《ASTM C857-2007 Standard Practice for Minimum Structural Design Loading for Underground Precast Concrete Utility Structures《地下预制混凝土多用途结构用最低结构设计负荷的标准实施规程》.pdf》由会员分享,可在线阅读,更多相关《ASTM C857-2007 Standard Practice for Minimum Structural Design Loading for Underground Precast Concrete Utility Structures《地下预制混凝土多用途结构用最低结构设计负荷的标准实施规程》.pdf(7页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C 857 07Standard Practice forMinimum Structural Design Loading for UndergroundPrecast Concrete Utility Structures1This standard is issued under the fixed designation C 857; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revisio
2、n, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon (e) indicates an editorial change since the last revision or reapproval.1. Scope1.1 This practice describes the minimum live loads and deadloads to be applied when designing monolithic o
3、r sectionalprecast concrete utility structures. Concrete pipe, box culverts,and material covered in Specification C 478 are excluded fromthis practice.NOTE 1For additional information see AASHTO Standard Specifica-tion for Highway Bridges, Seventeenth Edition.NOTE 2The purchaser is cautioned that he
4、 must properly correlate theanticipated loading conditions and the field requirements with the designloads used.1.2 The values stated in inch-pound units are to be regardedas the standard. The values given in parentheses are forinformation only.1.3 This standard does not purport to address all of th
5、esafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2C 478 Specification for Pre
6、cast Reinforced Concrete Man-hole Sections2.2 AASHTO Standard:Specification for Highway Bridges, Seventeenth Edition33. Terminology3.1 Definitions of Terms Specific to This Standard:3.1.1 dead loadswill consist of any other load that canaffect the design of the structure.3.1.2 live loadswill consist
7、 of any moving loads that canaffect the design of the structure and their associated impactand surcharge loads.3.1.3 utility structurea structure that is used by electric,gas, communication, or similar industries.4. Design Loads4.1 RoofThe design loads for the roof of any structure ator below ground
8、 level consists of the live loads includingimpact and dead loads that can develop as a result of earthpressure, hydrostatic pressure, and construction materials suchas used for roadways and walkways.4.1.1 Live LoadsThe vehicle and pedestrian load desig-nations are given in Table 1. Live load wheel s
9、pacing is shownin Fig. 1.4.1.2 Impact:4.1.2.1 The live loads A-16, A-12, and A-8 should beincreased as follows to sustain the effect of impact:4.1.2.2 Live Load Increase:0 to 12 in. (0 to 305 mm) below ground level, 30 %13 to 24 in. (330 to 610 mm) below ground level, 20 %25 to 35 in. (635 to 889 mm
10、) below ground level, 10 %36 in. (914 mm) or more below ground level, 0 %4.1.3 Dead LoadsDead loads will consist of the weight ofthe roof, roadbed, walkways, earth fill, access opening covers,and any other material that produces a static load.4.1.3.1 Recommended unit weights of materials for designc
11、alculations are as follows:Concrete, plain, and reinforced 150 lb/ft3(2043 kg/m3)Cast iron 450 lb/ft3(7208 kg/m3)Steel 490 lb/ft3(7850 kg/m3)Aluminum 175 lb/ft3(2804 kg/m3)Earth fill (dry) 110 lb/ft3(1762 kg/m3)Macadam 140 lb/ft3(2243 kg/m3)4.1.4 Distribution of Wheel Loads Through Earth Fills:4.1.4
12、.1 Wheel loads at ground level should be consideredapplied to a wheel load area as indicated in Fig. 2.4.1.4.2 Wheel loads should be distributed below groundlevel as a truncated pyramid, as shown in Fig. 3, in which thetop surface is the wheel load area and the distributed load areais equal to the f
13、ollowing:1This practice is under the jurisdiction of ASTM Committee C27 on PrecastConcrete Products and is the direct responsibility of Subcommittee C27.10 onUtility Structures.Current edition approved June 1, 2007. Published June 2007. Originallyapproved in 1978. Last previous edition approved in 2
14、001 as C 857 95 (2001).2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from American Association o
15、f State Highway and TransportationOfficials (AASHTO), 444 N. Capitol St., NW, Suite 249, Washington, DC 20001.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.DLA 5 W 1 1.75 H! L 1 1.75 H! (1)where:DLA = distributed load area, ft2(m2)
16、W = wheel load width, ft (m),L = wheel load length, ft (m), andH = depth of fill, ft (m).4.1.4.3 When several distributed load areas overlap, thetotal load shall be considered as uniformly distributed over thearea defined by the outside limits of the individual areas asindicated in Fig. 4. When the
17、dimensions of the com-positedistributed load area exceeds the roof area only that portion ofthe distributed load on the roof area shall be considered in thedesign.4.1.4.4 The distribution of wheel loads through earth fillmay be neglected when the depth of fill exceeds 8 ft (2.5 m).4.2 WallsThe desig
18、n loads for the walls of any structure ator below ground level will consist of surcharge loads resultingfrom live loads, dead loads that can develop as a result of earthpressure, hydrostatic pressure, and construc-tion materials suchas used for roadways and walkways. Load diagrams of liveload surcha
19、rge and dead loads are shown in Fig. 5.4.2.1 Live Loads:4.2.1.1 When traffic can come within a horizontal distancefrom the structure equal to one half the height of the structure,a live load surcharge pressure of not less than 0.5 % of thewheel loading of the traffic involved should be taken as the
20、liveload acting upon the wall of the structure.4.2.1.2 Surcharge pressures for various live loads trans-ferred to equivalent horizontal fluid pressure are as follows:A-16 16 000 lbf per wheel 3 0.005 = 80 lbf/ft2(3830 Pa) per wheelA-12 12 000 lbf per wheel 3 0.005 = 60 lbf/ft2(2873 Pa) per wheelA-8
21、8 000 lbf per wheel 3 0.005 = 40 lbf/ft2(1915 Pa) per wheelA-0.3 Refer to 4.2.2.14.2.1.3 Surcharge pressures resulting from live loads maybe neglected when the distance from ground level exceeds 8 ft(2.5 m).4.2.2 Dead Loads:4.2.2.1 The dead loads will consist of an earth pressureabove ground water l
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC8572007STANDARDPRACTICEFORMINIMUMSTRUCTURALDESIGNLOADINGFORUNDERGROUNDPRECASTCONCRETEUTILITYSTRUCTURES

链接地址:http://www.mydoc123.com/p-508548.html