1、Designation: D1068 10An American National StandardStandard Test Methods forIron in Water1This standard is issued under the fixed designation D1068; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number
2、 in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope*1.1 These test methods cover the determination of iron inwater.
3、 Procedures are given for determining total iron, dis-solved iron, and ferrous iron. Undissolved iron may becalculated from the total iron and dissolved iron determina-tions. The test methods are given as follows:Range SectionsTest Method AAtomic Absorption,Direct0.1 to 5.0 mg/L 7 to 16Test Method B
4、Atomic Absorption,Graphite Furnace5 to 100 g/L 17 to 26Test Method CPhotometricBathophenanthroline g/L40 to 1000 g/L 27 to 381.2 It is the users responsibility to ensure the validity ofthese test methods to waters of untested matrices.1.3 The chelation-extraction and two former photometrictest metho
5、ds were discontinued. See Appendix X2 for histori-cal information.1.4 The values stated in SI units are to be regarded asstandard. No other units of measurement are included in thisstandard.1.5 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It i
6、s theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use. Specific hazardsstatements are given in Note 3, 11.7.1, and X1.1.2.2. Referenced Documents2.1 ASTM Standards:2D858 Test Meth
7、ods for Manganese in WaterD1066 Practice for Sampling SteamD1129 Terminology Relating to WaterD1193 Specification for Reagent WaterD1687 Test Methods for Chromium in WaterD1688 Test Methods for Copper in WaterD1691 Test Methods for Zinc in WaterD1886 Test Methods for Nickel in WaterD2777 Practice fo
8、r Determination of Precision and Bias ofApplicable Test Methods of Committee D19 on WaterD3370 Practices for Sampling Water from Closed ConduitsD3558 Test Methods for Cobalt in WaterD3559 Test Methods for Lead in WaterD3919 Practice for Measuring Trace Elements in Water byGraphite Furnace Atomic Abs
9、orption SpectrophotometryD4841 Practice for Estimation of Holding Time for WaterSamples Containing Organic and Inorganic ConstituentsD5810 Guide for Spiking into Aqueous SamplesD5847 Practice for Writing Quality Control Specificationsfor Standard Test Methods for Water AnalysisE60 Practice for Analy
10、sis of Metals, Ores, and RelatedMaterials by Molecular Absorption SpectrometryE275 Practice for Describing and Measuring Performanceof Ultraviolet and Visible Spectrophotometers3. Terminology3.1 Definitions: For definitions of terms used in these testmethods, refer to Terminology D1129.3.2 Definitio
11、ns of Terms Specific to This Standard:3.2.1 total recoverable iron, nan arbitrary analytical termrelating to the recoverable forms of iron that are determinableby the digestion method which is included in these testmethods.4. Significance and Use4.1 Iron is the second most abundant metallic element
12、in theearths crust and is essential in the metabolism of plants andanimals. If presented in excessive amounts, however, it formsoxyhydroxide precipitates that stain laundry and porcelain. Asa result, the recommended limit for iron in domestic watersupplies is 0.3 mg/L. These test methods are useful
13、fordetermining iron in many natural waters.1These test methods are under the jurisdiction of ASTM Committee D19 onWater and are the direct responsibility of Subcommittee D19.05 on InorganicConstituents in Water.Current edition approved Sept. 1, 2010. Published October 2010. Originallyapproved in 194
14、9. Last previous edition approved in 2005 as D1068 051. DOI:10.1520/D1068-10.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page ont
15、he ASTM website.1*A Summary of Changes section appears at the end of this standard.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.5. Purity of Reagents5.1 Reagent grade chemicals shall be used in all tests.Unless otherwise indicated,
16、 it is intended that all reagents shallconform to the specifications of the Committee on AnalyticalReagents of the American Chemical Society, where suchspecifications are available.3Other grades may be used,provided it is first ascertained that the reagent is of sufficientlyhigh purity to permit its
17、 use without lessening the accuracy ofthe determination.5.2 Purity of WaterUnless otherwise indicated, referencesto water shall be understood to mean reagent water conformingto Specification D1193, Type I. Other reagent water types maybe used, provided it is first ascertained that the water is ofsuf
18、ficiently high purity to permit its use without adverselyaffecting the bias and precision of the test method. Type IIwater was specified at the time of round-robin testing of thesetest methods. In addition, water used in preparing solutions forthe determination of ferrous iron shall be freshly boile
19、d andessentially oxygen free.6. Sampling6.1 Collect the sample in accordance with Practice D1066or Practices D3370, as applicable.6.2 Samples should be preserved with HNO3or HCl (sp gr1.42) to a pH of 2 or less immediately at the time of collection.If only dissolved iron is to be determined, the sam
20、ple shall befiltered through a 0.45-m membrane filter before acidification.The holding time for samples can be calculated in accordancewith Practice D4841.6.3 If ferrous iron is to be determined, the sample should beanalyzed as soon as possible after collection and contact withatmospheric oxygen sho
21、uld be minimized.6.4 Additional information on sampling requirements forTest Method C is provided in 33.1.TEST METHOD AATOMIC ABSORPTION, DIRECT7. Scope7.1 This test method covers the determination of dissolvedand total recoverable iron in most waters and wastewaters.7.2 This test method is applicab
22、le in the range from 0.1 to5.0 mg/L of iron. The range may be extended to concentrationsgreater than 5.0 mg/L by dilution of the sample.7.3 This test method has been used successfully withreagent water; tap, ground, and surface waters; unspecifiedwastewaters; and a refinery primary treatment water.
23、It is theusers responsibility to ensure the validity of this test methodfor waters of untested matrices.8. Summary of Test Method8.1 Iron is determined by atomic absorption spectrophotom-etry. Dissolved iron is determined by atomizing the filteredsample directly with no pretreatment. Total recoverab
24、le iron isdetermined by atomizing the sample following hydrochloric-nitric acid digestion and filtration. The same digestion proce-dure may be used to determine total recoverable nickel (TestMethods D1886), chromium (Test Methods D1687), cobalt(Test Methods D3558), copper (Test Methods D1688), lead(
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMD10682010STANDARDTESTMETHODSFORIRONINWATER 水中 标准 试验 方法 PDF

链接地址:http://www.mydoc123.com/p-509209.html