《ASTM C511-2009 Standard Specification for Mixing Rooms Moist Cabinets Moist Rooms and Water Storage Tanks Used in the Testing of Hydraulic Cements and Concretes《水硬水泥和混凝土试验用搅拌室、湿气箱、.pdf》由会员分享,可在线阅读,更多相关《ASTM C511-2009 Standard Specification for Mixing Rooms Moist Cabinets Moist Rooms and Water Storage Tanks Used in the Testing of Hydraulic Cements and Concretes《水硬水泥和混凝土试验用搅拌室、湿气箱、.pdf(3页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C 511 09Standard Specification forMixing Rooms, Moist Cabinets, Moist Rooms, and WaterStorage Tanks Used in the Testing of Hydraulic Cementsand Concretes1This standard is issued under the fixed designation C 511; the number immediately following the designation indicates the year oforig
2、inal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope*1.1 This specification includes requirements for mixingrooms where
3、 paste and mortar specimens are prepared; and formoist cabinets, moist rooms, and water storage tanks wherepaste, mortar, and concrete specimens are stored.1.2 The values stated in SI units are to be regarded asstandard. No other units of measurement are included in thisstandard. Values in SI units
4、shall be obtained by measurementin SI units or by appropriate conversion, using the Rules forConversion and rounding given in Standard IEEE/ASTM SI10, of measurements made in other units.1.3 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is t
5、heresponsibility of the user of this standard to establish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2C51 Terminology Relating to Lime and Limestone (as usedby the Industry)E77 Test Metho
6、d for Inspection and Verification of Ther-mometersIEEE/ASTM SI 10 Standard for Use of the InternationalSystem of Units (SI): The Modern Metric System3. Terminology3.1 Definitions:3.1.1 mixing room, na room with controlled temperatureand relative humidity where cement paste and mortar speci-mens are
7、prepared.3.1.2 moist cabinet, na compartmented storage facility ofmoderate dimensions with controlled temperature and relativehumidity.3.1.3 moist room, na “walk-in” storage facility withcontrolled temperature and relative humidity, commonly calleda fog room when the prescribed relative humidity is
8、achievedby the atomization of water.4. Requirements for Cement Mixing Rooms4.1 The temperature of the air in the vicinity of the mixingslab, molds, and base plates shall be maintained at 23.0 6 4.0 C and at a relative humidity of not less than 50 %.4.2 The temperature of the mixing water used to pre
9、parecement paste and mortar specimens shall be 23.0 6 2.0 C.5. Temperature Measuring Devices5.1 Reference Temperature Measuring Deviceused toverify the temperature recorder, must be accurate and readableto 0.5 C. A copy of the certificate or report which verifies theaccuracy shall be available in th
10、e laboratory.NOTE 1The ice-point method described in Test Method E77may beused to ensure that no damage to the reference thermometer has occurredduring shipping.5.2 Temperature Recordershall record temperatures every15 min or less and shall be accurate and readable to 1 C. Thedata from the recorder
11、shall be evaluated at a minimum of onceeach week. A record of this evaluation documenting the datechecked, a confirmation that the data is within the requiredtemperature range, and the name of the individual performingthis evaluation shall be maintained in the laboratory. (Note 2)NOTE 2This requirem
12、ent may be satisfied by an initialed and datedtemperature recorder chart. Brief changes in the temperature due to dooropenings should be ignored.5.2.1 The temperature recorder shall be verified at leastevery six months or whenever there is a question of accuracy.5.2.1.1 For moist cabinets and rooms,
13、 position the referencetemperature measuring device in a readable position in air asnear as practical to the temperature recorder probe. Keep thedoor closed for at least 5 min prior to taking readings. Recordthe temperature readings of both the temperature recorder and1This specification is under th
14、e jurisdiction of ASTM Committee C01 onCement and is the direct responsibility of Subcommittee C01.95 on Coordination ofStandards.Current edition approved June 1, 2009. Published July 2009. Originally approvedin 1968. Last previous edition approved in 2006 as C 511 06.2For referenced ASTM standards,
15、 visit the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.1*A Summary of Changes section appears at the end of this standard.Copyright ASTM Internatio
16、nal, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.the reference temperature measuring device. When takingthese readings, the reference temperature measuring deviceshall remain in the moist cabinet or room and read immediatelyupon opening the door.5.2.1.2 For wa
17、ter storage tanks, position the referencetemperature measuring device in a readable position in water asnear as practical to the temperature recorder probe. Withoutremoving the reference temperature measuring device from thewater, record the temperature readings of both the temperaturerecorder and t
18、he reference temperature measuring device afterthe temperatures have stabilized.5.2.1.3 Verify the accuracy of the temperature recorder bycomparing the reading of the temperature recorder with that ofthe reference temperature measuring device during the normaloperation of the moist cabinet, moist ro
19、om or water storagetanks. If the difference between the temperature readings isgreater than 1 C, the temperature recorder shall be adjusted towithin 0.5 C of the reference temperature measuring device.6. Requirements for Moist Cabinets and Moist Rooms6.1 GeneralExcept during those times when specime
20、nsare being placed into or removed from storage, maintain theatmosphere in a moist cabinet or moist room at a temperatureof 23.0 6 2.0 C and a relative humidity of not less than 95 %.Maintain atmospheric conditions within a moist cabinet ormoist room such that test specimens in storage are saturated
21、with moisture to the degree needed to ensure that the exposedsurfaces of all specimens in storage both look moist and feelmoist (See Note 5). Equip all moist cabinets and moist roomswith a temperature recorder. The use of humidity recordingdevices is optional. Keep shelves on which fresh specimens a
22、replaced level.6.1.1 The air temperature inside the moist cabinet or moistroom shall be controlled with provisions made for heating orcooling, or both, as may be necessary. This shall be accom-plished in one of two ways:6.1.1.1 Thermostatically control the air temperature withinthe moist cabinet or
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC5112009STANDARDSPECIFICATIONFORMIXINGROOMSMOISTCABINETSMOISTROOMSANDWATERSTORAGETANKSUSEDINTHETESTINGOFHYDRAULICCEMENTSANDCONCRETES

链接地址:http://www.mydoc123.com/p-466898.html