ASTM D3941-1990(2007) Standard Test Method for Flash Point by the Equilibrium Method With a Closed-Cup Apparatus《平衡闭杯法测定闪点的试验方法》.pdf
《ASTM D3941-1990(2007) Standard Test Method for Flash Point by the Equilibrium Method With a Closed-Cup Apparatus《平衡闭杯法测定闪点的试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM D3941-1990(2007) Standard Test Method for Flash Point by the Equilibrium Method With a Closed-Cup Apparatus《平衡闭杯法测定闪点的试验方法》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D 3941 90 (Reapproved 2007)Standard Test Method forFlash Point by the Equilibrium Method With a Closed-CupApparatus1This standard is issued under the fixed designation D 3941; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revi
2、sion, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.INTRODUCTIONTest Methods D56an
3、d D93describe procedures using the Tag Closed Tester and the Pensky-Martens Tester, respectively. Both test methods depend on a definite rate of temperature increase tocontrol the precision of the test method. The rate of heating may not in all cases give the accuracyexpected because of low thermal
4、conductivity of certain materials. To reduce this effect, ISO/TC 35,Paints and Varnishes, and ISO/TC 28, Petroleum Products and Lubricants, have issued ISO 1523 inwhich the heating rate is considerably slower. This test method is similar to ISO 1523, but usesstandard ASTM cups, style, and format. Du
5、e to the slower heating rate, the time required to make adetermination of a flash point is considerably longer than for Test Methods D56and D93but theaccuracy is improved.1. Scope1.1 This test method covers the determination of the flashpoint of liquids in which the specimen and the air/vapormixture
6、 above it are approximately in temperature equilibrium.1.2 This test method is limited to a temperature range from0 to 110C (32 to 230F).1.3 The values stated in SI units are to be regarded as thestandard. The values given in parentheses are for informationonly.1.4 This standard should be used to me
7、asure and describethe properties of material, products, or assemblies in responseto heat and flame under controlled laboratory conditions andshould not be used to describe or appraise the fire hazard orfire risk of materials, products or assemblies under actual fireconditions. However, results of th
8、is test may be used aselements of a fire risk assessment which takes into account allof the factors which are pertinent to an assessment of the firehazard of a particular end use.1.5 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is therespon
9、sibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2D56 Test Method for Flash Point by Tag Closed Cup TesterD93 Test Methods for Flash Point by P
10、ensky-MartensClosed Cup TesterE1 Specification for ASTM Liquid-in-Glass Thermometers2.2 ISO Standard:ISO 1523 Paints, varnishes, petroleum, and relatedproductsDetermination of flash pointClosed cupequilibrium method33. Terminology3.1 Definitions:3.1.1 flash point, nthe lowest temperature corrected t
11、o apressure of 760 mm Hg (101.3 kPa) (1013 millibars) at whichapplication of an ignition source causes the vapor of thespecimen to ignite under specified conditions of test.4. Summary of Test Method4.1 A specimen is heated in a closed cup of standard designin a suitable liquid bath at the rate of 0.
12、5C (1.0F) in not lessthan 1.5 min so that the difference in temperature between the1This test method is under the jurisdiction of ASTM Committee D01 on Paintand Related Coatings, Materials, and Applications and is the direct responsibility ofSubcommittee D01.22 on Flammability and Safety.Current edi
13、tion approved June 1, 2007. Published June 2007. Originallyapproved in 1980. Last previous edition approved in 2001 as D 3941 90 (2001).2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume in
14、formation, refer to the standards Document Summary page onthe ASTM website.3Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036, http:/www.ansi.org.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-295
15、9, United States.specimen in the cup and bath never exceeds 2.0C (3.5F).Flash determinations are made at intervals of not less than 1.5min.5. Significance and Use5.1 This test method, using a slow rate of heating, providesa uniform temperature throughout the specimen. The slow rateof heating is nece
16、ssary because of the low thermal conductivityof some liquids such as paints, resins, and related products, andalso because of the poor heat transfer by convection inhigh-viscosity products. Since the specimen is being heated ata reduced rate, the longer time interval between each determi-nation is n
17、ecessary to reestablish after each flash test thesaturation concentration of vapor in the air space above thespecimen.NOTE 1ISO 1523 is used in United Nations Recommendations forTransportation of Dangerous Goods and in the International CivilAviationOrganization (ICAO) regulations and for similar re
18、gulations in theInternational Maritime Dangerous Goods (IMDG) code. Test MethodD 3941, which is similar to ISO 1523, is used in the United StatesDepartment of Transportation (USDOT) regulations. The ICAO andIMDG codes are used for transshipment of hazardous materials throughthe United States to othe
19、r countries.6. Apparatus6.1 Test Cups, equipped with their lid as specified in TestMethods D56(Tag) and D 93 (Pensky-Martens). Remove thetest cup assembly (including lid and specimen thermometer)from the Tag and Pensky-Martens apparatus to permit either tobe used in a separate water bath.6.1.1 If a
20、stirrer is fitted to the test cup used, it shall operateduring the heating period but must be stopped during theflashing determination. If the stirrer originally fitted to the testcup is removed, the aperture in the cover shall be securelyplugged before starting the test.6.2 Liquid BathAny suitable
21、liquid bath capable of beingadjusted to the required temperature and of adequate heatcapacity to meet the requirements of the test. A bath fitted witha stirrer and an adjustable thermostat is convenient (see 4.1).NOTE 2The bath should be fitted with a cover, especially when thespecified temperature
22、is above 160F. At about this temperature theinerting effect of the water vapor may prevent or delay the flashing of theliquid under test.6.3 ThermometersStandard thermometers as specified inTest Methods D56and D93. One thermometer shall be usedto measure the temperature of the water bath and one sha
23、ll beused for measuring the temperature of the specimen in the cup.NOTE 3The thermometers for the water bath should be mounted at thecorrect level of immersion for which they are specified in SpecificationE1.6.4 Support, for holding the test cup in the liquid bath sothat the cover and upper edge are
24、 horizontal and the cup isimmersed in direct contact with the liquid in such a positionthat the level of the specimen in the cup is the same as that ofthe liquid in the bath.6.5 ShieldA three sided shield, open in front, each side460 mm (18 in. ) wide and 610 mm (24 in.) high, isrecommended.7. Reage
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD394119902007STANDARDTESTMETHODFORFLASHPOINTBYTHEEQUILIBRIUMMETHODWITHACLOSEDCUPAPPARATUS 平衡 闭杯法

链接地址:http://www.mydoc123.com/p-515862.html