ASTM C980-2017 Standard Specification for Industrial Chimney Lining Brick《工业烟囱衬砖的标准规格》.pdf
《ASTM C980-2017 Standard Specification for Industrial Chimney Lining Brick《工业烟囱衬砖的标准规格》.pdf》由会员分享,可在线阅读,更多相关《ASTM C980-2017 Standard Specification for Industrial Chimney Lining Brick《工业烟囱衬砖的标准规格》.pdf(4页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C980 13aC980 17Standard Specification forIndustrial Chimney Lining Brick1This standard is issued under the fixed designation C980; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last revision. A number in
2、parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope*1.1 This specification covers solid kiln fired brick made from clay, shale, or mixtures thereof suitable for use in masonryconstruction in contact w
3、ith the chemicals present in flue gases found in industrial chimneys. These brick are normally used withchemical-resistant mortars.1.2 Terminology related to industrial floor brick is found in Terminology C1232.1.3 UnitsThe values stated in inch-pound units are to be regarded as standard. The values
4、 given in parentheses aremathematical conversions to SI units that are provided for information only and are not considered standard.1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibilityof the user of this standard to esta
5、blish appropriate safety and health practices and determine the applicability of regulatorylimitations prior to use.1.5 This international standard was developed in accordance with internationally recognized principles on standardizationestablished in the Decision on Principles for the Development o
6、f International Standards, Guides and Recommendations issuedby the World Trade Organization Technical Barriers to Trade (TBT) Committee.2. Referenced Documents2.1 ASTM Standards:2C20 Test Methods for Apparent Porosity, Water Absorption, Apparent Specific Gravity, and Bulk Density of Burned Refractor
7、yBrick and Shapes by Boiling WaterC67 Test Methods for Sampling and Testing Brick and Structural Clay TileC1232E11 Specification for Woven Wire Test Sieve Cloth and Test Sieves3. Terminology3.1 DefinitionsFor definitions relating to industrial chimney lining brick, refer to Terminology C1232.4. Clas
8、sification4.1 The physical and chemical properties of chimney lining brick differ from supplier to supplier mainly because theircomposition is determined by the source of raw materials. Chimney lining brick, regardless of these differences, are consideredto be of three types noted as follows:4.1.1 T
9、ype IFor use where low absorption and high acid resistance are not major factors.4.1.2 Type IIFor use where lower absorption and higher acid resistance are required.4.1.3 Type IIIFor use where lowest absorption and highest acid resistance are required.NOTE 1Types I, II, and III may not differ signif
10、icantly in their resistance to thermal shock, and selection of brick type should be based upon theirabsorption and acid-resistant service requirements.5. Sulfuric Acid Boil Test5.1 When tested in accordance with Section 9, the brick shall conform to the requirements for “MaximumAverage Weight Lossby
11、 H2SO4 Boil Test” as shown in Table 1.1 This specification is under the jurisdiction of ASTM Committee C15 on Manufactured Masonry Units and is the direct responsibility of Subcommittee C15.02 on Brickand Structural Clay Tile.Current edition approved Dec. 15, 2013June 1, 2017. Published January 2014
12、July 2017. Originally approved in 1982. Last previous edition approved in 2013 asC980 13.C980 13a. DOI: 10.1520/C0980-13A.10.1520/C0980-17.2 For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at serviceastm.org. For Annual Book of ASTM Standardsvolume
13、information, refer to the standards Document Summary page on the ASTM website.This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Becauseit may not be technically possible to adequate
14、ly depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current versionof the standard as published by ASTM is to be considered the official document.*A Summary of Changes section appears at the end of this standardCopyright ASTM Inte
15、rnational, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States16. Physical Properties6.1 Compressive StrengthWhen tested in accordance with Test Methods C67, Section 6 (Compressive Strength), the brickshall conform to the requirements for “Minimum Compressive Strength
16、” as shown in Table 1.6.2 Water AbsorptionWhen tested in accordance with Test Methods C20, the brick shall conform to the requirements for“Maximum Water Absorption by 2-h Boiling” as shown in Table 1.7. Dimensions, Mass, and Permissible Variations7.1 SizesThe sizes of brick shall be as specified by
17、the purchaser. When tested in accordance with Test Methods C67, Section11 (Measurement of Size), the brick shall conform to the requirements for “Permissible Variations in Dimensions” as shown inTable 2.7.2 WarpageWhen tested in accordance with Test Methods C67, Section 12 (Measurement of Warpage),
18、the tolerance onwarpage of the brick shall be as indicated in Table 2.8. Finish and Appearance8.1 Black HeartBrick when broken may have a dark area that has a steely appearance and is sharply delineated from thesurrounding normal color of the brick it is known as black heart or black core. Black hea
19、rt is generally the result of the reductionof iron minerals during the firing process. Its presence, regardless of size in brick that otherwise meet the physical and chemicalrequirements of this specification, shall not be cause for rejection.8.2 TextureScoring or matte texturing, or both, of the br
20、ick is recommended. However, no flutes or scores shall exceed 18 in.(3.0 mm) in height of protrusion or in depth.9. Test for Solubility in Sulfuric Acid9.1 Significance and UseThis test with sulphuric acid represents an extremely severe one and may not be significant forchemical-resistant brick in l
21、ess demanding applications. It can be assumed that sulphuric acid in this test concentration will be morecorrosive than most other acids excluding those containing flourine. A similar test procedure using other chemicals may be moresuitable for specific purposes. The performance of these other tests
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC9802017STANDARDSPECIFICATIONFORINDUSTRIALCHIMNEYLININGBRICK 工业 烟囱 标准 规格 PDF

链接地址:http://www.mydoc123.com/p-509040.html