ASTM C1668-2013 Standard Specification for Externally Applied Reflective Insulation Systems on Rigid Duct in Heating Ventilation and Air Conditioning (HVAC) Systems《供暖、通风和空调(HVAC)系.pdf
《ASTM C1668-2013 Standard Specification for Externally Applied Reflective Insulation Systems on Rigid Duct in Heating Ventilation and Air Conditioning (HVAC) Systems《供暖、通风和空调(HVAC)系.pdf》由会员分享,可在线阅读,更多相关《ASTM C1668-2013 Standard Specification for Externally Applied Reflective Insulation Systems on Rigid Duct in Heating Ventilation and Air Conditioning (HVAC) Systems《供暖、通风和空调(HVAC)系.pdf(5页珍藏版)》请在麦多课文档分享上搜索。
1、Designation: C1668 12C1668 13Standard Specification forExternally Applied Reflective Insulation Systems on RigidDuct in Heating, Ventilation, and Air Conditioning (HVAC)Systems1This standard is issued under the fixed designation C1668; the number immediately following the designation indicates the y
2、ear oforiginal adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. Asuperscript epsilon () indicates an editorial change since the last revision or reapproval.1. Scope1.1 This specification covers the requirements and physic
3、al properties of reflective insulation systems applied externally toRigid Heating, Ventilation, and Air Conditioning (HVAC) duct systems operating at or below 250F (121.1 C). These insulationsystems consist of one or more low-emittance surfaces, such as metallic foil or metallic deposits, mounted on
4、 substrates to producereflective air spaces. Reflective insulation systems derive thermal performance from surfaces with an emittance of no greater than0.1 facing enclosed air spaces.1.2 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathema
5、ticalconversions to SI units that are provided for information only and are not considered standard.1.3 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibilityof the user of this standard to establish appropriate safety and heal
6、th practices and determine the applicability of regulatorylimitations prior to use.2. Referenced Documents2.1 ASTM Standards:2C168 Terminology Relating to Thermal InsulationC335 Test Method for Steady-State Heat Transfer Properties of Pipe InsulationC390 Practice for Sampling and Acceptance of Therm
7、al Insulation LotsC411 Test Method for Hot-Surface Performance of High-Temperature Thermal InsulationC1045 Practice for Calculating Thermal Transmission Properties Under Steady-State ConditionsC1258 Test Method for Elevated Temperature and Humidity Resistance of Vapor Retarders for InsulationC1338 T
8、est Method for Determining Fungi Resistance of Insulation Materials and FacingsC1371 Test Method for Determination of Emittance of Materials Near Room Temperature Using Portable EmissometersE84 Test Method for Surface Burning Characteristics of Building MaterialsE96/E96M Test Methods for Water Vapor
9、 Transmission of MaterialsE2231 Practice for Specimen Preparation and Mounting of Pipe and Duct Insulation Materials to Assess Surface BurningCharacteristics2.2 Other Test Method:TAPPI Standard T-512 sp-02 Creasing of Flexible Packaging Material Paper Specimens for Testing33. Terminology3.1 Definiti
10、ons:3.1.1 Unless otherwise noted, the terms used in this specification conform to Terminology C168.3.2 Definitions of Terms Specific to This Standard:1 This specification is under the jurisdiction of ASTM Committee C16 on Thermal Insulation and is the direct responsibility of Subcommittee C16.21 on
11、ReflectiveInsulation.Current edition approved May 1, 2012May 1, 2013. Published May 2012June 2013. Originally approved in 2009. Last previous edition approved in 20102012 asC1668C166810.12. DOI: 10.1520/C166812.10.1520/C166813.2 For referencedASTM standards, visit theASTM website, www.astm.org, or c
12、ontactASTM Customer Service at serviceastm.org. For Annual Book of ASTM Standardsvolume information, refer to the standards Document Summary page on the ASTM website.3 Available from Technical Association of the Pulp and Paper Industry (TAPPI), 15 Technology Parkway South, Norcross, GA 30092, http:/
