ASTM D3828-2016 Standard Test Methods for Flash Point by Small Scale Closed Cup Tester《用小型闭杯试验机测定闪点的标准试验方法》.pdf
《ASTM D3828-2016 Standard Test Methods for Flash Point by Small Scale Closed Cup Tester《用小型闭杯试验机测定闪点的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM D3828-2016 Standard Test Methods for Flash Point by Small Scale Closed Cup Tester《用小型闭杯试验机测定闪点的标准试验方法》.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D3828 16Standard Test Methods forFlash Point by Small Scale Closed Cup Tester1This standard is issued under the fixed designation D3828; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A numb
2、er in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the U.S. Department of Defense.INTRODUCTIONThese small scale flash point methods are generally u
3、sed for testing a sample at a specifictemperature where the specimen being tested and the airvapor mixture above it are close to thermalequilibrium. Test Method D3941 covers other flash point equipment operated at a specific temperature.Flash point values are a function of the apparatus design, the
4、condition of the apparatus used, andthe operational procedure carried out. Flash point can therefore only be defined in terms of a standardtest method, and no general valid correlation can be guaranteed between results obtained by differenttest methods, or with test apparatus different from that spe
5、cified.1. Scope*1.1 These test methods cover procedures for flash pointtests, within the range of 30 C to 300 C, of petroleumproducts and biodiesel liquid fuels, using a small scale closedcup tester. The procedures may be used to determine, whethera product will or will not flash at a specified temp
6、erature(flash/no flash Method A) or the flash point of a sample(Method B). When used in conjunction with an electronicthermal flash detector, these test methods are also suitable forflash point tests on biodiesels such as fatty acid methyl esters(FAME).1.2 The values stated in SI units are to be reg
7、arded as thestandard. The values given in parentheses are for informationonly.1.3 This standard should be used to measure and describethe properties of materials, products, or assemblies in responseto heat and flame under controlled laboratory conditions andshould not be used to describe or appraise
8、 the fire hazard orfire risk of materials, products, or assemblies under actual fireconditions. However, results of this test may be used aselements of a fire risk assessment which takes into account allof the factors which are pertinent to an assessment of the firehazard of a particular end use.1.4
9、 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. Warning statement
10、sappear throughout. See also the Material Safety Data Sheets forthe product being tested.2. Referenced Documents2.1 ASTM Standards:2D3941 Test Method for Flash Point by the EquilibriumMethod With a Closed-Cup ApparatusD4057 Practice for Manual Sampling of Petroleum andPetroleum ProductsD4177 Practic
11、e for Automatic Sampling of Petroleum andPetroleum ProductsD6299 Practice for Applying Statistical Quality Assuranceand Control Charting Techniques to Evaluate AnalyticalMeasurement System PerformanceD6708 Practice for Statistical Assessment and Improvementof Expected Agreement Between Two Test Meth
12、ods thatPurport to Measure the Same Property of a MaterialE300 Practice for Sampling Industrial ChemicalsE1137/E1137M Specification for Industrial Platinum Resis-tance Thermometers2.2 ISO Standards:3Guide 34 Quality Systems Guidelines for the Production ofReference Materials1These test methods are u
13、nder the jurisdiction of ASTM Committee D02 onPetroleum Products, Liquid Fuels, and Lubricants and is the direct responsibility ofSubcommittee D02.08 on Volatility.Current edition approved June 1, 2016. Published July 2016. Originally approvedin 1979. Last previous edition approved in 2012 as D3828
14、12a. DOI: 10.1520/D3828-16.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from American National
15、Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036, http:/www.ansi.org.*A Summary of Changes section appears at the end of this standardCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States1Guide 35 Certification of Re
16、ference MaterialsGeneral andStatistical PrinciplesEN ISO 3679 Determination of Flash PointRapid Equilib-rium Closed Cup MethodEN ISO 3680 Determination of Flash/No FlashRapidEquilibrium Closed Cup MethodISO 60751 Industrial Platinum Resistance Thermometersand Platinum Temperature Sensors2.3 Energy I
17、nstitute Standards:4IP 523 Determination of Flash PointRapid EquilibriumClosed Cup MethodIP 524 Determination of Flash/No FlashRapid Equilib-rium Closed Cup Method3. Terminology3.1 Definitions:3.1.1 equilibrium, nin flash point test methods, the condi-tion where the vapor above the test specimen, an
18、d the testspecimen are at the same temperature at the time the ignitionsource is applied.3.1.1.1 DiscussionThis condition may not be fullyachieved in practice, since the temperature may not be uniformthroughout the test specimen, and the test cover and shutter onthe apparatus can be cooler or warmer
19、.3.1.2 flash point, nin flash point test methods, the lowesttemperature of the test specimen, adjusted to account forvariations in atmospheric pressure from 101.3 kPa, at whichapplication of an ignition source causes the vapors of the testspecimen to ignite under specified conditions of test.4. Summ
20、ary of Test Methods4.1 Method AFlash/No Flash TestA test specimen isintroduced, by a syringe, into the test cup of the selectedapparatus that is set and maintained at the specified tempera-ture. After a specific time an ignition source is applied and adetermination made as to whether or not a flash
21、occurred.4.2 Method BFinite (or Actual) Flash PointThismethod essentially repeats MethodAa number of times, and bychanging the test temperature and test specimen a number oftimes, determines the flash point.4.2.1 A test specimen is introduced into the test cup of theselected apparatus that is mainta
22、ined at the expected flashpoint. After a specified time an ignition source is applied and adetermination made whether or not a flash occurred.4.2.2 The test specimen is removed from the test cup; thetest cup and cover are cleaned, and the test temperatureadjusted 5 C (9 F) lower or higher depending
23、on whether ornot a flash occurred previously. A fresh test specimen isintroduced and tested. This procedure is repeated until the flashpoint is established within 5 C (9 F).4.2.3 The procedure is then repeated at 1 C (2 F) intervalsuntil the flash point is determined to the nearest 1 C (2 F).4.2.4 I
24、f improved accuracy is desired the procedure isrepeated at 0.5 C (1 F) intervals until the flash point isdetermined to the nearest 0.5 C (1 F).4.3 Test Time and Specimen Volume:4.3.1 For all products, except biodiesel; for test tempera-tures up to and including 100 C (212 F), the test time is1 min a
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD38282016STANDARDTESTMETHODSFORFLASHPOINTBYSMALLSCALECLOSEDCUPTESTER 小型 试验 测定 闪点 标准 方法 PDF

链接地址:http://www.mydoc123.com/p-515577.html