ASTM D6513-2000(2005) Standard Practice for Calculating the Superimposed Load on Wood-frame Walls for Standard Fire-Endurance Tests《计算标准耐火试验用木框架墙超强荷载的标准实施规程》.pdf
《ASTM D6513-2000(2005) Standard Practice for Calculating the Superimposed Load on Wood-frame Walls for Standard Fire-Endurance Tests《计算标准耐火试验用木框架墙超强荷载的标准实施规程》.pdf》由会员分享,可在线阅读,更多相关《ASTM D6513-2000(2005) Standard Practice for Calculating the Superimposed Load on Wood-frame Walls for Standard Fire-Endurance Tests《计算标准耐火试验用木框架墙超强荷载的标准实施规程》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D 6513 00 (Reapproved 2005)Standard Practice forCalculating the Superimposed Load on Wood-frame Wallsfor Standard Fire-Endurance Tests1This standard is issued under the fixed designation D 6513; the number immediately following the designation indicates the year oforiginal adoption or,
2、in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice covers procedures for calculating thesuperimposed axial load requi
3、red to be applied to load-bearingwood-frame walls throughout standard fire-endurance and fireand hose-stream tests.1.2 The calculations determine the maximum load allowedby design for wood-frame wall assemblies under nationallyrecognized structural design criteria.1.3 This practice is only applicabl
4、e to those wood-frameassemblies for which the nationally recognized structuraldesign criteria is the National Design Specification for WoodConstruction (NDS).21.4 The system of units to be used is that of the nationallyrecognized structural design criteria. For the NDS, the units areinch-pound.1.5 T
5、he text of this standard references notes and footnoteswhich provide explanatory material. These notes and footnotes(excluding those in tables and figures) shall not be consideredas requirements of the standard.1.6 This standard does not purport to address all of thesafety concerns, if any, associat
6、ed with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:3D9 Terminology Relating to WoodE119 Test Methods for Fire Tes
7、ts of Building Constructionand MaterialsE 176 Terminology Relating to Fire StandardsE 1529 Test Methods for Determining Effects of LargeHydrocarbon Pool Fires on Structural Members and As-semblies2.2 Other Standards:NDSNational Design Specification for Wood Construc-tion2NDS SupplementDesign Values
8、for Wood Construction23. Terminology3.1 DefinitionsDefinitions used in this practice are inaccordance with Terminology D9 and Terminology E 176,unless otherwise indicated.3.2 Definitions of Terms Specific to This Standard:3.2.1 gross area, nsection area calculated from overallactual dimensions of me
9、mber.3.2.2 net section area, nsection area calculated by deduct-ing from the gross section area the projected area of allmaterials removed by boring, grooving, dapping, notching, orother means.3.2.3 superimposed load, nThe additional external loadneeded to be applied to the assembly to result in the
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD651320002005STANDARDPRACTICEFORCALCULATINGTHESUPERIMPOSEDLOADONWOODFRAMEWALLSFORSTANDARDFIREENDURANCETESTS

链接地址:http://www.mydoc123.com/p-522731.html