ASTM D3828-2012 Standard Test Methods for Flash Point by Small Scale Closed Cup Tester《小刻度闭杯试验器测定液体闪点的标准试验方法》.pdf
《ASTM D3828-2012 Standard Test Methods for Flash Point by Small Scale Closed Cup Tester《小刻度闭杯试验器测定液体闪点的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM D3828-2012 Standard Test Methods for Flash Point by Small Scale Closed Cup Tester《小刻度闭杯试验器测定液体闪点的标准试验方法》.pdf(10页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D3828 12Standard Test Methods forFlash Point by Small Scale Closed Cup Tester1This standard is issued under the fixed designation D3828; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A numb
2、er in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.INTRODUCTIONThese small scale flash point methods are generally used f
3、or testing a sample at a specifictemperature where the specimen being tested and the airvapor mixture above it are close to thermalequilibrium. Test Method D3941 covers other flash point equipment operated at a specific temperature.Flash point values are a function of the apparatus design, the condi
4、tion of the apparatus used, andthe operational procedure carried out. Flash point can therefore only be defined in terms of a standardtest method, and no general valid correlation can be guaranteed between results obtained by differenttest methods, or with test apparatus different from that specifie
5、d.1. Scope*1.1 These test methods cover procedures for flash pointtests, within the range of 30 to 300C, of petroleum productsand biodiesel liquid fuels, using a small scale closed cup tester.The procedures may be used to determine, whether a productwill or will not flash at a specified temperature
6、(flash/no flashMethod A) or the flash point of a sample (Method B). Whenused in conjunction with an electronic thermal flash detector,these test methods are also suitable for flash point tests onbiodiesels such as fatty acid methyl esters (FAME).1.2 The values stated in SI units are to be regarded a
7、s thestandard. The values given in parentheses are for informationonly.1.3 This standard should be used to measure and describethe properties of materials, products, or assemblies in responseto heat and flame under controlled laboratory conditions andshould not be used to describe or appraise the fi
8、re hazard orfire risk of materials, products, or assemblies under actual fireconditions. However, results of this test may be used aselements of a fire risk assessment which takes into account allof the factors which are pertinent to an assessment of the firehazard of a particular end use.1.4 This s
9、tandard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. Warning statementsappear
10、 throughout. See also the Material Safety Data Sheets forthe product being tested.2. Referenced Documents2.1 ASTM Standards:2D3941 Test Method for Flash Point by the EquilibriumMethod With a Closed-Cup ApparatusD4057 Practice for Manual Sampling of Petroleum andPetroleum ProductsD4177 Practice for A
11、utomatic Sampling of Petroleum andPetroleum ProductsD6299 Practice for Applying Statistical Quality Assuranceand Control Charting Techniques to Evaluate AnalyticalMeasurement System PerformanceE300 Practice for Sampling Industrial ChemicalsE1137/E1137M Specification for Industrial Platinum Resis-tan
12、ce Thermometers2.2 ISO Standards:31These test methods are under the jurisdiction of ASTM Committee D02 onPetroleum Products and Lubricants and is the direct responsibility of SubcommitteeD02.08 on Volatility.Current edition approved May 15, 2012. Published October 2012. Originallyapproved in 1979. L
13、ast previous edition approved in 2009 as D382809. DOI:10.1520/D3828-12.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe AST
14、M website.3Available from American National Standards Institute (ANSI), 25 W. 43rd St.,4th Floor, New York, NY 10036, http:/www.ansi.org.1*A Summary of Changes section appears at the end of this standard.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-29
15、59, United States.Guide 34 Quality Systems Guidelines for the Production ofReference MaterialsGuide 35 Certification of Reference MaterialsGeneraland Statistical PrinciplesEN ISO 3679 Determination of Flash PointRapid Equi-librium Closed Cup MethodEN ISO 3680 Determination of Flash/No FlashRapidEqui
16、librium Closed Cup MethodISO 60751 Industrial platinum resistance thermometers andplatinum temperature sensors2.3 Energy Institute Standards:4IP 523 Determination of flash point Rapid equilibriumclosed cup methodIP 524 Determination of flash/no flash Rapid equilibriumclosed cup method3. Terminology3
17、.1 Definitions:3.1.1 equilibrium, nin flash point test methods, the con-dition where the vapor above the test specimen, and the testspecimen are at the same temperature at the time the ignitionsource is applied.3.1.1.1 DiscussionThis condition may not be fullyachieved in practice, since the temperat
18、ure may not be uniformthroughout the test specimen, and the test cover and shutter onthe apparatus can be cooler or warmer.3.1.2 flash point, nin flash point test methods, the lowesttemperature corrected to a pressure of 101.3 kPa (760 mm Hg)at which application of an ignition source causes the vapo
19、rs ofa specimen of the sample to ignite under specified conditions oftest.4. Summary of Test Methods4.1 Method AFlash/No Flash TestA test specimen isintroduced, by a syringe, into the test cup of the selectedapparatus that is set and maintained at the specified tempera-ture. After a specific time an
20、 ignition source is applied and adetermination made as to whether or not a flash occurred.4.2 Method BFinite (or Actual) Flash PointThismethod essentially repeats MethodAa number of times, and bychanging the test temperature and test specimen a number oftimes, determines the flash point.4.2.1 A test
21、 specimen is introduced into the test cup of theselected apparatus that is maintained at the expected flashpoint. After a specified time an ignition source is applied and adetermination made whether or not a flash occurred.4.2.2 The test specimen is removed from the test cup; thetest cup and cover a
22、re cleaned, and the test temperatureadjusted 5C (9F) lower or higher depending on whether ornot a flash occurred previously. A fresh test specimen isintroduced and tested. This procedure is repeated until the flashpoint is established within 5C (9F).4.2.3 The procedure is then repeated at 1C (2F) in
23、tervalsuntil the flash point is determined to the nearest 1C (2F).4.2.4 If improved accuracy is desired the procedure isrepeated at 0.5C (1F) intervals until the flash point isdetermined to the nearest 0.5C (1F).4.3 Test Time and Specimen Volume:4.3.1 For all products, except biodiesel; for test tem
24、pera-tures up to and including 100C (212F), the test time is 1minute and the specimen volume is 2 mL.4.3.2 For all products, except biodiesel; for test tempera-tures over 100C (212F), the test time is 2 minute and thespecimen volume is 4 mL.4.3.3 For biodiesel; for all test temperatures, the test ti
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD38282012STANDARDTESTMETHODSFORFLASHPOINTBYSMALLSCALECLOSEDCUPTESTER 刻度 试验 测定 液体 闪点 标准 方法 PDF

链接地址:http://www.mydoc123.com/p-515575.html