overallvolume of 7.0 6 0.3 mL.4.2 After closing the test chamber, the temperatures of thetest specimen and the regulated lid are allowed to equilibrate towithin 1C. Then the lid is heated at a prescribed, constant rate.For the fl
19、ash tests, a high voltage arc of defined energy isdischarged inside the test chamber at regular intervals. Aftereach ignition, a variable amount of air (see Table 1)isintroduced into the test chamber to provide the necessaryoxygen for the next flash test. The pressure inside the continu-ously closed
20、 but unsealed test chamber remains at ambientbarometric pressure except for the short time during the airintroduction and at a flash point.4.3 After each arc application, the instantaneous pressureincrease above the ambient barometric pressure inside the testchamber is monitored. When the pressure i
21、ncrease exceeds 20kPa, the temperature at that point is recorded as the uncorrectedflash point, which is then corrected to barometric pressure.5. Significance and Use5.1 The flash point temperature is one measure of thetendency of the test specimen to form a flammable mixturewith air under controlle
22、d laboratory conditions. It is only oneof a number of properties which must be considered inassessing the overall flammability hazard of a material.5.2 Flash point is used in shipping and safety regulations todefine flammable and combustible materials and for classifica-tion purposes. This definitio
23、n may vary from regulation toregulation. Consult the particular regulation involved for pre-cise definitions of these classifications.5.3 This test method can be used to measure and describethe properties of materials in response to heat and an ignitionsource under controlled laboratory conditions a
24、nd shall not beused to describe or appraise the fire hazard or fire risk ofmaterials under actual fire conditions. However, results of thistest method may be used as elements of a fire risk assessment,which takes into account all of the factors which are pertinentto an assessment of the fire hazard
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD70942004STANDARDTESTMETHODFORFLASHPOINTBYMODIFIEDCONTINUOUSLYCLOSEDCUPMCCCFPTESTER 改良 连续 试验 测量 闪点

链接地址:http://www.mydoc123.com/p-524470.html