13、www.tappi.org.This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Becauseit may not be technically possible to adequately depict all changes accurately, ASTM recommends that users con
14、sult prior editions as appropriate. In all cases only the current versionof the standard as published by ASTM is to be considered the official document.Copyright ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States13.2.1 HVAC ductsas pertaining to t
15、his standard, ducts having rigid rectangular or circular cross-section used to transfer airfrom the air handling equipment to the conditioned space and return.3.2.2 insulation spacersmaterial used to form enclosed air spaces that are interior to the reflective insulation system.3.2.3 reflective insu
16、lationthermal insulation consisting of one or more low emittance surfaces, bounding one or more enclosedair space(s). C1684. Classification4.1 Products covered by this specification are classified according to the substrate material and have the physical properties aslisted in Table 1.4.1.1 Type APr
17、oduct with polyethylene foam substrate.4.1.2 Type BProduct with polyethylene bubble pack substrate.4.1.3 Type CProduct with fiberglass substrate.4.1.4 Type DProduct with polyester fiber substrate.4.1.5 Type EProduct with kraft paper substrate.5. Ordering Information5.1 Specify the required thermal r
18、esistance.5.2 Specify the number of layers of insulation, width, thickness of the insulation system and the configuration of the duct(s) tobe insulated.5.3 Special markings, when required, shall be specified.5.4 Special performance requirements, when required.6. Materials and Manufacture6.1 Reflecti
19、ve insulation shall consist of low-emittance surface(s) with substrates and adhesives required to meet the specifiedthermal performance and physical properties. Air spaces shall be maintained by use of insulation spacers.6.2 Multiple layer reflective insulation shall be designed to attain the intend
20、ed separation of layers. The design separation shallbe maintained by the use of proper size, location and method of securing the insulation spacers to the duct system.6.3 DimensionsInsulation and properly sized insulation spacers shall be furnished in dimensions specifically agreed uponbetween the p
21、roducer and the buyer.7. Physical Properties7.1 EmittanceLow-emittance surfaces used for this insulation shall have a surface emittance of 0.1 or less, as determined inaccordance with 10.1.7.2 Water Vapor PermeanceThe water vapor permeance shall be determined in accordance with 10.2 and shall meet t
22、herequirements of Table 1.7.3 Surface Burning CharacteristicsSurface Burning Characteristics shall be determined in accordance with 10.3. Themaximum flame spread index shall not exceed 25 and the maximum smoke developed index shall not exceed 50.7.4 Aging ResistanceThe laminates of the reflective in
23、sulation shall be tested for aging resistance in accordance with 10.4.Three specimens shall be tested. The test specimens shall be shielded from condensate that drips from the ceiling of the humiditychamber during the test.7.4.1 After exposure the specimens shall be evaluated for visible corrosion a
24、nd delamination. For purposes of corrosionevaluation, disregard the outer 0.25 in. (6 mm) perimeter. No tested specimen shall exhibit visible corrosion or unaideddelamination of layers.TABLE 1 Classification CriteriaProperty TypeA TypeB TypeC TypeD TypeEEmittance #0.10#0.10#0.10#0.10#0.10Max. Flame
- 1.请仔细阅读文档,确保文档完整性,对于不预览、不比对内容而直接下载带来的问题本站不予受理。
- 2.下载的文档,不会出现我们的网址水印。
- 3、该文档所得收入(下载+内容+预览)归上传者、原创作者;如果您是本文档原作者,请点此认领!既往收益都归您。
下载文档到电脑,查找使用更方便
10000 积分 0人已下载
下载 | 加入VIP,交流精品资源 |
- 配套讲稿:
如PPT文件的首页显示word图标,表示该PPT已包含配套word讲稿。双击word图标可打开word文档。
- 特殊限制:
部分文档作品中含有的国旗、国徽等图片,仅作为作品整体效果示例展示,禁止商用。设计者仅对作品中独创性部分享有著作权。
- 关 键 词:
- ASTMC16682013STANDARDSPECIFICATIONFOREXTERNALLYAPPLIEDREFLECTIVEINSULATIONSYSTEMSONRIGIDDUCTINHEATINGVENTILATIONANDAIRCONDITIONINGHVACSYSTEMS

链接地址:http://www.mydoc123.com/p-465450.html