1、Designation: C 610 09Standard Specification forMolded Expanded Perlite Block and Pipe ThermalInsulation1This standard is issued under the fixed designation C 610; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the year of last rev
2、ision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.This standard has been approved for use by agencies of the Department of Defense.1. Scope1.1 This specification covers molded expanded per
3、liteblock, fittings, and pipe thermal insulation intended for use onsurfaces with temperatures between 80 to 1200F (27 to649C).1.2 The values stated in inch-pound units are to be regardedas standard. The values given in parentheses are mathematicalconversions to SI units that are provided for inform
4、ation onlyand are not considered standard.1.3 When the installation or use of thermal insulationmaterials, accessories, and systems may pose safety or healthproblems, the manufacturer shall provide the user appropriatecurrent information regarding any known problems associatedwith the recommended us
5、e of the companys products and shallalso recommend protective measures to be employed in theirsafe utilization. The following safety caveat applies only to thetest methods portion of this specification: This standard doesnot purport to address all of the safety concerns, if any,associated with its u
6、se. It is the responsibility of the user of thisstandard to establish appropriate safety and health practicesand determine the applicability of regulatory limitations priorto use.2. Referenced Documents2.1 ASTM Standards:2C 165 Test Method for Measuring Compressive Propertiesof Thermal InsulationsC
7、168 Terminology Relating to Thermal InsulationC 177 Test Method for Steady-State Heat Flux Measure-ments and Thermal Transmission Properties by Means ofthe Guarded-Hot-Plate ApparatusC 203 Test Methods for Breaking Load and Flexural Prop-erties of Block-Type Thermal InsulationC 302 Test Method for D
8、ensity and Dimensions of Pre-formed Pipe-Covering-Type Thermal InsulationC 303 Test Method for Dimensions and Density of Pre-formed Block and BoardType Thermal InsulationC 335 Test Method for Steady-State Heat Transfer Proper-ties of Pipe InsulationC 356 Test Method for Linear Shrinkage of Preformed
9、High-Temperature Thermal Insulation Subjected to Soak-ing HeatC 390 Practice for Sampling and Acceptance of ThermalInsulation LotsC411 Test Method for Hot-Surface Performance of High-Temperature Thermal InsulationC 421 Test Method for Tumbling Friability of PreformedBlock-Type and Preformed Pipe-Cov
10、ering-Type ThermalInsulationC 450 Practice for Fabrication of Thermal Insulating FittingCovers for NPS Piping, and Vessel LaggingC 518 Test Method for Steady-State Thermal TransmissionProperties by Means of the Heat Flow Meter ApparatusC 585 Practice for Inner and Outer Diameters of ThermalInsulatio
11、n for Nominal Sizes of Pipe and TubingC 795 Specification for Thermal Insulation for Use in Con-tact with Austenitic Stainless SteelC 1045 Practice for Calculating Thermal TransmissionProperties Under Steady-State ConditionsC 1058 Practice for Selecting Temperatures for Evaluatingand Reporting Therm
12、al Properties of Thermal InsulationC 1616 Test Method for Determining the Moisture Contentof Organic and Inorganic Insulation Materials by WeightE84 Test Method for Surface Burning Characteristics ofBuilding MaterialsE 136 Test Method for Behavior of Materials in a Vertical1This specification is und
13、er the jurisdiction of ASTM Committee C16 onThermal Insulation and is the direct responsibility of Subcommittee C16.20 onHomogeneous Inorganic Thermal Insulations.Current edition approved May 1, 2009. Published May 2009. Originallyapproved in 1967. Last previous edition approved in 2007 as C 610 07.
14、2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box
15、C700, West Conshohocken, PA 19428-2959, United States.Tube Furnace at 750C3. Terminology3.1 GeneralTerminology C 168 shall be considered asapplying to the terms used in this specification.3.2 Definitions of Terms Specific to This Standard:3.2.1 compositionmolded expanded perlite block, fitting,and p
16、ipe thermal insulation shall be composed principally ofexpanded perlite and silicate binders may contain reinforcingfibers.4. Standard Shapes, Sizes, and Dimensions4.1 Molded expanded perlite block, fitting, and pipe thermalinsulation shall be as follows:4.1.1 BlockBlock shall be furnished in length
17、s of either36 or 39.37 in. (914 or 1000 mm), widths of 6 in. (152 mm),12 in. (305 mm), 18 in. (457 mm), or 24 in. (610 mm), and inthickness from 112 to 6 in. (38 to 152 mm) in increments of12in. (13 mm).4.1.2 Pipe InsulationMolded expanded perlite pipe insu-lation shall be supplied either as hollow
18、cylindrical shapes splitin half lengthwise (in a plane including the cylindrical axis) orcurved segments. The pipe insulation shall be furnished insections or segments in lengths of either 36 or 39.37 in. (914 or1000 mm) to fit standard sizes of pipe and tubing, and innominal thickness from 1 to 4 i
19、n. (25 to 102 mm) in12-in.(13-mm) increments. Inner and outer diameters of multilayerconstruction may be specified. Inner and outer diameters shallbe in accordance with those standard dimensions specified inPractice C 585. Since outside diameter tolerances may bedifferent under individual manufactur
20、ing processes, it may benecessary to have pipe insulation furnished in two or morelayers nested by the manufacturer. The purchaser shall consultthe manufacturer for specific requirements.4.1.3 FittingsMolded (expanded insulation fittings shallconform to the inner and outer diameters in accordance wi
21、thPractice C 585. Mitered fittings shall be in accordance withPractice C 450.5. Dimensional Tolerances5.1 GeneralThe average tolerances for length, width, andthickness shall comply with the requirements shown in Table 1.5.2 Pipe InsulationThe following additional tolerancesapply to perlite pipe insu
22、lation supplied as half sections:5.2.1 Fit and ClosureWhen fitted to the appropriate sizepipe, the longitudinal seam of the pipe insulation shall close towithin116 in. (1.6 mm) along the entire length of the section.5.2.2 ConcentricityThe inner bore of the pipe insulationshall be concentric with the
23、 outer cylindrical surface. Thedeviation from concentricity shall not exceed18 in. (3.2 mm)or 5 % of the wall thickness, whichever is greater.5.2.3 Half-Section BalanceThe plane formed by the splitbetween half sections shall include the cylindrical axis. Devia-tion of the split plane from the cylind
24、er axis over the 36 or39.37-in. (914 or 1000-mm) length shall not exceed18 in. (3.2mm).6. Workmanship, Finish, and Appearance6.1 Since some requirements for this material are not easilydefined by a numerical value, the insulation shall not havevisible defects that will adversely affect its service q
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC6102009STANDARDSPECIFICATIONFORMOLDEDEXPANDEDPERLITEBLOCKANDPIPETHERMALINSULATIONPDF

链接地址:http://www.mydoc123.com/p-507752.html