ASTM D3201 D3201M-2013 Standard Test Method for Hygroscopic Properties of Fire-Retardant Wood and Wood-Based Products《阻燃木材和木制品吸湿特性的标准试验方法》.pdf
《ASTM D3201 D3201M-2013 Standard Test Method for Hygroscopic Properties of Fire-Retardant Wood and Wood-Based Products《阻燃木材和木制品吸湿特性的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM D3201 D3201M-2013 Standard Test Method for Hygroscopic Properties of Fire-Retardant Wood and Wood-Based Products《阻燃木材和木制品吸湿特性的标准试验方法》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D3201 08a1D3201/D3201M 13Standard Test Method forHygroscopic Properties of Fire-Retardant Wood and Wood-Based Products1This standard is issued under the fixed designation D3201;D3201/D3201M; the number immediately following the designation indicatesthe year of original adoption or, in t
2、he case of revision, the year of last revision. A number in parentheses indicates the year of lastreapproval. A superscript epsilon () indicates an editorial change since the last revision or reapproval.1 NOTENote 2 was editorially added in October 2009.1. Scope1.1 This test method prescribes the pr
3、ocedure for determining the hygroscopicity of fire retardant treated wood products bydetermining the moisture content of fire-retardant-treated wood and wood-based product samplesspecimens after exposure to astandard high relative humidity test condition of 92 6 2 % at 27 6 2C (81 6 4F).relative hum
4、idity at 81 6 4F 27 6 2C.1.2 The text of this test method references notes and footnotes which provide explanatory material. These notes and footnotes(excluding those in tables and figures) shall not be considered as requirements of this test method.1.3 The values stated in either SI units or inch-p
5、ound units are to be regarded separately as the standard. The inch-pound valuesgiven in parentheses are for information only and are not considered stated in each system may not be exact equivalents; therefore,each system shall be used independently of the other. Combining values from the two system
6、s may result in non-conformance withthe standard.1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibilityof the user of this standard to establish appropriate safety and health practices and determine the applicability of reg
7、ulatorylimitations prior to use.2. Referenced Documents2.1 ASTM Standards:2D9 Terminology Relating to Wood and Wood-Based ProductsE84 Test Method for Surface Burning Characteristics of Building MaterialsE176 Terminology of Fire StandardsE2768 Test Method for Extended Duration Surface Burning Charact
8、eristics of Building Materials (30 min Tunnel Test)3. Terminology3.1 DefinitionsDefinitions used in this practice are in accordance with Terminologies D9 and E176.4. Significance and Use4.1 The hygroscopic properties of wood and wood-based products treated with fire-retardant chemicals are often gre
9、ater thanfor untreated products. This is particularly true at the higher relative humidity conditions. This higher hygroscopicity sometimesis the cause for staining, decay, poor paint adhesion, and migration and exuding of chemicals and moisture at the high humidities.Corrosion of metal fasteners so
10、metimes also occurs.4.2 The results obtained with this standard are important in identifying treatments with low hygroscopic properties.4.3 Results can be useful in determining exposure limitations in service for specific treated products.4.4 Building codes and other specifications for fire-retardan
11、t-treated wood for interior use include requirements based on thistest method.1 This test method is under the jurisdiction of ASTM Committee D07 on Wood and is the direct responsibility of Subcommittee D07.07 on Fire Performance of Wood.Current edition approved Nov. 1, 2008June 15, 2013. Published D
12、ecember 2008July 2013. Originally approved in 1973. Last previous edition approved in 2008 asD3201 08.D3201 081. DOI: 10.1520/D3201-08AE01.10.1520/D3201-13.2 For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at serviceastm.org. For Annual Book of ASTM
13、 Standardsvolume information, refer to the standards Document Summary page on the ASTM website.This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Becauseit may not be technically pos
14、sible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current versionof the standard as published by ASTM is to be considered the official document.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, W
15、est Conshohocken, PA 19428-2959. United States15. Apparatus5.1 Conditioning chamber with air circulation and capable of being maintained at 2781 6 2C (814F 27 6 4F)2C and arelative humidity of 92 6 2 %.5.2 Oven, air-circulated and vented, capable of maintaining a temperature of 103217 6 2C (2174F 10
16、3 6 4F).2C.5.3 Weighing ScaleA scale or balance that will weigh a specimen within an accuracy of 60.2 %.6. Test Specimens6.1 A minimum of five specimens shall be selected that represent the lot. Unless otherwise specified, specimens shall be fullcross sections, no less than 25.4 mm (1 in.) along the
17、 grain, but longer as needed to provide a minimum volume of 33 000 mmfromthe untreated product/species combination that is to be tested. Solid wood specimens with identifiable sapwood shall be selectedwith as much sapwood as can be readily obtained from the lot of material from3 (2 in. which3). it i
18、s selected.6.2 Specimen Size:6.2.1 Solid wood specimens shall be cross sections cut from solid sawn, surfaced lumber of nominal 26 size. The testspecimens shall be 1.0 6 0.1 in. 25 6 3 mm along the grain by 5.5 6 0.1 in. 139 6 3 mm wide by 1.5 6 0.1 in. 38 6 3 mmdeep.6.2.2 Panel product specimens sh
19、all be cut from panels with a nominal thickness between 15/32 in. 12 mm and 5/8 in. 16mm. The test specimens shall be the thickness of the panel by 5.5 6 0.1 in. 139 6 3 mm by 5.5 6 0.1 in. 139 6 3 mm.6.2.3 Products for which the specimen sizes in 6.2.1 and 6.2.2 are not applicable may be tested usi
20、ng specimens with surfacearea to volume ratios greater than 3.7 in.2:1 in.3 0.15 mm2:1 mm3 and minimum mass of 0.11 lb. 50 g.6.3 The specimens shall be penetrated by the fire-retardant chemical to be representative for the treated product.Treatment withfire-retardant chemicals shall be done in a man
21、ner representative of that for the product/species being tested.NOTE 1The use of untreated specimens as control specimens is recommended to provide verification of the high-humidity conditions used.6.3.1 The fire retardant chemical retention of the treated product shall not be less than that specifi
22、ed by the agency certifyingthe flame spread index of the treated product. The retention shall provide a flame-spread index of 25 or less when tested inaccordance with either Test Method E2768 or with Test Method E84 for 10 min with no evidence of significant progressioncombustion when the test is co
23、ntinued for an additional 20-min period and without progression of the flame front beyond a distanceof 10.5 ft. 3.2 m beyond the centerline of the burners anytime during the 30-min extended test.6.3.2 The provisions of 6.3.1 are not intended to prevent use of this test method when the fire-retardant
24、 treatments being testedare for applications other than those requiring conformance to building code requirements for “fire-retardant-treated wood” thatrequire Test Method E84 test extended to 30 min or Test Method E2768. When alternative performance criteria for the treatedproducts are applicable,
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD3201D3201M2013STANDARDTESTMETHODFORHYGROSCOPICPROPERTIESOFFIRERETARDANTWOODANDWOODBASEDPRODUCTS

链接地址:http://www.mydoc123.com/p-514293.html