《ASTM D6450-2016 6825 Standard Test Method for Flash Point by Continuously Closed Cup (CCCFP) Tester《用连续闭杯 (CCCFP) 试验机测定闪点的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM D6450-2016 6825 Standard Test Method for Flash Point by Continuously Closed Cup (CCCFP) Tester《用连续闭杯 (CCCFP) 试验机测定闪点的标准试验方法》.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D6450 16Standard Test Method forFlash Point by Continuously Closed Cup (CCCFP) Tester1This standard is issued under the fixed designation D6450; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision
2、. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope*1.1 This flash point test method is a dynamic method anddepends on definite rates of temperature increase. It is one ofthe many flash
3、point test methods available, and every flashpoint test method, including this one, is an empirical method.NOTE 1Flash point values are not a constant physical-chemicalproperty of materials tested. They are a function of the apparatus design,the condition of the apparatus used, and the operational p
4、rocedure carriedout. Flash point can therefore only be defined in terms of a standard testmethod, and no general valid correlation can be guaranteed betweenresults obtained by different test methods or with test apparatus differentfrom that specified.1.2 This test method covers the determination of
5、the flashpoint of fuel oils, lube oils, solvents, and other liquids by acontinuously closed cup tester. The measurement is made on atest specimen of 1 mL.1.3 This test method utilizes a closed but unsealed cup withair injected into the test chamber.1.4 This test method is suitable for testing sample
6、s with aflash point from 10 C to 250 C.NOTE 2Flash point determinations below 10 C and above 250 C canbe performed; however, the precision has not been determined below andabove these temperatures.1.5 If the users specification requires a defined flash pointmethod other than this test method, neithe
7、r this test method norany other method should be substituted for the prescribedmethod without obtaining comparative data and an agreementfrom the specifier.1.6 The values stated in SI units are to be regarded asstandard. No other units of measurement are included in thisstandard. Temperatures are in
8、 degrees Celsius, and pressure isin kilo-pascals.1.7 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of re
9、gulatory limitations prior to use. Specific warningstatements appear throughout the standard.2. Referenced Documents2.1 ASTM Standards:2D4057 Practice for Manual Sampling of Petroleum andPetroleum ProductsD4177 Practice for Automatic Sampling of Petroleum andPetroleum ProductsD6299 Practice for Appl
10、ying Statistical Quality Assuranceand Control Charting Techniques to Evaluate AnalyticalMeasurement System PerformanceD6300 Practice for Determination of Precision and BiasData for Use in Test Methods for Petroleum Products andLubricantsE300 Practice for Sampling Industrial Chemicals2.2 ISO Standard
11、s:3ISO Guide 34 Quality Systems Guidelines for the Produc-tion of Reference MaterialsISO Guide 35 Certifications of Reference Material Generaland Statistical Principles3. Terminology3.1 Definitions:3.1.1 dynamic, adjthe condition in which the vapor abovethe test specimen and the test specimen are no
12、t in temperatureequilibrium at the time at which the ignition source is applied.3.1.2 flash point, nin flash point test methods, the lowesttemperature of the test specimen, adjusted to account forvariations in atmospheric pressure from 101.3 kPa, at whichapplication of an ignition source causes the
13、vapors of the testspecimen to ignite momentarily under specified conditions ofthe test.3.1.2.1 DiscussionFor the purpose of this test method, thetest specimen is deemed to have flashed when the hot flame ofthe ignited vapor causes an instantaneous pressure increase ofat least 20 kPa inside the close
14、d measuring chamber.1This test method is under the jurisdiction of ASTM Committee D02 onPetroleum Products, Liquid Fuels, and Lubricants and is the direct responsibility ofSubcommittee D02.08 on Volatility.Current edition approved June 1, 2016. Published July 2016. Originally approvedin 1999. Last p
15、revious edition approved in 2012 as D6450 121. DOI: 10.1520/D6450-16.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM
16、website.3Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036, http:/www.ansi.org.*A Summary of Changes section appears at the end of this standardCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959.
17、United States14. Summary of Test Method4.1 The lid of the test chamber is regulated to a temperatureat least 18 C below the expected flash point.A1 mL 6 0.1 mLtest specimen of a sample is introduced into the sample cup,ensuring that both specimen and cup are at a temperature atleast 18 C below the e
18、xpected flash point, cooling if neces-sary. The cup is then raised and pressed onto the lid of specifieddimensions to form the continuously closed but unsealed testchamber with an overall volume of 4.0 mL 6 0.2 mL.4.2 After closing the test chamber, the temperatures of thetest specimen and the regul
19、ated lid are allowed to equilibrate towithin 1 C. Then the lid is heated at a prescribed, constantrate. For the flash tests, an arc of defined energy is dischargedinside the test chamber at regular intervals. After each ignition,1.5 mL 6 0.5 mL of air is introduced into the test chamber toprovide th
20、e necessary oxygen for the next flash test. Thepressure inside the continuously closed but unsealed testchamber remains at ambient barometric pressure, except forthe short time during the air introduction and except at a flashpoint.4.3 After each arc, the instantaneous pressure increaseabove the amb
21、ient barometric pressure inside the test chamberis monitored. When the pressure increase exceeds a definedthreshold, the temperature at that point is recorded as theuncorrected flash point.5. Significance and Use5.1 The flash point temperature is one measure of thetendency of the test specimen to fo
22、rm a flammable mixturewith air under controlled laboratory conditions. It is only oneof a number of properties that must be considered in assessingthe overall flammability hazard of a material.5.2 Flash point is used in shipping and safety regulations todefine flammable and combustible materials and
23、 classify them.This definition may vary from regulation to regulation. Consultthe particular regulation involved for precise definitions ofthese classifications.5.3 This test method can be used to measure and describethe properties of materials in response to heat and an ignitionsource under control
24、led laboratory conditions and shall not beused to describe or appraise the fire hazard or fire risk ofmaterials under actual fire conditions. However, results of thistest method may be used as elements of a fire risk assessment,which takes into account all of the factors that are pertinent toan asse
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD645020166825STANDARDTESTMETHODFORFLASHPOINTBYCONTINUOUSLYCLOSEDCUPCCCFPTESTER 连续 CCCFP 试验 测定 闪点

链接地址:http://www.mydoc123.com/p-522546.html