ASTM C1710-2009 Standard Guide for Installation of Flexible Closed Cell Preformed Insulation in Tube and Sheet Form《管状及片状形式的柔性预制闭孔隔热材料安装的标准指南》.pdf
《ASTM C1710-2009 Standard Guide for Installation of Flexible Closed Cell Preformed Insulation in Tube and Sheet Form《管状及片状形式的柔性预制闭孔隔热材料安装的标准指南》.pdf》由会员分享,可在线阅读,更多相关《ASTM C1710-2009 Standard Guide for Installation of Flexible Closed Cell Preformed Insulation in Tube and Sheet Form《管状及片状形式的柔性预制闭孔隔热材料安装的标准指南》.pdf(9页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C1710 09Standard Guide forInstallation of Flexible Closed Cell Preformed Insulation inTube and Sheet Form1This standard is issued under the fixed designation C1710; the number immediately following the designation indicates the year oforiginal adoption or, in the case of revision, the y
2、ear of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This guide covers recommended installation techniquesfor flexible closed cell pre-formed insulation in tube or
3、sheetform. This guide is applicable to materials manufactured inaccordance with Specification C534 (Elastomeric based insu-lation) or Specification C1427 (polyolefin based insulation).The materials covered in this guide encompass a servicetemperature of -297F to 300F ( -183C to 150 C) asindicated in
4、 the material specifications referenced above. Manyof the recommendations made are specific to below ambientapplications only.1.2 The purpose of this guide is to optimize the thermalperformance and longevity of installed closed cell flexibleinsulation systems. By following this guide, the owner, and
5、designer can expect to achieve the energy savings expected andprevention of condensation under the specified design condi-tions. This document is limited to installation procedures anddoes not encompass system design.1.3 The values stated in inch-pound units are to be regardedas standard. The values
6、 given in parentheses are mathematicalconversions to SI units that are provided for information onlyand are not considered standard.1.4 This standard does not purport to address all of thesafety concerns, if any, associated with its use. It is theresponsibility of the user of this standard to establ
7、ish appro-priate safety and health practices and determine the applica-bility of regulatory limitations prior to use.2. Referenced Documents2.1 ASTM Standards:2C168 Terminology Relating to Thermal InsulationC534 Specification for Preformed Flexible Elastomeric Cel-lular Thermal Insulation in Sheet a
8、nd Tubular FormC585 Practice for Inner and Outer Diameters of ThermalInsulation for Nominal Sizes of Pipe and TubingC1427 Specification for Extruded Preformed Flexible Cel-lular Polyolefin Thermal Insulation in Sheet and TubularForm2.2 Other Standards:National Commerical, Industrial Insulation Stand
9、ards(MICA Manual)3ASHRAE Handbook (Fundamentals Chapter 26)4ASHRAE Handbook (Refrigeration Chapter 33)43. Terminology3.1 Definitions:C168 shall be considered as applying to the terms in thisspecification.3.2 Definitions of Terms Specific to This Standard:3.2.1 seamsLongitudinal or horizontal cross-s
10、ectionswhere insulation meets and must be adhered to itself or othersystem components.3.2.2 butt jointsCross-sections where two pieces of tubu-lar or sheet insulation must be adhered to itself or other systemcomponents.3.2.3 vapor (water) stopsLocations / methods to preventwater or water vapor from
11、traveling into or down a tubular pipesection.3.2.4 sleeving/multi layeringApplying another layer ofinsulation over the first layer. This process is used when theinsulation thickness required is greater than that which iscommercially available. This technique is also employed whenproper installation
12、practice requires multiple layers and orstaggered joint application, even if a single layer thickness isavailable.4. Summary of Guide4.1 Proper insulation thickness shall be installed as specifiedand not compromised. The integrity of the insulation system1This practice is under the jurisdiction of A
13、STM Committee C16 on ThermalInsulation and is the direct responsibility of Subcommittee C16.40 on InsulationSystems.Current edition approved Nov. 1, 2009. Published December 2009. DOI:10.1520/C171009.2For referenced ASTM standards, visit the ASTM website, www.astm.org, orcontact ASTM Customer Servic
14、e at serviceastm.org. For Annual Book of ASTMStandards volume information, refer to the standards Document Summary page onthe ASTM website.3Available from MICA (Midwest Insulation Contractors Association) 16712Elm Circle, Omaha, NE 68130. http:/www.micainsulation.org.4Available from American Society
15、 of Heating, Refrigerating, and Air-Conditioning Engineers, Inc. (ASHRAE), 1791 Tullie Circle, NE, Atlanta, GA30329, http:/www.ashrae.org.1Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.shall be maintained throughout the application.
16、 Never pull orstretch insulation, always push or over-size insulation.4.2 All seams, butt joints, cutouts and termination pointsshall be sealed with a manufacturers approved adhesive toprevent air/moisture intrusion. For below ambient applications,install vapor stops at all insulation terminations o
17、r interrup-tions, such as at supports, valves and flanges by adhering theinsulation directly to the pipe using a 2 in. (50 mm) strip ofcontact adhesive or sealant to maintain closure. Insulation tapecan also be used for this purpose. On straight runs, install vaporstops every 18 ft (5.4 m) to minimi
18、ze moisture problems if theyoccur.4.3 Specific product Manufacturers recommended instal-lation practices shall be used in all cases.4.4 Product should be applied to clean, dry surfaces. If thesystem is operating, additional steps may be needed to insure aproper installation.4.5 A coating, jacket, cl
19、adding or appropriate protectionshall be used where mechanical abuse or damage is expected.Outdoor applications may require special consideration referto the manufacturers recommendations.4.6 For satisfactory performance, properly installed protec-tive vapor retarders/barriers and vapor stops must b
20、e used onhigh relative humidity and below ambient temperature appli-cations to reduce movement of moisture through or around theinsulation to the colder interior surface.5. Significance and Use5.1 This guide applies to flexible closed cell insulationtubing and sheet materials manufactured according
21、to Specifi-cation C534 and Specification C1427. This standard is in-tended to provide a basic guide for installing these types ofmaterials.5.2 Confirm application use temperature is consistent withspecified use temperature for material as defined in ASTMSpecifications unless otherwise agreed upon wi
22、th the manufac-turer. There are different grades for each of the insulation typesreferred to in this guide, material and grade installed should bethat specified.5.3 This guide is not intended to cover all aspects associatedwith installation for all applications, consult the National,Commercial Indus
23、trial Insulation Standards (MICAManual) orthe specific product manufacturer for recommendations, orboth. (See ASHRAE Handbook (Fundamentals Chapter 26)and ASHRAE Handbook (Refrigeration Chapter 33)6. Workmanship, Finish and Appearance6.1 The insulation shall have no visible defects that willadversel
24、y affect its performance or appearance. Materials shallbe kept clean and dry until used. Use good quality tools at alltimes. Ensure cleanliness of insulation products, pipe work,vessels, fittings and tools. Avoid dust, dirt, oil or water onsurfaces and equipment. It is recommended to apply insulatio
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC17102009STANDARDGUIDEFORINSTALLATIONOFFLEXIBLECLOSEDCELLPREFORMEDINSULATIONINTUBEANDSHEETFORM 管状

链接地址:http://www.mydoc123.com/p-465610.html