《ASTM D1934-1995(2005) Standard Test Method for Oxidative Aging of Electrical Insulating Petroleum Oils by Open-Beaker Method《用开杯法作电绝缘石油的氧化老化的标准试验方法》.pdf》由会员分享,可在线阅读,更多相关《ASTM D1934-1995(2005) Standard Test Method for Oxidative Aging of Electrical Insulating Petroleum Oils by Open-Beaker Method《用开杯法作电绝缘石油的氧化老化的标准试验方法》.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: D 1934 95 (Reapproved 2005)Standard Test Method forOxidative Aging of Electrical Insulating Petroleum Oils byOpen-Beaker Method1This standard is issued under the fixed designation D 1934; the number immediately following the designation indicates the year oforiginal adoption or, in the
2、case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This test method covers two procedures for subjectingelectrical insulating oils to oxid
3、ative aging:1.1.1 Procedure A, without a metal catalyst, and1.1.2 Procedure B, with a metal catalyst.1.2 This test method is applicable to oils used as impreg-nating or pressure media in electrical power transmissioncables if less than 10 % of the oil evaporates during the agingprocedures. It applie
4、s and is generally useful primarily in theevaluation and quality control of unused oils, either inhibitedor uninhibited.1.3 The values stated in SI units are to be regarded as thestandard. The values given in parentheses are for informationonly.1.4 This standard does not purport to address all of th
5、esafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2D 664 Test Method forAcid N
6、umber of Petroleum Productsby Potentiometric TitrationD 923 Practices for Sampling Electrical Insulating LiquidsD 924 Test Method for Dissipation Factor (or Power Factor)and Relative Permittivity (Dielectric Constant) of Electri-cal Insulating LiquidsD 1169 Test Method for Specific Resistance (Resis
7、tivity) ofElectrical Insulating LiquidsE 145 Specification for Gravity-Convection and Forced-Ventilation OvensE 177 Practice for Use of the Terms Precision and Bias inASTM Test Methods3. Terminology3.1 Definitions of Terms Specific to This Standard:3.1.1 metal catalystany metal (for example, copper)
8、 thateither increases the rate of oxidation of the oil or reacts with theoxidation products to increase oil dielectric loss.3.1.2 oxidative agingexposure of oil to oxygen undercertain specified conditions.4. Summary of Test Method4.1 A 300 mL volume of oil, contained in 400 mL beaker isaged for 96 h
9、 in a circulating-air oven controlled at 115C,either with or without the presence of catalyst.5. Significance and Use5.1 Open-beaker oxidative aging methods have been usedfor many years in laboratories of oil companies, electricalequipment manufacturers, and electric utility companies inter-ested in
10、 the stability of electrical insulating oils under oxidativeconditions. They are particularly useful as a check on thecontinuity of production and shipment of insulating oils. Theyare also useful as process and product checks for applicabletype oils.5.2 Specification limits for oils subjected to ope
11、n-beakeroxidative aging by this method are established by agreementbetween individual producers and consumers of applicabletype oils. These properties of the oil involved in specificationlimits for aging stability may be measured after the oxidativeaging (and sometimes before aging) by appropriate t
12、est meth-ods such as Test Method D 924, Test Method D 1169, and TestMethod D 664.6. Apparatus6.1 Oven, electrically heated, thermostatically controlled,capable of maintaining a constant temperature of 115 6 1C(239 6 2F). Use an oven with a testing chamber large enoughto test the anticipated number o
13、f test specimens at one time. Auniformity of temperature within 61 % of the differentialbetween oven and ambient temperatures is required. (See Note1.) Circulate air in the chamber with a low velocity fan duringthe aging period. The volume and condition of the circulatedair is not considered to be c
14、ritical. It is recommended that the1This test method is under the jurisdiction of ASTM Committee D27 onElectrical Insulating Liquids and Gases and is the direct responsibility of Subcom-mittee D27.06 on Chemical Test.Current edition approved Oct. 1, 2005. Published November 2005. Originallyapproved
15、in 1962. Last previous edition approved in 2000 as D 1934 95 (2000).2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM w
16、ebsite.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.oven provide several air changes per hour, and that vapors andfumes be removed if present.NOTE 1Refer to Specification E 145 for the measurement of thetemperature uniformity of t
17、he oven.6.1.1 Procedure AFor test specimens aged in the absenceof a metal catalyst the choice of a suitable oven design is notcritical. Either fixed- or rotating-shelf stage ovens of satisfac-tory thermal quality may be used, although a rotating-shelfoven is preferred. If a fixed-shelf oven is used,
18、 it is recom-mended that test specimen positions within the oven bechanged periodically (for example, at daily intervals) to mini-mize the effects of any temperature differentials that may exist.6.1.2 Procedure BWhen a metal catalyst, such as copper,is used, the rate of oxidation usually is increase
19、d, and theprocedure becomes sensitive to movement of the oil past themetal surface. An aging oven equipped with a slowly rotatingshelf has been adopted for uniformity when a metal catalyst isused.3Other oven designs having satisfactory thermal qualityand a rotating shelf may be used.6.2 Beaker, boro
20、silicate glass, low-form, of 400-mL capac-ity. The approximate dimensions of a suitable beaker are100 mm in depth and 70 mm inside diameter. Clean the beakersused in the aging test, and thoroughly dry before use. Onerecommended cleaning procedure is as follows: Remove re-sidual oil from the beaker b
21、y rinsing in mineral spirits orequivalent. Rinse thoroughly with an acid cleaning solutionconsisting of 3 parts nitric acid (HNO3) to 1 part sulfuric acid(H2SO4). Remove traces of cleaning solution by carefullyrinsing with distilled water followed by rinsing in acetone andair drying. (Ammonium persu
22、lfate is also a suitable cleaningreagent.)47. Reagents and Materials7.1 Purity of ReagentsUse reagent grade chemicals in alltests. Unless otherwise indicated, it is intended that all reagentsshall conform to the specifications of the Committee onAnalytical Reagents of the American Chemical Society,
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD193419952005STANDARDTESTMETHODFOROXIDATIVEAGINGOFELECTRICALINSULATINGPETROLEUMOILSBYOPENBEAKERMETHOD

链接地址:http://www.mydoc123.com/p-510708.html