ASTM D5898 D5898M-1996(2005)e1 red 2350 Standard Guide for Standard Details for Adhered Sheet Waterproofing.pdf
《ASTM D5898 D5898M-1996(2005)e1 red 2350 Standard Guide for Standard Details for Adhered Sheet Waterproofing.pdf》由会员分享,可在线阅读,更多相关《ASTM D5898 D5898M-1996(2005)e1 red 2350 Standard Guide for Standard Details for Adhered Sheet Waterproofing.pdf(15页珍藏版)》请在麦多课文档分享上搜索。
1、Designation:D589896 (Reapproved 2005) Designation: D5898/D5898M 96(Reapproved 2005)1Standard Guide forStandard Details for Adhered Sheet Waterproofing1This standard is issued under the fixed designation D5898/D5898M; the number immediately following the designation indicates theyear of original adop
2、tion or, in the case of revision, the year of last revision. A number in parentheses indicates the year of lastreapproval. A superscript epsilon () indicates an editorial change since the last revision or reapproval.1NOTECaptions in Fig. 1 and units information were editorially updated in March 2012
3、.1. Scope1.1 This guide covers details for typical conditions encountered in adhered sheet waterproofing on below grade structures andplazas.1.2 This guide does not cover liquid applied waterproofing.1.3The values stated in SI units are to be regarded as the standard. The values given in parentheses
4、 are for information only.1.3 The values stated in either SI units or inch-pound units are to be regarded separately as standard. The values stated in eachsystem may not be exact equivalents; therefore, each system shall be used independently of the other. Combining values from thetwo systems may re
5、sult in non-conformance with the standard.2. Referenced Documents2.1 ASTM Standards:2D1079 Terminology Relating to Roofing and Waterproofing3. Terminology3.1 DefinitionsFor definitions of terms used in this guide, refer to Terminology D1079.3.2 Definitions of Terms Specific to This Standard:3.2.1 ad
6、hered sheet waterproofing, na system consisting of one or more plies of organic or glass fiber felts or fabrics appliedin hot or cold bitumens or modified bitumens, or one or more plies of a manufactured sheet of modified bitumen that may bereinforced or laminated with scrim or polyethylene, or a po
7、lymeric or vulcanized elastomeric membrane. The system is applieddirectly to concrete or masonry surfaces below grade.3.2.2 elevated slab, na framed or suspended concrete slab over a habitable or useable space.3.2.3 fillet, nliquid applied modified bitumen or mastic used at internal corners before m
8、embrane application to form atransition of less than 90.3.2.4 reinforcement, ngenerally, one or more strips of membrane, felts, or fabrics, installed at corners and over constructionjoints.3.3 Abbreviations:3.3.1 LAMliquid applied membrane.3.3.2 SSstainless steel.3.3.3 EJexpansion joint.3.3.4 NRnot
9、recommended.3.3.5 MTLnoncorrosive metal.4. Significance and Use4.1 This guide illustrates general details for below grade and plaza waterproofing. It serves as a guide that will enable thedesigner to prepare complete waterproofing details for each specific condition that occurs on a project.1This gu
10、ide is under the jurisdiction of ASTM Committee D08 on Roofing and Waterproofing and is the direct responsibility of Subcommittee D08.22 on Waterproofingand Dampproofing Systems.Current edition approved July 1, 2005. Published July 2005. Originally approved in 1996. Last previous edition approved in
11、 1996 as D5898 96. DOI:10.1520/D5898_D5898M-96R05E01.2For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at serviceastm.org. For Annual Book of ASTM Standardsvolume information, refer to the standards Document Summary page on the ASTM website.1This
12、document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions
13、 as appropriate. In all cases only the current versionof the standard as published by ASTM is to be considered the official document.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.5. Drawings5.1 This guide is not all inclusive. The d
14、esigner should detail all typical and special conditions on the project, paying particularattention to transitions in plane and intersection of different details. The applicator should provide shop drawings of each conditionto confirm field conditions and to verify his understanding of the design in
15、tent.5.2 Waterproofing membranes and reinforcement are indicated on the figures as a single thick line, regardless of the number ofplies.5.3 Protection layers have been omitted for clarity. See Section 6.6. Protection6.1 Protection materials are required over all waterproofing to prevent damage from
16、 backfill, reinforcing chairs, andconstruction traffic, unless the membrane system incorporates an integral protection layer. Protection also is required wheremembranes terminate above grade and may be exposed to ultraviolet light.6.2 Materials for protection include: asphalt composition boards, pla
17、stic drainage panels, low density expanded polystyreneboards, and extruded polystyrene insulation. Low density expanded polystyrene boards and some types of plastic drainage panelsare not suitable for protection on horizontal surfaces. Protection materials are loose-laid on horizontal membranes and
18、attached tovertical membranes with compatible adhesives. They should be installed as soon as possible after the membrane, or each portionof it, is completed or water tested.7. Reinforcement7.1 Reinforcement is required for built-up and modified bitumen membranes at transitions, such as internal and
19、external cornersand at static concrete construction joints and cracks. Reinforcement also is required where reinforcing bars, pipes, and conduitspenetrate the membrane. Separate reinforcement generally is not required for polymeric and vulcanized elastomeric membranes.7.2 Reinforcement usually is in
20、stalled before the membrane but may be applied over it. Refer to the membrane manufacturerfor details.7.3 The minimum reinforcement is one ply. Systems using a multiple ply membrane usually require two or more reinforcementplies, whereas single ply modified bitumen systems generally require one.7.4
21、When additional plies are used as reinforcement, they should extend at least 150 mm (6 in.)6 in. beyond the corner orpenetration and each succeeding ply should extend 75 mm (3 in.)3 in. beyond the previous ply.7.5 Where reinforcing bars penetrate waterproofing, such as at rock anchors and wall to sl
22、ab transitions, they should be sealedwith reinforcing plies finger cut around the bars or liquid applied membrane or both.7.6 Some manufacturers require cementitious cants or a liquid applied waterproofing or mastic fillet at reentrant angles,chamfered external corners, and other special conditions
23、to be implemented during construction. These should be indicated onproject details.7.7 Details should recognize the normal sequencing of construction. Foundation walls may be cast before or after slabs on grade.Structural slabs are cast after walls. Waterproofing of individual elements frequently fo
24、llows this sequence, for example, walls arewaterproofed before the structural slab is cast. The resultant cold joints may be dynamic.8. Penetrations8.1 Flashing at penetrations should accommodate differential movement between the slab and the pipe, conduit, or drain. Forbuilt-up and modified bitumen
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD5898D5898M19962005E1RED2350STANDARDGUIDEFORSTANDARDDETAILSFORADHEREDSHEETWATERPROOFINGPDF

链接地址:http://www.mydoc123.com/p-520994.html