《ASTM C1710-2016 Standard Guide for Installation of Flexible Closed Cell Preformed Insulation in Tube and Sheet Form《管和板形中柔性封闭单元预制绝缘部件安装的标准指南》.pdf》由会员分享,可在线阅读,更多相关《ASTM C1710-2016 Standard Guide for Installation of Flexible Closed Cell Preformed Insulation in Tube and Sheet Form《管和板形中柔性封闭单元预制绝缘部件安装的标准指南》.pdf(9页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C1710 16Standard Guide forInstallation of Flexible Closed Cell Preformed Insulation inTube and Sheet Form1This standard is issued under the fixed designation C1710; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the y
2、ear of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This guide covers recommended installation techniquesfor flexible closed cell pre-formed insulation in tube or
3、sheetform. This guide is applicable to materials manufactured inaccordance with Specification C534 (Elastomeric based insu-lation) or Specification C1427 (polyolefin based insulation).The materials covered in this guide encompass a servicetemperature of 297 to 300F (183 to 150C) as indicated inthe m
4、aterial specifications referenced above. Many of therecommendations made are specific to below ambient applica-tions only.1.2 The purpose of this guide is to optimize the thermalperformance and longevity of installed closed cell flexibleinsulation systems. By following this guide, the owner, anddesi
5、gner can expect to achieve the energy savings expected andprevention of condensation under the specified design condi-tions. This document is limited to installation procedures anddoes not encompass system design.1.3 The values stated in inch-pound units are to be regardedas standard. The values giv
6、en in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.4 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establish
7、appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2C168 Terminology Relating to Thermal InsulationC534 Specification for Preformed Flexible Elastomeric Cel-lular Thermal Insulation in Sheet and T
8、ubular FormC585 Practice for Inner and Outer Diameters of ThermalInsulation for Nominal Sizes of Pipe and TubingC1427 Specification for Extruded Preformed Flexible Cel-lular Polyolefin Thermal Insulation in Sheet and TubularForm2.2 Other Standards:National Commerical, Industrial Insulation Standards
9、(MICA Manual)3ASHRAE Handbook (Fundamentals Chapter 26)4ASHRAE Handbook (Refrigeration Chapter 33)43. Terminology3.1 DefinitionsTerminology C168 shall be considered asapplying to the terms in this specification.3.2 Definitions of Terms Specific to This Standard:3.2.1 seamsLongitudinal or horizontal
10、cross-sectionswhere insulation meets and must be adhered to itself or othersystem components.3.2.2 butt jointsCross-sections where two pieces of tubu-lar or sheet insulation must be adhered to itself or other systemcomponents.3.2.3 vapor (water) stopsLocations / methods to preventwater or water vapo
11、r from traveling from one pipe insulationsection to an adjacent insulation and prevent water travelingdown the annular space between the pipe insulation and thetubular pipe.3.2.4 sleeving/multi layeringApplying another layer ofinsulation over the first layer. This process is used when theinsulation
12、thickness required is greater than that which iscommercially available. This technique is also employed whenproper installation practice requires multiple layers and orstaggered joint application, even if a single layer thickness isavailable.1This guide is under the jurisdiction of ASTM Committee C1
13、6 on ThermalInsulation and is the direct responsibility of Subcommittee C16.40 on InsulationSystems.Current edition approved Sept. 1, 2016. Published October 2016. Originallyapproved in 2009. Last previous edition approved in 2015 as C1710 15.DOI:10.1520/C1710-16.2For referenced ASTM standards, visi
14、t the ASTM website, www.astm.org, orcontact ASTM Customer Service at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from MICA(Midwest Insulation ContractorsAssociation) 16712 ElmCircle, Omaha, NE 68130.
15、 http:/www.micainsulation.org.4Available from American Society of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. (ASHRAE), 1791 Tullie Circle, NE, Atlanta, GA30329, http:/www.ashrae.org.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959.
16、United States14. Summary of Guide4.1 Proper insulation thickness shall be installed as specifiedand not compromised. The integrity of the insulation systemshall be maintained throughout the application. Never pull orstretch insulation, always push or over-size insulation.4.2 All seams, butt joints,
17、cutouts and termination pointsshall be sealed with a manufacturers approved adhesive toprevent air/moisture intrusion. For below ambient applications,install vapor stops at all insulation terminations orinterruptions, such as at supports, valves and flanges This canbe accomplished by several methods
18、; by adhering the insula-tion directly to the pipe using a 2 in. (50 mm) strip of contactadhesive or sealant to maintain closure, insulation tape can alsobe used for this purpose by wrapping it around the pipe. Avapor barrier mastic or tape can also be used for this purpose.On straight runs, install
19、 vapor stops every 18 ft (5.4 m) tominimize moisture problems if they occur.4.3 Specific product Manufacturers recommended instal-lation practices shall be used in all cases.4.4 Product should be applied to clean, dry surfaces. If thesystem is operating, additional steps may be needed to insure apro
20、per installation.4.5 A coating, jacket, cladding or appropriate protectionshall be used where mechanical abuse or damage is expected.Outdoor applications may require special consideration referto the manufacturers recommendations.4.6 For satisfactory performance, properly installed protec-tive vapor
21、 retarders/barriers and vapor stops must be used onhigh relative humidity and below ambient temperature appli-cations to reduce movement of moisture through or around theinsulation to the colder interior surface.5. Significance and Use5.1 This guide applies to flexible closed cell insulationtubing a
22、nd sheet materials manufactured according to Specifi-cations C534 and C1427. This standard is intended to providea basic guide for installing these types of materials.5.2 Confirm application use temperature is consistent withspecified use temperature for material as defined in ASTMSpecifications unl
23、ess otherwise agreed upon with the manufac-turer. There are different grades for each of the insulation typesreferred to in this guide, material and grade installed should bethat specified.5.3 This guide is not intended to cover all aspects associatedwith installation for all applications, consult t
24、he National,Commercial Industrial Insulation Standards (MICAManual) orthe specific product manufacturer for recommendations, orboth. (See ASHRAE Handbook (Fundamentals Chapter 26)and ASHRAE Handbook (Refrigeration Chapter 33)6. Workmanship, Finish and Appearance6.1 The insulation shall have no visib
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC17102016STANDARDGUIDEFORINSTALLATIONOFFLEXIBLECLOSEDCELLPREFORMEDINSULATIONINTUBEANDSHEETFORM 板形中

链接地址:http://www.mydoc123.com/p-465613.html