ASTM D5837-1999(2005) Standard Test Method for Furanic Compounds in Electrical Insulating Liquids by High- Performance Liquid Chromatography (HPLC)《用高效液相色谱法(HPLC)测试电绝缘液中呋喃化合物的标准试验方.pdf
《ASTM D5837-1999(2005) Standard Test Method for Furanic Compounds in Electrical Insulating Liquids by High- Performance Liquid Chromatography (HPLC)《用高效液相色谱法(HPLC)测试电绝缘液中呋喃化合物的标准试验方.pdf》由会员分享,可在线阅读,更多相关《ASTM D5837-1999(2005) Standard Test Method for Furanic Compounds in Electrical Insulating Liquids by High- Performance Liquid Chromatography (HPLC)《用高效液相色谱法(HPLC)测试电绝缘液中呋喃化合物的标准试验方.pdf(8页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D 5837 99 (Reapproved 2005)Standard Test Method forFuranic Compounds in Electrical Insulating Liquids by High-Performance Liquid Chromatography (HPLC)1This standard is issued under the fixed designation D 5837; the number immediately following the designation indicates the year oforigin
2、al adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method covers the determination in electricalinsulatin
3、g liquids of products of the degradation of cellulosicmaterials such as paper, pressboard, and cotton materialstypically found as insulating materials in electrical equipment.These degradation products are substituted furan derivatives,commonly referred to as furanic compounds or furans. Thistest me
4、thod allows either liquid/liquid or solid phase extraction(SPE) of the furanic compounds from the sample matrixfollowed by analysis for specific furanic compounds by HPLCor direct injection for analysis of specific furanic compoundsby HPLC.1.2 The individual furanic compounds that may be identi-fied
5、 and quantified include the following:5-hydroxymethyl-2-furaldehydefurfuryl alcohol2-furaldehyde2-acetylfuran5-methyl-2-furaldehyde1.3 The direct injection method generally has a higher limitof detection, especially for furfuryl alcohol. Greater interfer-ence for furfuryl alcohol may be expected whe
6、n using thedirect injection method as opposed to extraction methods.1.4 This test method has been used to successfully test forfuranic compounds in mineral insulating oil, silicone fluid,high fire point electrical insulating oils of mineral origin,askarels, and perchloroethylene-based dielectric flu
7、ids.1.5 The values stated in SI units are to be regarded asstandard. No other units of measurement are included in thisstandard.1.6 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish
8、appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2D 923 Practices for Sampling Electrical Insulating LiquidsD 3487 Specification for Mineral Insulating Oil Used inElectrical ApparatusD 3612 Test
9、 Method for Analysis of Gases Dissolved inElectrical Insulating Oil by Gas ChromatographyD 3613 Practice for Sampling Insulating Liquids for GasAnalysis and Determination of Water Content2.2 International Electrotechnical Commission (IEC) Stan-dard:Method 1198 Furanic Compounds Analysis in Mineral O
10、ilInsulating Oil33. Terminology3.1 Definitions of Terms Specific to This Standard:3.1.1 adsorbent, nthe stationary phase in solid-phaseextraction; silica is used as the adsorbent in this test method.3.1.2 extract, nthe liquid phase of a liquid/liquid extrac-tion containing the compound that has been
11、 extracted and thatwill be analyzed.3.1.3 liquid/liquid extraction, nthe preparative step ofextraction by mixing nonpolar test specimen with polar solventto preferentially partition and concentrate polar compounds ofinterest from an insulating liquid test specimen.3.1.4 mobile phase, nthe carrier li
12、quid phase in an HPLCanalytical system used to transfer the prepared test specimen toand through the analytical column and detector; the composi-tion of the mobile phase affects elution time and separation ofanalytes.3.1.5 solid phase extraction (SPE), na preparative stepbased on column chromatograp
13、hy, where intermolecular inter-actions between adsorbent, solvent, and test specimen compo-nents are optimized to effect retention of analytes on a1This test method is under the jurisdiction of ASTM Committee D27 onElectrical Insulating Liquids and Gases and is the direct responsibility of Subcom-mi
14、ttee D27.03 on Analytical Tests.Current edition approved Oct. 1, 2005. Published November 2005. Originallyapproved in 1995. Last previous edition approved in 1999 as D 5837 99e1.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org.
15、For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from IEC, IEC Central Office, 3 rue de Varembe, P.O. Box 131,CH-1211, Geneva 20, Switzerland.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshoh
16、ocken, PA 19428-2959, United States.solid-phase extraction cartridge, followed by solvent elutionfrom the extraction cartridge.3.1.6 ultraviolet (UV), adjreferring to that region of theelectromagnetic spectrum including wavelengths from 10 to380 nm. The UV detectors of most HPLC systems operate inth
17、e range of wavelengths from 190 to 380 nm.4. Summary of Test Method4.1 Furanic compounds in electrical insulating liquids areextracted from a known volume of test specimen by means ofa liquid/liquid extraction or solid-phase extraction. A directinjection of the oil also may be used.4.2 A portion of
18、the extract or an aliquot of the oil isintroduced into an HPLC system equipped with a suitableanalytical column and UV detector.4.3 Furanic compounds in the test specimen are identifiedand quantified by comparison to standards of known concen-tration.5. Significance and Use5.1 Furanic compounds are
19、generated by the degradation ofcellulosic materials used in the solid insulation systems ofelectrical equipment.5.2 Furanic compounds which are oil soluble to an appre-ciable degree will migrate into the insulating liquid.5.3 High concentrations or unusual increases in the concen-trations of furanic
20、 compounds in oil may indicate cellulosedegradation from aging or incipient fault conditions. Testingfor furanic compounds may be used to complement dissolvedgas in oil analysis as performed in accordance with TestMethod D 3612.6. Interferences6.1 Materials used in the manufacture of the polypropyle
21、netubes and polyethylene frits of some commercially preparedsolid-phase extraction columns may interfere with the deter-mination of furanic compounds, such as furfuryl alcohol and5-hydroxymethyl-2-furaldehyde.6.2 The use of acetone in any preparative or analytical stepwill cause accelerated sample d
22、ecay and may interfere with theaccurate determination of 5-hydroxymethyl-2- furaldehyde.6.3 The use of cellulosic filtering media may serve to adsorbfuranic compounds yielding erroneous or unreproducible re-sults, or both.7. Apparatus7.1 High-Performance Liquid Chromatograph (HPLC)The required analy
23、tical apparatus, an HPLC, consists of aninjection device with sample loop, pumping system capable ofmixing at least two solvents, reversed phase analytical column,UV detector or detectors with the ability to operate at aminimum of two wavelengths, and a data recording device orintegrator.7.2 It is r
24、ecommended that a precolumn packed with thesame material as the analytical column be used to increasecolumn life and remove interferences.7.3 Helium sparging of the mobile-phase solvents is recom-mended in some cases and with some types of HPLC equip-ment to displace atmospheric gases dissolved in t
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
5000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD583719992005STANDARDTESTMETHODFORFURANICCOMPOUNDSINELECTRICALINSULATINGLIQUIDSBYHIGHPERFORMANCELIQUIDCHROMATOGRAPHYHPLC

链接地址:http://www.mydoc123.com/p-520829.html