ASTM C90-2014 Standard Specification for Loadbearing Concrete Masonry Units《承重混凝土砌块的标准规格》.pdf
《ASTM C90-2014 Standard Specification for Loadbearing Concrete Masonry Units《承重混凝土砌块的标准规格》.pdf》由会员分享,可在线阅读,更多相关《ASTM C90-2014 Standard Specification for Loadbearing Concrete Masonry Units《承重混凝土砌块的标准规格》.pdf(5页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C90 13C90 14Standard Specification forLoadbearing Concrete Masonry Units1This standard is issued under the fixed designation C90; the number immediately following the designation indicates the year of originaladoption or, in the case of revision, the year of last revision.Anumber in par
2、entheses indicates the year of last reapproval.Asuperscriptepsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the U.S. Department of Defense.1. Scope*1.1 This specification covers hollow and solid (see 5.3 and 5.4) co
3、ncrete masonry units made from hydraulic cement, water, andmineral aggregates with or without the inclusion of other materials. There are three classes of concrete masonry units: (1) normalweight, (2) medium weight, and (3) lightweight. These units are suitable for both loadbearing and nonloadbearin
4、g applications.1.2 Concrete masonry units covered by this specification are made from lightweight or normal weight aggregates, or both.NOTE 1The requirements of this specification have been researched, evaluated, and established for over a century, resulting in the physical propertiesand attributes
5、defined here. These requirements are uniquely and solely applicable to concrete masonry units manufactured on equipment using low orzero slump concrete and the constituent materials defined herein. Many performance attributes of concrete masonry units are indirectly accounted for,or inherently refle
6、cted within, the requirements of this specification without direct measurement, assessment, or evaluation. Applying the requirementsof this specification to products that may be similar in appearance, use, or nature to those covered by this specification may not address all pertinentphysical propert
7、ies necessary to ensure performance or serviceability of the resulting construction in real-world applications under typical exposureenvironments. Products manufactured using alternative materials, manufacturing methods, or curing processes not covered by this specification shouldnot be evaluated so
8、lely using the requirements in this specification; however, developers of new products can consider the property requirements of thisspecification as a beginning benchmark for unit performance. It is reasonable to test new products for system performance as well as unit performance.1.3 The text of t
9、his specification references notes and footnotes which provide explanatory material. These notes and footnotes(excluding those in tables and figures) shall not be considered as requirements of the standard.1.4 The values stated in inch-pound units are to be regarded as standard. The values given in
10、parentheses are mathematicalconversions to SI units that are provided for information only and are not considered standard.NOTE 2When particular features are desired such as surface textures for appearance or bond, finish, color, or particular properties such as densityclassification, higher compres
11、sive strength, fire resistance, thermal performance or acoustical performance, these features should be specified separatelyby the purchaser. Suppliers should be consulted as to the availability of units having the desired features.2. Referenced Documents2.1 ASTM Standards:2C33 Specification for Con
12、crete AggregatesC140 Test Methods for Sampling and Testing Concrete Masonry Units and Related UnitsC150 Specification for Portland CementC331 Specification for Lightweight Aggregates for Concrete Masonry UnitsC426 Test Method for Linear Drying Shrinkage of Concrete Masonry UnitsC595 Specification fo
13、r Blended Hydraulic CementsC618 Specification for Coal Fly Ash and Raw or Calcined Natural Pozzolan for Use in ConcreteC979 Specification for Pigments for Integrally Colored ConcreteC989 Specification for Slag Cement for Use in Concrete and MortarsC1157 Performance Specification for Hydraulic Cement
14、C1232 Terminology of MasonryC1240 Specification for Silica Fume Used in Cementitious MixturesC1314 Test Method for Compressive Strength of Masonry Prisms1 This specification is under the jurisdiction of ASTM Committee C15 on Manufactured Masonry Units and is the direct responsibility of Subcommittee
15、 C15.03 onConcrete Masonry Units and Related Units.Current edition approved June 1, 2013Feb. 1, 2014. Published June 2013February 2014. Originally approved in 1931. Last previous edition approved in 20122013 asC90 12.C90 13. DOI: 10.1520/C0090-13.10.1520/C0090-14.2 For referencedASTM standards, visi
16、t theASTM website, www.astm.org, or contactASTM Customer Service at serviceastm.org. For Annual Book of ASTM Standardsvolume information, refer to the standards Document Summary page on the ASTM website.This document is not an ASTM standard and is intended only to provide the user of an ASTM standar
17、d an indication of what changes have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current versionof the standard as published by ASTM i
18、s to be considered the official document.*A Summary of Changes section appears at the end of this standardCopyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States1E519 Test Method for Diagonal Tension (Shear) in Masonry AssemblagesE72 Test Met
19、hods of Conducting Strength Tests of Panels for Building Construction3. Terminology3.1 Terminology defined in Terminology C1232 shall apply for this specification.4. Materials4.1 Cementitious MaterialsMaterials shall conform to the following applicable specifications:4.1.1 Portland CementSpecificati
20、on C150.4.1.2 Modified Portland CementPortland cement conforming to Specification C150, modified as follows:(1) LimestoneIf calcium carbonate is added to the cement, the CaCO3 content shall not be less than 85 %.(2) Limitation on Insoluble Residue1.5 %.(3) Limitation on Air Content of MortarVolume p
21、ercent, 22 % max.(4) Limitation on Loss on Ignition7 %.4.1.3 Blended Hydraulic CementsSpecification C595.4.1.4 Hydraulic CementSpecification C1157.4.1.5 PozzolansSpecification C618.4.1.6 Blast Furnace Slag CementSpecification C989.4.1.7 Silica FumeSpecification C1240.4.2 AggregatesAggregates shall c
22、onform to the following specifications, except that grading requirements shall notnecessarily apply:4.2.1 Normal Weight AggregatesSpecification C33.4.2.2 Lightweight AggregatesSpecification C331.4.3 Pigments for Integrally Colored ConcreteSpecification C979.4.4 Other ConstituentsAir-entraining agent
23、s, integral water repellents, and other constituents shall be previously establishedas suitable for use in concrete masonry units and shall conform to applicable ASTM standards or shall be shown by test orexperience not to be detrimental to the durability of the concrete masonry units or any materia
24、l customarily used in masonryconstruction.5. Physical Requirements5.1 At the time of delivery to the purchaser, units shall conform to the physical requirements prescribed in Table 1 and Table2. All units shall be sound and free of cracks or other defects that interfere with the proper placement of
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC902014STANDARDSPECIFICATIONFORLOADBEARINGCONCRETEMASONRYUNITS 承重 混凝土 砌块 标准 规格 PDF

链接地址:http://www.mydoc123.com/p-508716.html